Forced convective boiling heat transfer for a ternary refrigerant mixture inside a horizontal tube

수평관내 3성분 혼합냉매의 강제대류비등 열전달

  • 오종택 (여수대학교 냉동공학과)
  • Published : 1999.11.01

Abstract

The forced convective boiling heat transfer coefficients of R-407C were measured inside a horizontal tube 6.0mm I.D. and 4.0m long. The heat transfer coefficients increased according to an increase in heat flux at constant mass flux. Because nucleation was completely suppressed in the two-phase flow region with high quality, heat transfer coefficients in forced convective evaporation were higher than those in nucleate boiling region. Average heat transfer coefficients of R-407C were about 30 percent lower than the pure refrigerant correlation, due to mass transfer resistance at the gas-liquid interface. However, the total experimental data shows an agreement with the predicted data for ternary refrigerant mixtures with a mean deviation of 30%.

Keywords