• Title/Summary/Keyword: 수격

Search Result 116, Processing Time 0.038 seconds

Two-dimensional unsteady flow analysis with a five region turbulence models for a simple pipeline system (단순한 관망체계에서 5영역 난류 모형을 이용한 2차원 부정류 흐름 해석 연구)

  • Kim, Hyun Jun;Kim, Sangh Hyun;Baek, Da Won
    • Journal of Korea Water Resources Association
    • /
    • v.51 no.11
    • /
    • pp.971-976
    • /
    • 2018
  • An accurate analysis of pipeline transient is important for proper management and operation of a water distribution systems. The computational accuracy and its cost are two distinct components for unsteady flow analysis model, which can be strength and weakness of three-dimensional model and one-dimensional model, respectively. In this study, we used two-dimensional unsteady flow model with Five-Region Turbulence model (FRTM) with the implementation of interaction between liquid and air Since FRTM has an empirical component to be determined, we explored the response feature of two-dimensional flow model. The relationship between friction behaviour and the variation of undetermined parameter was configured through the comparison between numerical simulations and experimental results.

Efficient Calculation of External Flow for Transient Simulation in Pipe Networks (상수관망의 수격현상 모의를 위한 외부 유출입 유량의 효율적해석)

  • Park, Jae-Hong;Han, Geon-Yeon
    • Journal of Korea Water Resources Association
    • /
    • v.34 no.5
    • /
    • pp.427-438
    • /
    • 2001
  • A numerical model to analyze the unsteady flow in water distribution system was developed by using wave adjustment method. When analyzing the unsteady flow in the real water distribution system, the computational procedures are very complex due to the various boundary condition. Wave adjustment method, which can solve the boundary condition more simply and accurately, was introduced to overcome this difficulty and related equations to solve external flow directly were presented. Using these equations, the numerical model was developed to analyze water hammer. The suggested model was applied to a hypothetical distribution system and a real system with 26 pipes with various external flow boundary condition to evaluate the applicability of the developed model. The simulation results by this model agree with those by Karney's analysis in terms of discharge and pressure.

  • PDF

Optimal Design of Hydraulic Device at the Seobyun Pumping Station using Genetic Algorithm (유전자 알고리즘을 이용한 서변 가압장 수리구조물의 최적설계)

  • Jeong, Bong-Seok;Kim, Ju-In;Kim, Sang-Hyeon;Park, Nam-Sik
    • Journal of Korea Water Resources Association
    • /
    • v.33 no.3
    • /
    • pp.289-298
    • /
    • 2000
  • In order to minimize the impact of water hammer In a pipeline, a determination of optimum position of hydraulic structures with best operation of pressure relief valve was explored at the Seobyun pumping station. Method of characteristics is used to simulate a surge impact originating from abrupt stop of pumping operation in a pipeline. Genetic algorithm shows a powerful capability in searching a global solution, especially for a nonlinear problem The application results suggests that the maximum positive pressure can be relaxed by decreasing the opening time of pressure relief valve, meanwhile the maximum negative pressure can be relaxed by increasing the opening time of pressure relief valve. This study shows that the integration of a genetic algorithm with a transient analysis technique such as method of characteristic can improve the design of hydraulic structure in a pipe network.

  • PDF

Customized unsteady analysis and minimization of damage due to unsteady flow in water distribution system (상수관망의 맞춤형 부정류해석 및 부정류피해 최소화 방안)

  • Kwon, Hyuk Jae;Yoo, Min Kyu
    • Proceedings of the Korea Water Resources Association Conference
    • /
    • 2015.05a
    • /
    • pp.287-291
    • /
    • 2015
  • 본 연구에서는 두 지역의 실제 상수관망에 대해서 부정류해석을 수행하였고 각각의 상수관망에 필요한 부정류피해 최소화방안을 제시하였다. 첫 번째 대상지역은 베트남 호치민으로 148개 절점과 162개의 파이프로 이루어진 소블럭 상수관망이며 두 번째 대상지역은 파주시 광탄면으로 512개 절점과 527개의 파이프로 이루어진 세 개의 소블럭 상수관망이다. 두지역의 상수관망은 지형적면이나 규모면에서 다른 모습을 하고 있기 때문에 부정류해석 시 발생가능한 피해유형이 틀린 것으로 나타났다. 호치민의 경우 배수지의 높이가 낮고 도시 내 표고차가 없어서 관망 내 평균수압이 $1kg/cm^2$을 약간 상회하는 수준으로 수압이 낮고 수압차 역시 작다. 따라서 상수관망에서 일어날 수 있는 소요수량의 변화나 소화전 사용과 같은 작은 변화에도 역류발생이 빈번히 일어나는 것으로 나타났으며 역류발생이 잦은 파이프를 선정할 수 있었다. 상당히 많은 파이프에서 단기간 역류가 발생하는 것을 확인할 수 있었다. 짧은 기간에 발생하는 변화에 대한 단기간 역류는 교차연결(Cross-Connection)의 문제를 야기할 수 있다. 따라서 역류발생이 빈번히 일어나는 파이프 주위에 check valve나 역지밸브등의 설치를 통해 역류로 인한 피해를 최소화할 수 있다. 파주시 광탄면 지역의 소블럭 집합으로써 고저차가 많은 지역이다. 배수지 밸브개폐 시 발생 가능한 수충격에 대한 시뮬레이션과 펌프장정지로 인해 발생할 수 있는 수충격에 발생 시뮬레이션을 수행하였고 관망내에서 자주 발생하는 밸브개폐로 인한 시뮬레이션을 수행하였다. 그 결과 광탄의 경우 수충격 발생위험 지점은 배수지 근처로 나타났고 수격압이 최대 $2.5kg/cm^2$에서 $3.0kg/cm^2$까지 발생 가능한 것으로 나타났고 밸브개폐시간이 1-2초 지연되어도 상당히 큰 수격압을 줄일 수 있는 것으로 나타났다. 수충격압이 크게 발생할 수 있는 지역에 수충격피해 최소화를 위해 surge tank와 같은 장치를 설치해야 한다. 또한 발생가능한 수격압의 크기를 통계적기법을 통해 확률밀도함수로 나타낼 수 있었다. 이 결과는 앞으로 상수관망의 설계나 운영에서 수충격피해 방지 장치 및 설비를 시공할 때 장치의 규모나 용량을 결정할 때 유용한 정보가 될 것으로 판단된다.

  • PDF