Effects of Plate Pitch and Chevron Angle in a Plate Heat Exchanger on Thermal Energy Performance

판형 열교환기의 피치 및 세브론각이 열에너지 성능에 미치는 영향

  • Published : 2004.09.30

Abstract

Thermal energy performance of a brazed plate heat exchanger has been evaluated experimentally. The effects of plate pitch as well as chevron angle of a plate heat exchanger on the heat transfer rate and pressure drop have been investigated in the wide range as mass flow rates in detail. This problem is of particular interest in the design of a plate heat exchanger. The results obtained indicate that both heat transfer rate and pressure drop are increased as mass flow rate is increased, as expected. It is also found that the heat transfer rate is increased with a decrease in the plate pitch while the heat transfer is decreased with a decrease in the chevron angle. Friction factor correlations are suggested based on the measured pressure drop and effectiveness of plate heat exchangers are also compared.

Keywords

Acknowledgement

Supported by : 과학재단

References

  1. H. S. Ryu. and J. S. Yun.,''Application of Plate Heat Exchangers in HVAC System and Air-Conditioning System,'' Air- Conditioning and Refrigeration Engineering, Vol. 27, No. 3, 1998, pp. 218-231
  2. J. H. Kim., O. K. Kwon., J. H. Yun. and C. S. Lee.,'An Experimental Study on the Performance of a Brazed Plate Heat Exchanger,' Korean Journal of Air- Conditioning and Refrigeration Engineering, Vol. 14, No. 1, 2002, pp. 83-90
  3. Y. H. Kim., D. H. Han. and K. J. Lee., 'Experiments on Condensation Hweat Transfer and Pressure Drop in Plate Heat Exchangers with Different Chevron Angles,' Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 13, No. 11, 2001, pp. 1141-1148
  4. H. Martin,'A theoretical approach to predict the performance of chevron-type plate heat exchangers,' Chemical Engineering and Processing, Vol. 35, 1996, pp. 301-310 https://doi.org/10.1016/0255-2701(95)04129-X
  5. B. H. Kang. and D. K. Kim., 'Evaluation on thermal energy performance of a plate heat exchanger,' Transaction of the Korean Hydrogen Energy Society, Vol. 14, No. 1, 2003, pp. 53-60
  6. Y. Y. Yan. and T. F. Lin., 'Evaporation heat transfer and pressure drop of refrigerant R-134a in a plate heat exchanger,' ASME J. Heat Transfer, Vol. 121, 1999, pp. 118-127 https://doi.org/10.1115/1.2825924