• Title/Summary/Keyword: 냉매 407C

검색결과 51건 처리시간 0.018초

대체냉매 R407C 및 R410A를 이용한 슬릿휜-관 열교환기의 응축특성에 관한 연구 (An Experimental Study on Condensation Characteristics of Slit Fin-tube Heat Exchanger Using Alternative Refrigerants, R407C and R410A)

  • 전창덕;장경근;강신형;이진호
    • 설비공학논문집
    • /
    • 제14권9호
    • /
    • pp.706-716
    • /
    • 2002
  • R410A and R407C are considered to be alternative refrigerants to R22 for the air-conditioners. Experimental investigation is made to study the condensation heat transfer characteristics of slit fin-tube heat exchanger using alternative refrigerants R410A and R407C. R407C, a non-azeotropic refrigerant mixture, exhibited a quite different condensation phenomenon from those of R22 and R410A and its condensation heat transfer coefficient was much lower than that of R22 and R410A. Between the R22 and R410A, the condensation heat transfer coefficient of R410A, near-azeotropic refrigerant mixture, was a little higher than that of R22. R410A also showed the lowest condensation pressure drop across the test section. For all refrigerants, the condensation heat transfer coefficient and pressure drop increase as the mass flux increases.

대체냉매를 사용한 에어콘에서 합성오일과 건조제(M/S)의 영향 (Effects of Refrigerant Oils and Molecular Sieve on Air Conditioner using Alternative Refrigerant)

  • 좌성훈;홍정기;김창국;윤백;강석춘
    • 설비공학논문집
    • /
    • 제8권4호
    • /
    • pp.473-483
    • /
    • 1996
  • To protect the ozone layer, R22 will be replaced with HFCs. R407C is a leading candidate as alternative refrigerant for air conditioner due to its similar thermodynamic characteristics with R22. In replacing R22 with R407C, the compatibility with lubricating oil is of major concern. Polyol ester (POE) oil among the synthetic oils is considered to be the best lubricant for use with R407C because of good electrical properties and miscibility. However, lubricating ability of mixture of R407C/POE oil is lower than that of R22/mineral oil due to the production of acid by hydrolysis which causes corrosive wear. Therefore, to minimize water content, it is needed to develop a molecular sieve desiccant which is compatible with R407C and ester oil. This paper discusses (1) the change of properties of POE oil when current molecular seive is used, (2) the effects of POE oils and additives on durability of compressor. Through compressor life test and bench wear test, it was found that inadequate use of POE oils and additives may promote the deteriation of molecular sieve, resulting in decrease of durability of compressor.

  • PDF

수평관내 3성분 혼합냉매의 강제대류비등 열전달 (Forced convective boiling heat transfer for a ternary refrigerant mixture inside a horizontal tube)

  • 오종택
    • 설비공학논문집
    • /
    • 제11권6호
    • /
    • pp.912-920
    • /
    • 1999
  • The forced convective boiling heat transfer coefficients of R-407C were measured inside a horizontal tube 6.0mm I.D. and 4.0m long. The heat transfer coefficients increased according to an increase in heat flux at constant mass flux. Because nucleation was completely suppressed in the two-phase flow region with high quality, heat transfer coefficients in forced convective evaporation were higher than those in nucleate boiling region. Average heat transfer coefficients of R-407C were about 30 percent lower than the pure refrigerant correlation, due to mass transfer resistance at the gas-liquid interface. However, the total experimental data shows an agreement with the predicted data for ternary refrigerant mixtures with a mean deviation of 30%.

  • PDF

수평 평활관 및 전열촉진관내 대체 냉매 R-407C의 응축 열전달 특성에 관한 연구 (Heat Transfer Characteristics of R-407C During Condensing Inside Horizontal Smooth and Micro-Fin Tubes)

  • 노건상;오후규
    • 대한기계학회논문집B
    • /
    • 제23권2호
    • /
    • pp.210-217
    • /
    • 1999
  • This paper reports the experimental results on heat transfer characteristics of R-22 and R-407C(HFC-32/125/134a 23/25/52 wt%) condensing inside horizontal smooth and finned tubes. The test condensers used In the study are double pipe heat exchangers of 7.5 mm ID, 9.5 mm OD smooth tube, and 60 finned micro-fin tube with 8.53 mm ID, 9.53 mm OD. Each of these tubes was 4 000 mm long tubes connected with an U-bend. These U type two-path test tubes are divided In 8 local test sections for the identification of the local condensing heat transfer characterisitcs and pressure drop, U-bend effects on condensing flows. Inlet quality is maintained 1.0, and refrigerant mass velocity is varied from 102.0 to $301.0kg/m^2{\cdot}s$. From the results, it was found that the pressure drop of the R-407C Increased, and heat transfer coefficient decreased compared to those of R-22. In comparison condensing heat transfer characteristics of micro-fm tube with those of smooth tube, increasing of condensing heat transfer coefficient was found outstanding compared to the increasing ratio of pressure drop. Furthermore, pressure drop In U-bend showed at most a 30 % compared to the total pressure drop in the test section.

