• Title/Summary/Keyword: 대심도 지하역사

Search Result 11, Processing Time 0.025 seconds

THE STUDY ON THE CHARACTERISTICS OF FIRE DRIVEN SMOKE-FLOW FOR DIFFERENT FIRE-LOCATION IN DEEPLY UNDERGROUND SUBWAY STATION (대심도 지하역사에서 화원 위치에 따른 연기거동 특징 연구)

  • Kim, H.B.;Jang, Y.J.;Lee, C.H.;Jung, W.S.
    • 한국전산유체공학회:학술대회논문집
    • /
    • 2009.04a
    • /
    • pp.202-207
    • /
    • 2009
  • In this study, Numerical simulations were performed to analyze the characteristics of fire driven smoke flow for different location of fire source in the deeply underground subway station with using FDS code. The fire driven smoke-flow which was simulated by using Parallel Computational Method for fast calculation and LES for turbulence model. In this research, the fire location to obstruct a suitable egress from the fire disaster were discussed.

  • PDF

THE COMPARISON ON THE CHARACTERISTIC OF THE FIRE DRIVEN SMOKE-FLOW FOR THE PLATFORM TYPES IN THE DEEPLY UNDERGROUND SUBWAY STATION (대심도 지하철 승강장의 종류별 연기전파특성 비교고찰)

  • Kim, H.B.;Jang, Y.J.;Lee, D.H.;Jung, W.S.;Whang, H.B.
    • 한국전산유체공학회:학술대회논문집
    • /
    • 2010.05a
    • /
    • pp.505-507
    • /
    • 2010
  • In this paper, the comparison on the fire driven smoke flow for platform types was conducted in the Deeply Underground Subway Station. Soongsil-University station (47m depth) as a bank type platform and Mandeok Station as a island type platform were selected for fire numerical simulation. The characteristics of fire driven smoke-flows were analyzed from the simulation results. The proper plan of evacuation against fire for each type was considered through the results.

  • PDF

The Study on Fire Phenomena in The Deeply Underground Subway Station (대심도 지하역사에서의 화재현상 연구)

  • Jang, Yong-Jun;Kim, Hag-Beom;Lee, Chang-Hyun;Jung, Woo-Sung
    • Proceedings of the KSR Conference
    • /
    • 2008.06a
    • /
    • pp.1773-1780
    • /
    • 2008
  • When the fire occur in the deeply underground subway station, the difficulties of passenger evacuation are expected because of many stairs to the exit. In this study, SOONGSIL-University station (7 line, 47m depth) is the one of the deepest subway stations of the each line in the Seoul metro. The numerical computational-simulation was performed for the fire driven flow in the subway station. Hot and smoke flow was analyzed from the simulation results. The proper plan of evacuation against fire was considered through the results. The fire driven flow was simulated using FDS code in which LES method was applied. The Heat Release Rate was 10MW and the ultrafast model was applied for the growing model of the fire source. The proper mesh size was determined from the characteristic length of fire size. The parallel computational method was employed to compute the flow and heat eqn's in the meshes, which are about 10,000,000, with 6cpu of the linux clustering machine.

  • PDF

Investigation for Fire Flow of the Deeply Underground Shin-Gum-Ho Subway Station (대심도 신금호역사의 화재 유동에 대한 고찰)

  • Jang, Yong-Jun;Park, Il-Soon;Kim, Jin-Ho;Jung, Woo-Sung;Kim, Hag-Beom;Lee, Chang-Hyun
    • Proceedings of the KSR Conference
    • /
    • 2010.06a
    • /
    • pp.110-115
    • /
    • 2010
  • Recently the deeply underground tunnels have been increased along the subway railroads of urban area compared to the past subway railroads. The Shin-Gum-Ho subway station (the Fifth lines, the depth : 46m) which is the third among the deep subway stations in the Korea was chosen as the model of deeply underground stations, and attempted to do simulation of fire. This station consists of three entrance, the basement first floor (B1), the basement second floor (B2), the basement eighth floor or platform (B8) and escalators and stairs from B2 to B8. The total number of grid was about 9,000,000 to make simulation of fire and smoke from the platform to entrance in this research, and the grid system was divided into 19 blocks to increase the efficiency of this simulation. The FDS (Fire Dynamics Simulation) was chosen to make the simulation of fire, and the model of turbulent flow was LES (Large Eddy Simulation). Each block is processed in a CPU using parallel processing of MPI (Message Passing Interface). The resource of CPU for this simulation is a ten of Intel 3.0 GHz Dual CPU (20 CPU).

