DOI QR코드

DOI QR Code

Analysis of the Insulation Resistance Trend according to the Installation Environment of the Electric Wiring of the Melting Furnace

용해로 전기배선의 설치환경에 따른 절연저항 추이 분석

  • Suk Bong Ko (Korea Industrial Safety Association) ;
  • Doo-Hyun Kim (Department of Safety Engineering, Chungbuk National University) ;
  • Sung-Chul Kim (Department of Safety Engineering, Chungbuk National University)
  • Received : 2022.12.28
  • Accepted : 2023.04.18
  • Published : 2023.04.30

Abstract

In this study, the process and the environment of a melting furnace, located in Workplace A in Chungnam Province was inspected, and the insulation resistances of electrical circuits and motors were measured, and their changes over five years (2017-2021) were analyzed. It was found that the exhaust fan, oil pumps #A and #B, and heater were installed in 2010. Their insulation resistances decreased from 2017. Specifically, the insulation resistance of Oil Pump #A decreased from 100 (㏁) in 2018 to 20(㏁) in 2021, an 80% reduction. The fast decrease in insulation resistance was due to the high temperature of the melting furnace affecting surrounding the electrical facilities. A safety management scheme on the electrical facility of the melting furnace was proposed.

Keywords

References

  1. National Fire Agency, National Fire Data System, 2016-2020.
  2. Y. K. Park , Y. S. Cho, K W Lee, K H Um and D. H. Park, "Load Current and Temperature Measurement for Measuring the Insulation Resistance of the 6.6 kV Cable", J. Korean Inst. Electr. Electron. Mater. Eng., Vol. 28, No. 1, pp. 46-50, 2015. https://doi.org/10.4313/JKEM.2015.28.1.46
  3. Ministry of Trade, Industry and Energy, Electrical Equipment Technology Standards, 2016.
  4. Korea Electric Equipment Technical Standard, http://kec.kea.kr
  5. Industrial Safety and Health Act, https://kras.kosha.or.kr1. Jun. 2022.
  6. K. C. Kim, D. H. Kim and S. C. Kim, "Analysis" of Thermal and Insulation Resistance Characteristics by Aging of Electrical Socket Outlet", J. Korean Soc. Saf., Vol. 34, No. 5, pp. 22-30, 2019.
  7. H. J. Park, "Lifetime Prediction on PVC Insulation Material for IV and HIV Insulated Wire", J. Korean Soc. Saf., Vol. 34, No. 1, pp. 8-13, 2019.
  8. Energy usage Statistics, https://.index.go.kr, 2022
  9. Maintenance of Electrical Equipment Technology Standards (Notification of Ministry of Trade, Industry and Energy No. 2020-227, December 31, 2020.
  10. KOSHA GUIDE (P-143-2014) Furnace of the Korea Occupational Safety and Health Agency, 2014.