수평관에서 R22 대체냉매 및 R134a의 포화증기 온도변화에 따른 외부 응축 열전달계수에 관한 연구 (External Condensation Heat Transfer Coefficients of R22 Alternative Refrigerants and R134a According to the Saturated Vapor Temperature Change on a Smooth Tube)

  • 유길상;황지환;박기정;정동수
    • 설비공학논문집
    • /
    • 제17권8호
    • /
    • pp.729-735
    • /
    • 2005
  • In this study, external condensation heat transfer coefficients (HTCs) were measured on a horizontal smooth tube at the saturated vapor temperature of $30^{\circ}C,\;39{\circ}C,\;and\;50^{\circ}C$ for R22, R410A, R407C, and R134a with the wall subcooling of $3\~8^{\circ}C$. The HTCs of all refrigerants are the highest at $30^{\circ}C,\;39{\circ}C,\;and\;50^{\circ}C$ in order. This trend is due to its excellent thermodynamic properties of the liquid phase. The measured data of HTCs were compared with the calculated ones by Nusselt's equation for a smooth tube. Measured HTCs of R22, R134a, R410A are $4.2\~7.5\%$ higher than prediction respectively while those of R407C are $15.6\~28.9\%$ lower than the prediction.

응축압력 변화에 따른 R407C의 응축특성에 관한 연구 (An Experimental Study on Condensation Characteristics at Various Condensation Pressure of R407C)

  • 전창덕;장경근;김창덕;이진호
    • 설비공학논문집
    • /
    • 제15권3호
    • /
    • pp.230-238
    • /
    • 2003
  • R407C is considered as alternative refrigerant of R22 for air conditioners. Experimental investigation is made to study the condensation heat transfer characteristics of slit fin-tube heat exchanger using alternative refrigerant, R407C. Experiments are carried out at condensation pressure of 2110 kPa and 1943 kPa with the degree of superheat of 1$0^{\circ}C$ and mass flux varying from 150 to 250 kg/$m^2$s for refrigerant side. The inlet air condition is dry bulb temperature of 35$^{\circ}C$, relative humidity of 50% and air velocity varying from 0.8 to 1.6 m/s. Experiments show that pressure drop gets smaller at a higher condensation pressure especially when condensation pressure is raised from 1943 to 2110 kPa. Heat transfer rate gets smaller at a lower condensation pressure in the range of experimental condition.

대체냉매 R-407C와 R-410A를 사용하는 냉동시스템의 오일농도 예측에 관한 연구 (A study on prediction of oil concentration in the R-407C and R-410A refrigeration system)

  • 이종문;김창년;박영무
    • 설비공학논문집
    • /
    • 제11권3호
    • /
    • pp.384-390
    • /
    • 1999
  • A vibrating U-Tube decimeter has been evaluated as a sensor for measuring the concentration of oil in the liquid line of a refrigeration system. Calibration and performance tests were conducted under simulated liquid-line conditions for R-407C/POE oil and R-410A/POE oil mixtures in oil concentration from 0 to 15 weight percent. Test temperatures ranged from 20 to 5$0^{\circ}C$. As a result of test, oil concentration correlations are presented in terms of specific gravity at each constant temperature. These equations enable to predict the oil concentration without any extraction of the mixture, and can be applied for R-407C/POE oil and R-410A/POE oil mixtures.

  • PDF

동일한 유입온도조건에서 R407C와 R22 적용 응축기의 특성비교 (Comparison of Condenser Characteristics Using R407C and R22 on the Same Inlet Temperature Condition)

  • 김창덕;전창덕;이진호
    • 설비공학논문집
    • /
    • 제15권7호
    • /
    • pp.595-603
    • /
    • 2003
  • R407C is considered as an alternative refrigerant to R22 for air conditioners. An experimental investigation was made to study the characteristics of the condensation heat transfer and pressure drop for R407C flowing in a fin-and-tube heat exchanger used for commercial air-conditioning units. Experiments were carried out under the conditions of inlet refrigerant temperature of 6$0^{\circ}C$ and refrigerant mass flux varying from 150 to 250 kg/$m^2$s for refrigerant side. The inlet air has dry bulb temperature of 35$^{\circ}C$ , relative humidity of 50% and air velocity varying from 0.8 to 1.6 m/s. Experiments show that air velocity increased by 25% is needed for R407C than that of R22 for subcooling temperature of 5$^{\circ}C$, which resulted in air-side pressure drop increase of 28.8% for R407C as compared to R22. As a consequence, in order to provide the same design condition of a condenser, the fan requires higher electric-power consumption with R407C than that with R22.

R-22 대체용 혼합냉매의 열역학적 성능에 대한 실험연구 (An experimental investigation of thermodynamic performance of R-22 alternative blends)

  • 황의필;김창년;박영무
    • 설비공학논문집
    • /
    • 제9권1호
    • /
    • pp.82-91
    • /
    • 1997
  • R-410a and R-407c witch have the best potential among the substances being considered as R-22 alternatives were tested as "drop in" refrigerants against a set R-22 baseline tests for comparison. The performance evaluations were carried out in a psychrometric calorimeter test facility using the residential split-type air conditioner under the ARI rating conditions. Other than the use of different lubricant and a hand-operated expansion valve, one of the commercial systems was selected for the experiment. Performance characteristics were measured; compressor power, capacity, VCR, mass flow rate and COP. The tests showed that R-407c can be directly applied to the existing refrigeration system because of its similar vapor pressure and other thermopysical properties with those of R-22. However, it required change to the volume flow rate of compressor in order to achieve the similar performance with R-22 because of its relatively small VCR and capacity. Meanwhile, R-410a has too high a vapor pressure to be applied to the existing system and this feature results in relatively low COP of the system compared to that of R-22. But this could be improved by changing compressor design considering R-410a's relatively high VCR and capacity compared to those of R-22.

  • PDF