  • PDF

Numerical Study on the characteristics of fire driven flow for smoke ventilation system operating in the deeply underground subway station (대심도 지하역사에서의 화재시 급 배기 동작유무에 따른 열 연기 거동 분석)

  • Jang, Yong-Jun;Kim, Hag-Beom;Lee, Chang-Hyun;Jung, Woo-Sung
    • Proceedings of the KSR Conference
    • /
    • 2008.11b
    • /
    • pp.66-72
    • /
    • 2008
  • In this study, transient 3D numerical simulations were performed to analyze the characteristics of fire driven flow for smoke ventilation system operating conditions in the deeply underground subway station. The smoke flow patterns were compared and discussed under smoke fan operating mode and off mode in the platform. Soongsil Univ. station(line number 7)was chosen for simulation which was the one of the deepest underground subway stations in the each lines of Seoul. The geometry for model is 365m in length include railway, 23.5m for width, 47m for depth. Therefore 10,000,000 structured grids were used for fire simulation. The parallel computational method for fast calculation was employed to compute the heat and mass transfer eqn's with 6 CPUs(Intel 3.0GHz Dual CPU, 12Cores) of the linux clustering machine. The fire driven flow was simulated with using FDS code in which LES method was applied. The Heat release rate was 10MW and The Ultrafast model was applied for the growing model of the fire source.

  • PDF

Smoke Control Experiment of a Very Deep Underground Station Where Platform Screen Doors are Installed (I) - Analysis on Smoke Control Performance on the Platform (스크린도어가 설치된 대심도 지하역사의 제연 실험 I - 승강장에서의 제연의 효과 분석)

  • Park, Won-Hee;Kim, Chang-Yong;Cho, Youngmin;Kwon, Tae-Soon;Lee, Duck-Hee
    • Asia-pacific Journal of Multimedia Services Convergent with Art, Humanities, and Sociology
    • /
    • v.8 no.7
    • /
    • pp.485-496
    • /
    • 2018
  • In this paper, the smoke behavior in an underground station on operation of the fans in the ventiliation of the station was measured by the experimental method when the fire occurred in the underground station platform where the platfrom screen door was installed. The ventilation characteristics were compared when the ventilation system was operated and when the ventilation system was not operated when a fire occurred at the platform where the clean door was closed. To simulate the fire smoke, the smoke generated from the smoke generator was heated using a hot air fan. The transmittance was measured using a smoke density meter to quantitatively measure fire smoke. If the screen door is closed and the ventilation system of the underground station does not work, it is confirmed that if a fire occurs in the platform, smoke accumulates inside the platform, evacuating passengers is very difficult and can lead to a very dangerous situation. On the other hand, under the condition that the ventilation facility of the subway station is operated, the smoke evacuates to the outside through the ventilation facility of the underground station, and airflow is formed in the direction from the waiting room to the waiting area, so that the passenger located on the platform can safely evacuate toward the concourse. In the following paper, we will discuss the concurrent effect of tunnel ventilation through tunnel vent near the platform.

Numerical Study on the Smoke Movement and Evacuation in the Deeply Underground Subway Station Fire (대심도 지하역사에서의 화재시 연기거동과 피난에 대한 수치해석 연구)

  • Kim, Hong-Jin;Bae, Sung-Yong;Choi, Young-Ki;Hong, Gi-Bae;Ryou, Hong-Sun
    • Proceedings of the KSR Conference
    • /
    • 2011.10a
    • /
    • pp.1342-1347
    • /
    • 2011
  • Advantages of the deeply underground subway are underground space efficiency, high speed, decrease of noise and vibration. However, when fire occurs in the deeply underground subway station, large casualties are occurred like Daegu subway station fire due to the increase of evacuation distance. In this study, a numerical analysis was performed by using the fire and evacuation analysis program FDS+EVAC for smoke movement and evacuation in Beotigogae station among the deeply underground subway station. Heat release rate of carriage fire was set 10MW and the fire growth rate was ultrafast. As a result, the smoke move to the exit at 1085 second. The total evacuation time took 956 second.

