• 제목/요약/키워드: 국소배기

검색결과 65건 처리시간 0.018초

공동주택의 국소배기용 루프팬 성능개선에 관한 연구 (Study on the Performance Improvement of Roof Fan Used for Local Exhaust System Installed in Apartment)

  • 권용일;정열화;안정헌
    • 설비공학논문집
    • /
    • 제24권2호
    • /
    • pp.136-141
    • /
    • 2012
  • Performance improvement of local exhaust system used in toilet and cooking place are main concern in a field of ventilation. In Korea, There are many high riser residential apartments in recent years. These buildings were not viewed as being major contributors to exhaust pollutants producted in indoor. It was because many engineers thought that exhaust in high riser building depends on stack effect. This study investigates on the performance improvement of terminal device, roof fan, of vertical spiral duct used in high riser residential apartments. This paper focuses mainly on the effect of accessories, number or shape of blades, composed of roof fan with function of exhaust air volume of toilet and cooking place. Roof fan with 10 blades is observed at optimum exhaust performance in this study.

반밀폐형 공간에서 비등온 고농도 연무의 배연산출량 산정을 위한 Froude 상사연구 (The Froude Scaling Study on the Ventilation of Non-isothermal Concentrated Fume from the Semi-closed Space)

  • 장혁상;최병일;박재철;김명배
    • 대한환경공학회지
    • /
    • 제27권8호
    • /
    • pp.877-885
    • /
    • 2005
  • 반 밀폐형 공간에서 발생되는 비등온 고농도의 연무를 제거하기 위해 필요한 배연량 산정을 위한 실형과 모형사이의 Froude 상사연구를 시행하였다. Zukoski의 연무상승 방정식을 기반으로 하는 무차원 상사방정식을 구성한 다음 체적 $1\;m^3(1\;m\;{\times}\;1\;m\;{\times}\;1\;m)$인 모형 A와 체적 $0.125\;m^3(0.5\;m\;{\times}\;0.5\;m\;{\times}\;0.5\;m)$인 모형 B를 사용하여 기하학적 상사성에 따른 파라메터인 무차원 에너지방출량과 무차원 질량유량과의 상관관계를 실험적으로 평가하였다. 실험적 결과는 고농도 배연에 관련하며 구성된 이론적 상사가 타당함을 보여주었고 본 연구에서 구성된 이론적 방정식이 범용으로 적용될 수 있음을 보여 주었다. 본 연구의 실험조건에서 제어공간에 투입된 최대 에너지량은 $20\;kW/m^3$이며 이 범위 이하의 열량 투입조건에서 배연량 대비 에너지 투입양 간의 상사가 잘 이루어졌다. 연구 범위의 에너지 투입조건에서 열적영향에 의한 필요 배연량의 증가는 단순한 양론적 추정 배연량에 비해 20-30% 추가되는 것으로 나타났다. 본 연구 자료를 바탕으로 고농도 비등온 조건에서 열부력 및 확산효과에 의해 이탈되는 제어대상 연무를 효율적으로 제어하기 위한 국소배기시스템의 설계 개선을 가져 올 수 있다.

대형 주물공정 용접작업장의 건강 위해인자 및 환기 개선 (Health Risk Factors and Ventilation Improvements in Welding Operation at Large-sized Casting Process)

  • 정종현;정유진;이상만;이정희;손병현;임현술
    • 청정기술
    • /
    • 제20권2호
    • /
    • pp.171-178
    • /
    • 2014
  • 이 연구에서는 대형 주물공정 용접작업장 근로자들의 건강보호 및 작업환경 개선을 위해 위해인자 조사 및 분석작업을 수행하였다. 또한, 대상 작업장의 작업환경을 개선하기 위해 측정 및 전산유체해석 모델링을 수행한 후 효과적인 환기방법을 제안하였다. 대형 주물공정 용접작업장 근로자들의 건강 위해인자를 조사한 결과, A사는 산화철분진, B사와 C사는 용접흄, D사는 용접 흄과 산화철분진이 주오염원인 것으로 확인되었다. 작업자 호흡영역에서의 흄 농도는 $0.05{\sim}4.37mg/m^3$이었고, 용접작업장 공기 중 흄 농도는 $0.13{\sim}7.54mg/m^3$이었다. 또한, 용접작업 시 최적의 환기방법을 제안하기 위해 측정 및 전산유체해석 모사를 수행한 결과, 배기공정의 경우에는 배기 덕트를 용접점에 근접시켜 국소배기를 실시하는 것이 효과적인 것으로 나타났다. 급기공정의 경우에는 개구부 끝 부분에서 급기를 하며 급기용 팬은 작업 공간 외부에 설치하는 것이 효과적일 것으로 나타났다. 향후 대형 주물공정 용접작업장의 터널형 반밀폐 공간에 대한 환기방법을 표준화한다면 주물산업 및 조선업 등에 종사하는 용접 근로자들의 건강보호 및 작업환경 개선에 매우 효과적일 것으로 판단된다.

