Browse > Article

A Study on Improvement of Industrial Hood in Ventilation System for Elimination of Harmful Material and Dust  

Kim, Young-Sun (Department of Precision Mechanical Engineering, Chosun University)
Oh, Yool-Kwon (Department of Mechatronics Engineering, Chosun University)
Publication Information
Korean Journal of Air-Conditioning and Refrigeration Engineering / v.20, no.4, 2008 , pp. 238-244 More about this Journal
Abstract
This study investigates on the improvement of inhalation effect of hood which attached new device named as "gas-guide-device" in local exhaust ventilation system for the effective elimination of harmful material and dust in manufacturing factory. The gas-guide-device having a diamond shape is composed of width (b) and two sides of a device (X, Y) and its size is selected the industrial hood under application in manufacturing factory after due consideration. In order to investigate the effect of gas-guide-device, numerical and experimental study is performed that the flow velocity is calculated and is measured by a commercial program "COMSOL $Multiphysics^{TM}$" and a hot wire type of anemometer, respectively. The numerical and experimental results are revealed is a similar pattern and flow velocity has improved to hood attached gas-guide-device. Also, the numerical method and result is also verified the dependance. Moreover, the optimum shape and size of gas-guide-device is revealed that the width (b) and the ratio of two sides of gas-guide-device (X, Y) has 125mm and 4 to 6.
Keywords
Local exhaust ventilation system; Gas-guide-device; Flow velocity; Industrial hood;
Citations & Related Records
연도 인용수 순위
  • Reference
1 Kim, K. Y., Baek, S. J. and Sung, H. J., 2000, Fully-Implicit Decoupling Method for Incompressible Navier-Stokes Equations, Proceeding of the KSME, Vol. 24, No. 10, pp. 1327-1325
2 Leigh, S. B., 1995, An Evaluation of Airtightness Performance and Analysis of Energy Savings Potential in Apartment Housing, Solar Energy, Vol. 15, No. 3, pp. 119-125   DOI   ScienceOn
3 Rie, D. H., 1997, Implementation and inovation of an industrial ventilation facilities., SAREK J, Vol. 26, No. 2, pp. 67-75
4 Kim, W. K., Han, S. H. and Choi, Y. D., 2007, Velocity Measurement Technique in a Narrow Passage by Hot-Wire Anemometer, Proceeding of the SAREK, Vol. 19, No. 2, pp. 191-201
5 Kim, T. H. and Jin, M. K., 1996, Development of Industrial Ventilation System Design Software, Proceedings of the KOSAE, pp. 191-194