Browse > Article

Comparison of Condenser Characteristics Using R407C and R22 on the Same Inlet Temperature Condition  

김창덕 (㈜센추리 기술연구소)
전창덕 (충주대학교 기계공학과)
이진호 (연세대학교 기계공학과)
Publication Information
Korean Journal of Air-Conditioning and Refrigeration Engineering / v.15, no.7, 2003 , pp. 595-603 More about this Journal
Abstract
R407C is considered as an alternative refrigerant to R22 for air conditioners. An experimental investigation was made to study the characteristics of the condensation heat transfer and pressure drop for R407C flowing in a fin-and-tube heat exchanger used for commercial air-conditioning units. Experiments were carried out under the conditions of inlet refrigerant temperature of 6$0^{\circ}C$ and refrigerant mass flux varying from 150 to 250 kg/$m^2$s for refrigerant side. The inlet air has dry bulb temperature of 35$^{\circ}C$ , relative humidity of 50% and air velocity varying from 0.8 to 1.6 m/s. Experiments show that air velocity increased by 25% is needed for R407C than that of R22 for subcooling temperature of 5$^{\circ}C$, which resulted in air-side pressure drop increase of 28.8% for R407C as compared to R22. As a consequence, in order to provide the same design condition of a condenser, the fan requires higher electric-power consumption with R407C than that with R22.
Keywords
Alternative refrigerant; R407C; Condensation; Heat transfer rate; Pressure drop;
Citations & Related Records
Times Cited By KSCI : 4  (Citation Analysis)
연도 인용수 순위
1 Horizontal flow boiling of R22 and R407C in a 9.52mm micro-fin tube /
[ Kuo,C.S.;Wang,C.C. ] / Applied Thermal Engineering   ScienceOn
2 Experimental investigation on condensation heat transfer and pressure drop of new HFC refrigerants /
[ Cavallini,A.;Censi,G;Col,D.;Doretti,L.;Longo,G.A.;Rossetto,L. ] / International Journal Refrigeration   ScienceOn
3 Flow boiling heat transfer characteristics of R22 alternative refrigerants in a horizontal smooth tube /
[ Han,J.U.;Kim.S.J.;jung,D.S.;Kim,Y.I. ] / Korean Journal of Air-Conditioning and Refrigerating Engineering   과학기술학회마을
4 /
[ ASHRAE ] / Fundamental Handbook(SI)
5 Describing uncertainties in single sample experiments /
[ Kline,S.J.;McClintock,F.A. ] / Mechanical Engineering
6 A study thermal performance of air-cooled heat exchangers using alternative refrigerant /
[ Ebisu,T.;Kasai,D.;Torikoshi,K. ] / 33rd National Heat Transfer Symposium of Japan
7 Heat transfer prediction of air-to-refrigerant two-phase flow boiling of alternatives to HCFC-22 inside air/refrigerant enhanced surface tubing /
[ Sami,S.M.;Grell,J. ] / Journal of Energy Research   ScienceOn
8 /
[ McLinden,M.O.;Klein,S.A.;Lemmon,E.W.;Peskin,A.P. ] / Thermodynamic and transport properties of refrigerants and refrigerant mixtures database(REFPROP) Ver.6.01
9 Two-phase heat transfer characteristics for R22/R407C in a 6.5mm smooth tube /
[ Wang,C.C.;Chiang,C.S. ] / Int. J. Heat and Fluid Flow   ScienceOn
10 An experimental study on condensation characteristics at various condensation pressure of R407C /
[ Jeon,C.D.;Jang,K.K.;Kim,C.D.;Lee,J. ] / Korean Journal of Air-Conditioning and Refrigerating Engineering   과학기술학회마을
11 Experimental study on evaporation and condensation heat transfer enhancement for R-407C using herringbone heat transfer tube /
[ Ebisu,T.;Torikoshi.K. ] / ASHRAE Transaction, Symposia
12 An experimental study on condensation characteristics of slit fin-tube heat exchanger using alternative refrigerants,R407C and R410A /
[ Jeon,C.D.;Jang,K.K.;Kang,S.H.;Lee,J. ] / korean Journal of Air-Conditioning and Refrigerating Engineering   과학기술학회마을
13 Montreal Protocol on Substance that Deplete the Ozone Layer /
[] / Final Act, United Nations Environment Programme