디클로로메탄 사용 세척공정의 국소배기장치 설치 후 노출농도 변화 (Change in Exposure Concentration in the Cleaning Process after Installing a Local Exhaust System)

  • 조명화;김승기;김현수
    • 한국산업보건학회지
    • /
    • 제33권3호
    • /
    • pp.280-283
    • /
    • 2023
  • Objectives: The purpose of this study was to examine the change in exposure concentration in the cleaning process after installing a local exhaust system. Methods: Dichloromethane measurement was conducted according to the KOSHA Guide (A-19-2019). Results: After the local exhaust device was installed, a total of three measurements were conducted, including temporary work environment measurements, and all of the measurements did not exceed the DCM exposure standard, but were more than 50% of the DCM Time Weighted Average((8-TWA) Conclusions: It is thought that the local ventilation system of a small business needs not only support for the initial installation cost, but also educational support for maintaining the performance of the local ventilation system and support for consumables (adsorbents, filters, etc.) that incur periodic costs.

공업고등학교 용접실습실의 용접흄 발생농도와 국소배기 실태 (Status of Welding Fume Concentration and Local exhaust Ventilation System at Welding Laboratory in Technical High School)

  • 황성환;손부순;장봉기;박종안;이종화
    • 한국산업보건학회지
    • /
    • 제11권1호
    • /
    • pp.1-8
    • /
    • 2001
  • This study was performed to evaluate a local exhaust ventilation system capability and welding fume concentration in welding laboratory at 5 technical high schools. Results of the study are as follows; 1. The personal exposure of welding fume in welding laboratory was measured. The geometric mean of 73 personal samples was $6.27mg/m^3$($3.85{\sim}9.88mg/m^3$), and 68.5% of these exceeded TLV of the Korea Ministry of Labor. 2. The geometric mean of welding fume at outside of booth was $2.27mg/m^3$($1.57{\sim}2.58mg/m^3$). All of measured concentrations were lower than TLV of the Korea Ministry of Labor. 3. Local exhaust ventilation system in welding laboratory could not remove hazardous substance effectively because of inappropriate canopy hood and absurd design. 4. The possibility of exposure risk was estimated to be high because of working point under breathing zone, misplacement of working table and insufficient supply of respiratory protector. 5. The mean values of capture velocity and transportation velocity of local exhaust ventilation system in welding laboratory were 0.38m/sec, 4.27m/sec respectively. These values were satisfied the guideline of the Korea Ministry of Labor. 6. The efficiency of performance of local ventilation system was anticipated to be decreased because of accumulated dust and alien substance on fan and duct.

  • PDF

일부 탈지세척 및 도금공정 국소배기장치의 성능점검과 개선방안 (Performance of Local Exhaust Ventilation Systems of Degreasing and Plating Workplaces)

  • 한돈희
    • 한국산업보건학회지
    • /
    • 제8권2호
    • /
    • pp.178-185
    • /
    • 1998
  • In order to evaluate and improve the performance of local exhaust ventilation systems for two TCE degreasing (A, B) and two electroplating (C, E) and one acid dipping & plating (D) operations located in Kimhae, the performance test was conducted with trace gases and a thermal anemometer (Kanomax 24-6111, Japan). For the inadequately designed systems, the improvement and redesigns in compliance with recommendation by ACGIH was suggested. The results of performance test for each system are as follows; 1. System of Workplace A was generally well-designed. Actual exhaust air flow rate was in excess of 68% above the recommended standard exhaust air flow rate. 2. System of Workplace B was very well-designed and completely enclosed. 3. All systems of Workplace C including hoods were poorly-designed and actual exhaust air flow rates were insufficient for open tanks. All systems should be upgraded according to ACGIH recommendations. 4. Supply and exhaust air flow rate of push-pull exhaust systems in Workplace D should be greatly increased. The width of flange of dipping tank hood should be increased with the value suggested. 5. System of Workplace E was well-designed. Actual exhaust air flow rate was in excess of 54% above the required.

