DOI QR코드

DOI QR Code

고무제품제조공장의 가류공정에 설치된 유도전동기의 설치환경 및 화재위험성 분석

Analysis of Installation Environment and Fire Risk of Induction Motors Installed in the Curing Process of a Rubber Product Manufacturing Plant

  • 이종찬 ((주)KT&G 안전보건관리실) ;
  • 김두현 (충북대학교 안전공학과) ;
  • 김성철 (충북대학교 안전공학과)
  • Jong-Chan Lee (Safety & Health Management Office) ;
  • Doo-Hyun Kim (Department of Safety Engineering, Chungbuk National University) ;
  • Sung-Chul Kim (Department of Safety Engineering, Chungbuk National University)
  • 투고 : 2023.01.27
  • 심사 : 2023.04.14
  • 발행 : 2023.04.30

초록

This study analyzed the fire status of a rubber product manufacturing factory based on 19 years of fire data. Through the analysis of the current state of fire, electrical fires accounted for 58.19%, and among electrical fires, motor fires were the highest at 26.21%. For the motor fire occurrence process, the curing process accounted for the highest rate of 51.9%. Therefore, the installation environment was investigated for the motor in the curing process, and it was confirmed that the motor's maximum ambient temperature exceeded 40℃. In particular, in the case of the motor for curing operation, the motor was installed in a separate motor room, so the average indoor temperature was 48.10℃ and the motor frame's maximum temperature was 72.80℃. In this study, the risk of motor fire was confirmed through a field survey, and a safety management plan was derived by finding a process with high fire risk and conducting an experiment on the motor's installation environment and electrical characteristics in that process.

키워드

참고문헌

  1. 2021 Edition of NFPA 921(Guide for Fire and Explosion Investigations), Chapter 9, "Electricity and Fire", pp. 123-151, 2021
  2. National Fire Data System, "2022 Fire Statistic" (31. Dec. 2022)
  3. Motor Reliability Working Group, "Report Of Large Motor Reliability Survey Of Industrial And Commercial Installations, Part I", IEEE Trans. Ind. Appl., Vol. IA-21, pp. 853-864, 1985. https://doi.org/10.1109/TIA.1985.349532
  4. Failure Mode / Mechanism Distributions (FMD) 2016.
  5. Y. B. Kim and K. H. Kim, "Analysis on the Voltage, Current and Temperature Signals for Free and Locked Operation of Three Speed Electric Fan", Fire Science and Engineering, Vol. 28, No. 3, pp. 87-91, 2014. https://doi.org/10.7731/KIFSE.2014.28.3.087
  6. D. H. Kim and H. S. Lee, "Detection of Current Signal and Thermal Characteristics of Electric Fan Operated in Various Situations" J. Korean Soc. Saf., Vol. 29, No. 3, pp. 20-27, 2014. https://doi.org/10.14346/JKOSOS.2014.29.3.020
  7. H. K. Ji and J. Y. Sone, "Study on the Fire Risk in Locked Rotor Condition of Single-Phase Induction Motor", Fire Science and Engineering, Vol. 34, No. 2, pp 64-71, 2020 https://doi.org/10.7731/KIFSE.78b50c46
  8. NEXEN TIRE Homepage, Tire Manufacturing Process
  9. Hankooktire & Technology, "Working Environment Measurement Results", Second half of 2022.
  10. S. B. Yu, M. S. Jeon and J. C. Kim , "Analysis of Induction Motor and Fault Protection Technology for Field Technicians", Electric Engineers Magazine, Vol. 204, Issue 8, pp. 44-47, 1999.
  11. KS C IEC 60085 : 2007, "Thermal Evaluation and Classification of Electrical Insulation", Korean Agency for Technology and Standards, p. 4, 2021.
  12. J. C. Lee, D. H. Kim and S. C. Kim, "A Study on the Electrical and Heat Generation Characteristics of an Induction Motor under Restrained Operation", J. Korean Soc. Saf., Vol. 38, No. 1, pp. 25-33, 2023.