Simulation Study of Smoke Control Accordance with Zoning in the Atrium Space of High-rise Buildings (초고층 건물 아트리움 공간에서의 제연구획에 따른 시뮬레이션 연구)

  • Ryu, Hyungkyou;Bae, Sanghwan;Lee, Byungseok
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.26 no.7
    • /
    • pp.335-342
    • /
    • 2014
  • The big issue in fire and life safety protection in atriums is that hot smoke can spread vertically via the atrium openings, and impact atrium floors remote from the fire. Three different strategies to provide fire and life safety protection for atrium space were evaluated in this study, using the FDS model. Strategy A is the atrium protection approach addressed in the Korean Building Fire Protection Code, where atria are required to be enclosed with fire shutters from the $2^{nd}$ floor to the atrium top, and the ground floor is allowed to open to the atrium; in this case, no smoke control is required. Strategy B is the atrium protection approach, with smoke control provided in accordance with NFPA 92B; in this case, no atrium floor is enclosed. Strategy C is the atrium protection approach, in which some of the upper atrium floors are enclosed (the case of the top atrium floor being enclosed is evaluated in this study), and atrium smoke control is also provided to protect the lower atrium floors.

A Numerical Study of Smoke Movement for the Three Types of Atrium Fires using PISO Algorithm (PISO 알고리즘을 이용한 세 가지 형태의 아트리움 공간에서 화재 발생시 연기 거동에 대한 수치해석적 연구)

  • 정진용;유홍선;김성찬
    • Fire Science and Engineering
    • /
    • v.13 no.1
    • /
    • pp.21-30
    • /
    • 1999
  • In this paper, the smoke filling process for the three types of atrium spaces are simulated u using the two types of deterministic fire model; zone models and field models. The zone models u used are the FffiST, CFAST, and CCFM.VENTS m떠els develo야퍼 at the Building and Fire R Research Laboratories, NIST, USA and the NBTC one-room model of FIR.ECAIι delveloped at C CSffiO, Austr;외ia. The field models used are the fire field model developed by W. K Chow and a a self-developed Sl\1EP(Smoke Movement Estimating Program) based on computational fluid d dynamics the$\alpha$1es. The results pn려icted by the two approaches are very similar. The field model u using SIl\1PLE algorithm or SIl\1PLER algorithm requires much more computing time compared w with the use of Sl\1EP using PISO algorithm.

  • PDF

An Application Study on a Strategy to Promote Natural Ventilation at an Atrium Building (아트리움을 이용한 자연환기 활성화 방안에 관한 사례 연구)

  • Shin, Seon-Joon;Lee, Seung-Yeon;Jo, Jin-Kyun;Han, Soo-Gon;Hong, Min-Ho
    • Proceedings of the SAREK Conference
    • /
    • 2008.06a
    • /
    • pp.540-545
    • /
    • 2008
  • An atrium has great potential in natural ventilation aided by buoyance effect. Architectural design of an atrium is very critical to maximize the effect. However, it is not easy of an atrium to have optimum shape for natural ventilation, from the aesthetic and economic point of view. Admitting this condition, we suggested a strategy to promote natural ventilation, which can be adopted only with small design change. At first, we installed BIPV on the top of an atrium to strengthen buoyancy effect, and combine forced ventilation by low pressure fan. To evaluate the performance of the measure, CFD simulation and Energy-Airflow analysis were achieved.

  • PDF

A Study on Planning for Elderly Hospital's Atrium on the base of Users Demand (사용자요구기반에 의한 노인전문병원 아트리움계획 연구)

  • Kim, Yun-Soo;Lee, Yeun-Sook
    • KIEAE Journal
    • /
    • v.13 no.2
    • /
    • pp.101-106
    • /
    • 2013
  • As the number of aged people increase, hospitals specializing in elderly cares have also increased very rapidly. Therefore it is necessary to improve the quality of these hospitals for the elderly people in order to enhance the function of these hospitals not only for conventional treatment but also for recovery and convalescence. To study such trend and needs, this study researched on planning for Elderly Hospital's Atrium that provides a space for the elderly people so that they may enjoy the natural environment while being supported from diverse aspects for long term cares and sustained living, and tried to find out design solutions based on users' demand through questionnaire survey and interviews both with the management of the elderly hospital and the inpatients or the users. As a result of this study, it was revealed that each user showed his or her own respective characteristics concerning his or her expectation about the environment of their using spaces, and according to this result the strategic direction and design plan could be drawn. Based on plans for this Elderly Hospital's Atrium specializing in cares for the elderly people, useful information will be provided for caring, treatment and recovering environment of the elderly hospitals in future considering not only the conventional medical and technical services but also the inpatients' or the users' physical, psychological and social factors.

