DOI QR코드

DOI QR Code

A Case Study on the Islanding Detection Protection of PV System and ESS System

태양광 발전과 ESS 시스템의 연계운전시 단독운전 방지 사례 연구

  • Lim, Jong Rok (Photovoltaics Laboratory, New and Renewable Energy Institute, Korea Institute of Energy Research) ;
  • Hwang, Hye-Mi (Photovoltaics Laboratory, New and Renewable Energy Institute, Korea Institute of Energy Research) ;
  • Shin, Woo Gyun (Photovoltaics Laboratory, New and Renewable Energy Institute, Korea Institute of Energy Research) ;
  • Ju, Young-Chul (Photovoltaics Laboratory, New and Renewable Energy Institute, Korea Institute of Energy Research) ;
  • Jung, Young Seok (Photovoltaics Laboratory, New and Renewable Energy Institute, Korea Institute of Energy Research) ;
  • Kang, Gi-Hwan (Photovoltaics Laboratory, New and Renewable Energy Institute, Korea Institute of Energy Research) ;
  • Ko, Suk-Whan (Photovoltaics Laboratory, New and Renewable Energy Institute, Korea Institute of Energy Research)
  • 임종록 (한국에너지기술연구원 신재생에너지연구소 태양광 연구실) ;
  • 황혜미 (한국에너지기술연구원 신재생에너지연구소 태양광 연구실) ;
  • 신우균 (한국에너지기술연구원 신재생에너지연구소 태양광 연구실) ;
  • 주영철 (한국에너지기술연구원 신재생에너지연구소 태양광 연구실) ;
  • 정영석 (한국에너지기술연구원 신재생에너지연구소 태양광 연구실) ;
  • 강기환 (한국에너지기술연구원 신재생에너지연구소 태양광 연구실) ;
  • 고석환 (한국에너지기술연구원 신재생에너지연구소 태양광 연구실)
  • Received : 2019.01.03
  • Accepted : 2019.02.20
  • Published : 2019.02.28

Abstract

BIPV or BAPV installation applied to building is increasing through public utility mandates enterprise. Solar PV energy generates only during the day, but if it is operated in convergence with ESS, which stores electrical energy, it can restrain the fossil energy used in buildings throughout the day. A solution is to converge with PV system and ESS. However, PV systems and ESS connected to the power grid in parallel can cause problems of electrical stability. A study was conducted on the case of failure to detect islanding operation under the parallel operation of PV generation and ESS that are connected in parallel to power grid. Experiments conducted various non-islanding detections under the operating conditions. In the experiment results, when one PCS - PV inverter or ESS inverter - was operating under the islanding condition, it stopped working within 0.5 seconds of the Korean grid standard. However, when both of PV inverter and ESS inverter were operating at the same time under the islanding situation, the anti-islanding algorithm did not operate normally and both inverters continuously supplied power to the connected RLC loads. islanding detection Algorithm developed by each inverter manufacturer has caused this phenomenon. Therefore, this paper presented a new test standard for islanding detection.

Keywords

TOONB4_2019_v39n1_59_f0001.png 이미지

Fig. 1 Configuration diagram for islanding detect test

TOONB4_2019_v39n1_59_f0002.png 이미지

Fig. 2 The test results for islanding detect of one inverter

TOONB4_2019_v39n1_59_f0003.png 이미지

Fig. 3 The results for islanding detect of case 3 (R load capacity: 40 [kW])

TOONB4_2019_v39n1_59_f0004.png 이미지

Fig. 5 The results for islanding detect of case 5 (R load capacity: 10 [kW])

TOONB4_2019_v39n1_59_f0005.png 이미지

Fig. 4 The results for islanding detect of case 4 (R load capacity: 0 [kW])

TOONB4_2019_v39n1_59_f0006.png 이미지

Fig. 6 The results for islanding detect of case 6(R load capacity: 15 [kW])

Table 1 Specification of test inverters

TOONB4_2019_v39n1_59_t0001.png 이미지

Table 2 The description of test case for inverter output and load capacity

TOONB4_2019_v39n1_59_t0002.png 이미지

References

  1. Basic road map for the Achievement of the 2030 Nation Greenhouse Gas Reduction Goal in the Korean
  2. Choi, W. K, Oh, M. S., and Shin, W. C., The Simplified Pre-Estimation Model Development of a BIPV Generation Rate by the District Division, Journal of the Korean Solar Energy Society, Vol. 36, No. 2, pp. 19-29, 2016. https://doi.org/10.7836/KSES.2016.36.2.019
  3. Park, J. W., Kim, H. K., Kim, T. Y., and Leigh, S. B., A Study on the Effect of Air Gap for Reducing the Temperature of Vertical Building Applied Photovoltaics through CFD Simulation, Journal of the Architectural Institute of Korea Planning & Design, Vol. 28, No. 5, pp. 249-256, 2012. https://doi.org/10.5659/JAIK_PD.2012.28.5.249
  4. Wu, X., Liu, Y., Xu, J., Lei, W., Si, X., Du, W., and Lin, J., Monitoring the Performance of the Building Attached Photovoltaic (BAPV) System in Shanghai, Energy and buildings, Vol. 88, pp. 174-182, 2015. https://doi.org/10.1016/j.enbuild.2014.11.073
  5. Husein, M., Hau, V. B., Chung, I. Y., Chae, W. K., and Lee, H. J., Design and Dynamic Performance Analysis of a Stand-alone Microgrid, Journal of Electrical Engineering & Technology, Vol. 12, No. 5, pp. 1777-1788, 2017. https://doi.org/10.5370/JEET.2017.12.5.1777
  6. Kim, J. Y., Jeon, J. H., Kim, S. K., Cho, C., Park, J. H., Kim, H. M., and Nam, K. Y., Cooperative control strategy of energy storage system and microsources for stabilizing the microgrid during islanded operation, IEEE Transactions on Power Electronics, Vol. 25, No. 12, pp. 3037-3048, 2010. https://doi.org/10.1109/TPEL.2010.2073488
  7. Verhoeven, Bas. Utility aspects of grid connected photovoltaic power systems. International Energy Agency, 1998.
  8. Chung, I. -Y. and Moon, S. -I., A New Islanding Detection Method Using Phase-locked Loop for Inverter-interfaced Distributed Generators, Journal of Electrical Engineering and Technology, Vol. 2, No. 2, pp. 165-171, 2007. https://doi.org/10.5370/JEET.2007.2.2.165
  9. Zomer, C., Nobre, A., Cassatella, P., Reindl, T., and Ruther, R., The Balance between Aesthetics and Performance in Building‐integrated Photovoltaics in the Tropics, Progress in Photovoltaics: Research and Applications Vol. 22, No. 7, pp. 744-756, 2014. https://doi.org/10.1002/pip.2430
  10. Choi, J. -S., Ko, J. -S., and Chung, D. -H., Development of Novel Algorithm for Anti-Islanding of Grid-Connected PV Inverter. Journal of the Korean Institute of Illuminating and Electrical Installation Engineers Vol. 25, No. 10, pp. 76-86, 2011. https://doi.org/10.5207/JIEIE.2011.25.10.076