DOI QR코드

DOI QR Code

Evaluation of Floor Heating Performance and Design Criteria for Operating an Outdoor Swimming Pool During Winter : A Case Study

동절기 옥외 수영장 시설의 운영을 위한 바닥난방 성능평가 및 설계기준에 관한 사례연구

  • Cho, Jinkyun (Construction & Energy Business Division, KCL(Korea Conformity Laboratories)) ;
  • Woo, Kyunghun (Construction Technology Team, Samsung C&T Corporation) ;
  • Kim, Jin-Ho (Department of Building Technology, Suwon Science College)
  • 조진균 (한국건설생활환경시험연구원) ;
  • 우경헌 (삼성물산(주) 건설부문) ;
  • 김진호 (수원과학대학교 건축기계설비과)
  • Received : 2017.03.26
  • Accepted : 2017.03.30
  • Published : 2017.06.10

Abstract

This study aimed to analyze the deck floor heating system of an outdoor swimming pool in terms of the thermal capacity/output and the surface temperature distribution based on the outdoor temperature, to design for anti-freezing during winter. Through the transient heat transfer simulation with PHYSIBEL and theoretical equations, the surface temperature distribution of the floor heating system at two outdoor conditions in Jeju, were calculated and evaluated. The results indicate that the specific thermal output required for maintaining $4^{\circ}C$ surface temperature at the design outdoor temperature of $0.1^{\circ}C$, was about $90W/m^2$. This performance analysis can be applied for future design criteria, including optimizations of system capacity and size.

Keywords

References

  1. KMA, 2011, Climatological normals of Korea(1981-2010), Korea Meteorological Administration.
  2. ASHRAE, 2015, ASHRAE Handbook-HVAC Applications, Chapter 51 snow melting and freeze protection.
  3. Housing Research Institute, 1996, A Study on the Criteria of Design and Construction for Snow Melting System, Korea National Housing Corporation.
  4. Recknagel, H. and Sprenger, E., 1982, Heating and Air Conditioning, Gradjevinska knjiga, Belgrade.