A Numerical Study for the Atrium Smoke Control by Fire Shutter and Evacuation (방화셔터를 이용한 아트리움 제연과 피난안전에 관한 수치해석 연구)

  • Jeon, Heung-Kyun;Choi, Young-Sang;Choo, Hong-Lok
    • Fire Science and Engineering
    • /
    • v.24 no.5
    • /
    • pp.50-59
    • /
    • 2010
  • Four fire scenarios, as the cases of fire sizes of 2 MW and 5 MW, and no installation and activation of atrium fire shutter for dormitory building of Daegu 'D college', were developed and fire simulations were run using FDS (ver. 5.5.0) and Pathfinder 2009 programs. By assessing fire and evacuation, the effects of atrium fire shutter and vents on the smoke control of atrium were evaluated and this study also analyzed fire hazard and egress safety for occupants in the dormitory. Fire shutter's preventing smoke transport around atrium was much effective, but smoke layer descended down the design limit of smoke height and kept about 2 m height from the atrium floor in all cases because flow rate through vents was not enough. For the case of 5 MW fire and no fire shutter, fire hazard was higher due to visibility than temperature and allowable egress time to stairwell was short less than 5 seconds for the occupants on the floors of 4F to 7F. For total occupants, egress time out of main doorway was calculated about 136 seconds. It is sure that additional systems improving the performance of smoke control need to be installed for more safe evacuation.

A Study of office Building ATRIUM for the using realities (사무소건물 아트리움(ATRIUM) 이용실태에 관한 조사 연구)

  • 장경수
    • Korean Institute of Interior Design Journal
    • /
    • no.1
    • /
    • pp.32-38
    • /
    • 1992
  • The significance of this study is to supply the basic data in the case of planning atrium. the contents is analyzed in the side of functional and architectural seperately and is dealt with the extent of perception on Atrium, the actual conditions of using , the extent of preference and requesting on facilities the feeling of space, the relationship of moving-line with any other places and so on especially, office building.

  • PDF

The Analytical Study of Fire Properties in Atrium Space (아트리움 공간에 있어서 화재온도성상에 관한 이론해석)

  • 김화중;이지희;최금란;김경례
    • Proceedings of the Computational Structural Engineering Institute Conference
    • /
    • 1993.10a
    • /
    • pp.113-119
    • /
    • 1993
  • Atrium being on fire, the flame is spread vertically, the methods of fire protection and the standards of security are different respectively. Therefore, in the case of atrium, it has many problems on the fire protection and the application of statute according to the space properties. So it is important to analysis, atrium being on fire, fire properties to space properties. From these points of view, the purpose of this study is to analysis the fire properties of atrium .

  • PDF

The Experimental Study of Fire Properties in Atrium Space of High-rise Buildings (고층빌딩의 아트리움 공간에 있어서 화재성상에 관한 실험 연구)

  • 김화중;양승호;최금란
    • Fire Science and Engineering
    • /
    • v.7 no.2
    • /
    • pp.13-23
    • /
    • 1993
  • Recently, the plans and constructions of atrium are prevalent widely. But. in the case of atrium it has many problems from the viewpoint of space properties of atrium. Therefore, planning of fire protection is required urgently. The purpose of this study is to analysis the fire properties on the several heights of atrium through three models which the ratio of atrium's width to height is 1:1, 1:1.5 and 1:2 respectively.

  • PDF

Environmental planning of large enclosure (대공간의 환경계획)

  • 손장열
    • The Magazine of the Society of Air-Conditioning and Refrigerating Engineers of Korea
    • /
    • v.28 no.1
    • /
    • pp.1-9
    • /
    • 1999
  • 인간의 생활이 날로 윤택해지고 다양화되며 과학기술이 발달됨에 따라 쾌적하고 거대한 공간에 대한 요구가 커져 가고 있다. 이러한 대공간의 종류에는 종교건축 집회장, 공항 터미널, 역사, 스포츠 시설(실내 체육관, 수영장 등), 공연장, 호텔 등의 대 연회장, 사무소건물 등의 아트리움, 공장 등이 있으며, 우리나라에서도 이미 여러 곳에 대공간의 건물이 건립되었고 앞으로도 보다 많은 대공간의 건립이 예상되고 있다.

  • PDF