Abstract
In case of Lighting occurs in Domestic combined distribution line, normally the voltage for the neutral line increase dramatically. General connection for underground cable is bundled common earth type so the lightning over voltage increase at the concentric-neutral line is not big enough to give impact on cable sheath. But in case of Non bundled common earth type it is necessary to analyze the phenomena on cable sheath caused by lightening overvoltage. Especially pole and cable joint are the core factor to consider. In this paper concrete pole and cable joint were evaluated in case of Non bundled common earth type combined distribution Line. EMTP simulation model has been designed and several case study were made. Also several experimental test were made to verify the simulation result.