  • PDF

유해물질 및 공업용 분진 제거를 위한 산업용 후드 개선에 관한 연구 (A Study on Improvement of Industrial Hood in Ventilation System for Elimination of Harmful Material and Dust)

  • 김영선;오율권
    • 설비공학논문집
    • /
    • 제20권4호
    • /
    • pp.238-244
    • /
    • 2008
  • This study investigates on the improvement of inhalation effect of hood which attached new device named as "gas-guide-device" in local exhaust ventilation system for the effective elimination of harmful material and dust in manufacturing factory. The gas-guide-device having a diamond shape is composed of width (b) and two sides of a device (X, Y) and its size is selected the industrial hood under application in manufacturing factory after due consideration. In order to investigate the effect of gas-guide-device, numerical and experimental study is performed that the flow velocity is calculated and is measured by a commercial program "COMSOL $Multiphysics^{TM}$" and a hot wire type of anemometer, respectively. The numerical and experimental results are revealed is a similar pattern and flow velocity has improved to hood attached gas-guide-device. Also, the numerical method and result is also verified the dependance. Moreover, the optimum shape and size of gas-guide-device is revealed that the width (b) and the ratio of two sides of gas-guide-device (X, Y) has 125mm and 4 to 6.

대기오염(大氣汚染)이 전주(全州)·군산간(群山間) 국도변(國道邊) 왕벚나무에 미치는 영향(影響) (I) -수용성(水溶性) 황(黃), Pb, Cd 함유량을 중심(中心)으로- (Effect of Air Pollution on Cherry Tree (Prunus yedoensis Matsumara) planted on National Roadsides between Cheonju and Kunsan City (I) -Water soluble sulfur, Lead and Cadmium Contents in the Leaves-)

  • 김창호;황유철;임경빈
    • 한국산림과학회지
    • /
    • 제81권2호
    • /
    • pp.117-123
    • /
    • 1992
  • 본(本) 연구(硏究)는 전주(全州)-군산간(群山間) 국도변(國道邊) 약(約) 40Km에 열식(列植)된 왕벚나무를 대상으로 하여 자동차 배기가스에 의한 공기오염(空氣汚染)이 왕벚나무의 생육(生育)에 미치는 영향(影響)을 규명(糾明)하고자, 선정(選定)된 전주(全州)-군산간(群山間) 국도변양측(國道邊兩側)에 10개의 지점(地點)에서 각(各) 지점(地點) 당 5그루씩 총(總) 100주(株)에 있어서 수관중간부위(樹冠中間部位)에서 성숙엽(成熟葉)을 채취(採取)하여 엽중(葉中) 수용성(水容性) 황(黃), Pb, 그리고 Cd 함유량(含有量)을 조사(調査)하였다. 주요결과는 다음과 같다. (1) 엽중수용성(葉中水溶性) 황(黃) 함유량(含有量)은 0.06-0.07%의 범위를 보였고, 대조구보다 2배(倍)가 더 많았다. 전주(全州)-이리간(裡里間)보다는 이리(裡里)-군산간(群山間)의 시료(試料)가 더 높은 수용성(水容性) 황(黃) 함유량(含有量)을 보였다. 대조시료(對照試料)와 비교할 때 황(黃)의 오염(汚染)이 인정되었다. (2) Pb 함유량(含有量)은 12-35ppm의 범위를 보였고 도로우측시료(道路右側試料)의 함유량(含有量)이 좌측시료(左側試料) 함유량(含有量)보다 높았다. 대조시료(對照試料)와 비교할 때 Pb의 더 많은 흡수량(吸收量)을 인정할 수 있었다. Pb 오염원(汚染源)은 일단 차량의 배기(排氣)가스에서 오는 것으로 추단(推斷)하고 이곳을 스쳐가는 바람의 영향도 생각 될 수 있는 것으로 보았다. (3) Cd 함유량(含有量)은 0.42-0.98ppm의 범위를 보였고 대조시료(對照試料)와 비교할 때 Cd의 오염(汚染)이 인정 될 수 있었다. (4) 벚나무 도로수(道路樹)의 건강도(健康度)는 주로 교통에 의한 오염이외(汚染以外)에도 개체(個體)에 따fms 유전적(遺傳的) 차이(差異), 그리고 국소입지(局所立地)의 차등(差等), 제인자(諸因子)의 혼합작용(混合作用)이 생각될 수 있을 것이다.

