The Performance Improvement of a Gas Injection Heat Pump with a Flash Tank

기액분리기를 적용한 가스 인젝션 히트펌프의 성능 향상에 관한 실험적 연구

  • Son, Kilsoo (Department of Mechanical Engineering, Graduate School Korea University) ;
  • Kim, Dongwoo (Department of Mechanical Engineering, Graduate School Korea University) ;
  • Choi, Sungkyung (Department of Mechanical Engineering, Graduate School Korea University) ;
  • Kim, Yongchan (Department of Mechanical Engineering, Korea University)
  • 손길수 (고려대학교 기계공학과 대학원) ;
  • 김동우 (고려대학교 기계공학과 대학원) ;
  • 최성경 (고려대학교 기계공학과 대학원) ;
  • 김용찬 (고려대학교 기계공학부)
  • Received : 2016.12.02
  • Accepted : 2017.04.11
  • Published : 2017.06.10

Abstract

Air-source heat pumps are widely used in residential heating systems. However, the decrease in the capacity of the heat pump is unavoidable when operating at very low and high ambient temperatures. The vapor injection technique is considered a promising technology to overcome this problem. Recent research on vapor injection cycles have mainly adopted a scroll compressor with an internal heat exchanger at severe operating conditions. This study measured the COP and EER of a gas injection heat pump using a flash tank with an inverter-driven rotary compressor at severe operating conditions. Compared to non-injection heat pumps, the heating capacity and COP of the gas injection heat pump improved up to 15% and 2.9%, respectively, at outdoor temperatures of $-10^{\circ}C$ to $7^{\circ}C$. The cooling capacity of the gas injection heat pump was 11% higher than the non-injection heat pump at an outdoor temperature of $35^{\circ}C$. At the same time, the EER of the gas injection heat pump was similar to that of the non-injection heat pump.

Keywords

References

  1. Sami, S. M. and Tulej, P. J., 1995, A new design for an air-source heat pump using a ternary mixture for cold climates, Heat Recovery and CHP, Vol. 15, No. 6, pp. 521-529. https://doi.org/10.1016/0890-4332(95)90062-4
  2. Wang, X., Hwang, Y., and Reinhard, R., 2009, Two-stage heat pump system with vapor-injected scroll compressor using R410A as a refrigerant, International Journal of Refrigeration, Vol. 32, No. 6, pp. 1442-1451. https://doi.org/10.1016/j.ijrefrig.2009.03.004
  3. Roh, C. W. and Kim, M. S., 2011, Effects of intermediate pressure on the heating performance of a heat pump system using R410A vapor-injection technique, International Journal of Refrigeration, Vol. 34, No. 8, pp. 1911-1921. https://doi.org/10.1016/j.ijrefrig.2011.07.011
  4. Baek, C., Heo, J., Jung, J., Lee, E., and Kim, Y., 2015, Effects of vapor injection techniques on the heating performance of a $CO_2$ heat pump at low ambient temperature, International Journal of Refrigeration, Vol. 43, pp. 26-35.
  5. Heo, J., Jeong, M. W., and Kim, Y., 2010, Effects of flash tank vapor injection on the heating performance of an inverter-driven heat pump for cold regions, International Journal of Refrigeration, Vol. 33, No. 4, pp. 848-855. https://doi.org/10.1016/j.ijrefrig.2009.12.021
  6. Heo, J., Jeong, Kang, H., and Kim, Y., 2011, Optimum cycle control of a two-stage injection heat pump with a double expansion sub-cooler, International Journal of Refrigeration, Vol. 35, No. 1, pp. 58-67. https://doi.org/10.1016/j.ijrefrig.2011.09.005
  7. Heo, J., Jeong, M. W., Baek, C., and Kim, Y., 2010, Comparison of the heating performance of air-source heat pumps using various types of refrigerant injection, International Journal of Refrigeration, Vol. 34, No. 2, pp. 444-453. https://doi.org/10.1016/j.ijrefrig.2010.10.003
  8. Heo, J., Jeong, M., Jeong, J., and Kim, Y., 2008, Effects of gas injection on the heating performance of a two-stage heat pump using a twin rotary compressor with refrigerant charge amount, Korean Journal of Air-conditioning and Refrigeration Engineering, Vol. 3, No. 16, pp. 77-82.
  9. Hwang, Y., Xing, X., Reinhard, R., and Hung, P., 2010, Control strategy of vapor injection cycle, International Refrigeration and Air Conditioning Conference, Paper 1066.
  10. Xing, X., Hwang, Y., and Reinhard, R., 2011, Refrigerant injection for heat pumping/air conditioning systems: Literature review and challenges discussions, International Journal of Refrigeration, Vol. 34, pp. 402-415. https://doi.org/10.1016/j.ijrefrig.2010.09.015
  11. Baolong, W., Wenxing, S., Linjun, H., and Xianting, L., 2009, Optimization of refrigeration system with gas-injected scroll compressor, International Journal of Refrigeration, Vol. 32, No. 7, pp. 1544-1554. https://doi.org/10.1016/j.ijrefrig.2009.06.008
  12. Ko, S., Heo, J., Cho, I., and Kim, Y., 2012, Heating performance characteristics of a heat pump with a variable speed injection scroll compressor, Korean Journal of Air-conditioning and Refrigeration Engineering, Vol. 24, No. 5, pp. 377-384. https://doi.org/10.6110/KJACR.2012.24.5.377
  13. Jeong, M., Heo, J., Jeong, H., and Kim, Y., 2009, The cooling performance enhancement of a variable speed heat pump using gas injection technique, Korean Journal of Air-conditioning and Refrigeration Engineering, Vol. 21, No. 8, pp. 425-432.
  14. Ma, G. and Zhao, H., 2008, Experimental study of a heat pump system with flash-tank coupled with scroll compressor, Energy and Buildings, Vol. 40, No. 5, pp. 697-701. https://doi.org/10.1016/j.enbuild.2007.05.003