• Title/Summary/Keyword: Concentric-neutral line

Search Result 1, Processing Time 0.02 seconds

A Study of Concentric-Neutral Line Voltage Increase Related by Pole and Cable Joint When Lightening Overvoltage Injected in Combined Distribution Line (혼합 배전선로에 직격낙뢰시 전주와 케이블직선접속재가 케이블 동심중성선 전위상승에 미치는 영향)

  • Jeon, Yong-Joo;Jeon, Myung-Su
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.67 no.6
    • /
    • pp.702-707
    • /
    • 2018
  • In case of Lighting occurs in Domestic combined distribution line, normally the voltage for the neutral line increase dramatically. General connection for underground cable is bundled common earth type so the lightning over voltage increase at the concentric-neutral line is not big enough to give impact on cable sheath. But in case of Non bundled common earth type it is necessary to analyze the phenomena on cable sheath caused by lightening overvoltage. Especially pole and cable joint are the core factor to consider. In this paper concrete pole and cable joint were evaluated in case of Non bundled common earth type combined distribution Line. EMTP simulation model has been designed and several case study were made. Also several experimental test were made to verify the simulation result.