  • PDF

가연성 금속분진 폭발시 저장 및 포집용 구조물에 대한 3차원 유한요소 해석 (3-Dimensional Finite Element Analysis for Collecting Structure of Combustible Metal Dust During Explosion)

  • 장창봉;용종원;백종배;권혁면;고재욱
    • 한국가스학회지
    • /
    • 제15권5호
    • /
    • pp.19-24
    • /
    • 2011
  • 최근 산업구조가 미래 첨단산업 위주로 전환되면서 자동차를 비롯한 항공기, 휴대폰, 전자기기 등 다양한 산업분야의 제품에 Al, Mg, Li, Zn과 같은 가연성 금속의 사용량이 크게 증가하고 있으며 이러한 가연성 금속의 가공과 정에서 발생하는 금속분진에 의한 폭발 사고 또한 증가하고 있다. 금속분진에 의한 폭발사고는 가연성 금속분진을 포집 및 저장하는 국소배기설비의 공기정화장치에서 대부분 발생함에 따라 공기정화장치내 폭발 발생시 폭발압력에 의한 공기정화장치 구조물의 변형과 파열형태를 단순 예측이 아닌 유한요소해석(FEA)법에 의해 기술적으로 분석 및 제시하고자 본 연구를 수행하였다.

일부 영세 도금사업장의 국소배기성능과 공기중 총크롬, 6가 크롬 및 니켈농도와의 관계분석 (Evaluation on the Efficiencies of Local Exhaust Systems and Airborne Concentrations of Total Chromium, Hexa-valent Chromium and Nickel in Some Electroplating Plants)

  • 박동욱;박두용;신용철;오세민;정규철
    • 한국산업보건학회지
    • /
    • 제3권1호
    • /
    • pp.68-77
    • /
    • 1993
  • To evaluate efficiencies of the local exhaust systems installed in chromiun and nickel eletroplating tanks, specifications of each tank and general performances of the local exhaust systems were measured in 16 electroplating plants from July 3 to November 24, 1992. Airborne concentrations of total chromium, hexa-chromium and nickel were also measured, Most of the local exhaust systems installed in electroplating plants were inadequately designed. Average capture velocities of local exhaust systems in chromium and nickel tanks were 0.45 m/sec and 0.29 m/sec. Average slot velocities in chromium and nickel tanks were 7.30 m/sec and 2.87 m/sec repectively. Both average capture and solt velocities were in noncompliance with the standards recommened by American Conference of Governmental Industrial Hygienists (ACGIH) and National Institute for Occupational Safety and Health (NIOSH), Exhausted air volume was insufficient in all local exhaust systems surveyed. Worker exposure levels to total chromium, hexa-chromium and nickel were $43.0{\mu}g/m^3$, $1.7{\mu}g/m^3$ and $9.3{\mu}g/m^3$, which were below the Korean Standard and U.S. Occupational Health and Safety Administration (OHSA) Permissible Exposure Limit(REL). However, Worker exposure level to hexa-chromium exceeded the NIOSH Recommended Exposure Limit(REL) of $1{\mu}g/m^3$. As the result of Scheffee's multiple comparions, worker exposure levels to all metals were significantly different between two groups by the management state of existing local exhaust systems (p<0.05). However, Difference between a group with local exhaust systems which were poorly managed and another group without local exhaust system was satatistically non-significant.

  • PDF