  • PDF

Experimental Study for the Capacity of Ordinary and Emergency Ventilation System in Deeply Underground Subway Station (대심도 지하역사 승강장 및 대합실 평상시/비상시 급·배기 풍량에 대한 실험적 연구)

  • Jang, Yong-Jun;Lee, Ho-Seok;Park, Duck-Shin
    • Journal of the Korean Society for Railway
    • /
    • v.15 no.6
    • /
    • pp.579-587
    • /
    • 2012
  • Shin-gumho station in Seoul underground subway have been selected to be experimentally investigated and analyzed for the real air supply & exhaust capacity compared to the original capacity of ordinary and emergency condition. The depth of Shin-gumho station is 43.6m which consists of the island-type platform ($8^{th}$ floor in underground) and a two-story lobby (first & second floor in underground). An emergency staircase connects between the platform and the lobby. Hot-wire anemometer, capture hood, wind vane & velocity meter and data acquisition systems are employed to perform the automatic measurement in this experiment. For ordinary case, air supply and exhaust capacity in the lobby were reduced by 34% and 46% compared to the original capacity, respectively. Air supply and exhaust capacity in the platform were reduced by 66% and 38%, respectively. For emergency case, air supply in the lobby was reduced by 42% and air exhaust in the platform was reduced by 28% compared to the original capacity. Therefore, air pollution in the station is expected to be worse in the ordinary environment and smoke control capability in the platform will be weakened in case of fire emergency.

Smoke Control Experiment of a Very Deep Underground Station Where Platform Screens Doors are Installed - Analysis on Smoke Control Performance by Fans equipped in Tunnel (스크린도어가 설치된 대심도 지하역사의 제연 실험 - 터널 송풍기에 의한 제연의 효과 분석)

  • Park, Won-Hee;Kim, Chang-Yong;Cho, Youngmin
    • Asia-pacific Journal of Multimedia Services Convergent with Art, Humanities, and Sociology
    • /
    • v.9 no.9
    • /
    • pp.721-736
    • /
    • 2019
  • In this paper, the behavior of the fire smoke due to the operation of the ventilation systems when the fire occurred in the underground station (6 basement floors) and the tunnel at the great depth was measured. Fire smoke was generated by using a smoke generator which realized heat buoyancy effect by using hot air blower. The two locations of the fire were selected on the platform and on the platform of the tunnel located outside the screen door. A ventilation mode is generally used in which smoke is exhausted through a vent hole provided in a platform when a platform fire occurs. The tests were performed by operating the exhaust through the ventilation holes of the tunnel part located at both ends of the platform. The smoke density and the wind speed/velocity were measured at various positions, and the videos were taken to analyze the movement and smoke of the smoke. In both cases for fire inside the platform and in the railway tunnel, due to the ventilation mode operation of the fan for the platform and the exhaust of the fans in the tunnel smoke were well exhausted and the smoke propagation to the area near the smoke zone was suppressed. The smoke-control mode, which is applied to both fans for the platform and fans for in the tunnel at both ends of the platform, can provide a safer evacuation environment to the passengers from the fire smoke when the platform fire or fire train stops.

Optimal Deployment for Evacuation Safety Zone at Intermodal Transfer Station (복합환승센터 피난대피구역 적정 배치 방법론 개발)

  • You, So-Young;Jeong, Eunbi
    • The Journal of The Korea Institute of Intelligent Transport Systems
    • /
    • v.18 no.1
    • /
    • pp.27-42
    • /
    • 2019
  • It is not easy to evacuate when people face with emergency situation in deep underground space because space perception and synthetic judgement are readily lowered. In stead of evacuating safely outside within the given time, evacuation safety zone is required to be designed and installed. In this study, PATS (Pedestrian movement based Assessment Toolkit for Simulation) is applied to build a comprehensive and analytic framework for seeking the optimal (or proper) numbers and locations of evacuation safety zone. With two scenarios of emergency situation at intermodal transfer center with the 6 floor in underground, the problematic location on the evacuation path has been identified and the proper locations has been presented.