Experimental study on the performance of a brazed plate heat exchanger (용접식 판형 열교환기의 성능에 관한 실험적 연구)

  • Kim, Jong-Ha;Yun, Jae-Ho;Kwon, Oh-Kyung;Kim, Jong-Hun;Ryu, Hae-Sung;Lee, Chang-Sik
    • Proceedings of the KSME Conference
    • /
    • 2001.06d
    • /
    • pp.477-482
    • /
    • 2001
  • An experimental study on the performance evaluation of a brazed plate heat-exchanger with 10RT of normal cooling capacity has been carried out. In the present study, a brazed type plate heat exchanger was tested at a chevron angle $25^{\circ}$ with refrigerant R-22. Mass flux was ranged from $23\;to\;58kg/m^{2}s$ in condensation, and from $22\;to\;53kg/m^{2}s$ in evaporation. The heat transfer coefficient and pressure drop increased with the mass flux increases. The water side pressure drop increased with the cooling water flow rate and chilled water flow rate increases, while mass flux has little affect. It is also shown that the system performance can be improved by enlarging condensation heat transfer area.

  • PDF

Performance of A Fresh Water Generator Applied Plate Heat Exchangers and Flow in the Channel (판형열교환기를 적용한 청수제조장치의 성능 및 채널내 유동)

  • Jin, Z.H.;Ji, M.K.;Lee, K.S.;Chung, H.S.;Jeong, H.M.
    • Journal of Power System Engineering
    • /
    • v.13 no.5
    • /
    • pp.5-10
    • /
    • 2009
  • 본 연구에서는 판형열교환기를 적용한 청수제조장치의 성능에 대하여 연구를 수행하였다. 판형열교환기는 자체의 높은 열전달 성능과 컴펙트한 장점으로 하여 산업에서 점차 널리 사용되고 있다. 또한 사용, 유지보수가 다른 종류의 열교환기에 비하여 편리하여 유연성 있게 사용할 수 있다. 본 실험에서는 세브론 각도가 60도인 전열판을 사용하였으며 이젝터의 작동으로 열교환기를 장착하고 있는 탱크내부에 진공압력을 유지함으로서 내부유체가 $51^{\circ}C{\sim}57^{\circ}C$에서 증발현상이 발생하는 것을 확인하였다. 또한 수치해석적 방법을 통하여 복잡하며 좁은 세브론전열판으로 이루어진 유로내의 유동특성을 파악할 수 있었다.

  • PDF

An Experimental Study of Condensation in Plate Heat Exchangers with R-410A (R-410A를 적용한 판형 열교환기의 응축 성능에 관한 실험적 연구)

  • Byun, J.H.;Lee, K.J.
    • Proceedings of the KSME Conference
    • /
    • 2000.04b
    • /
    • pp.304-310
    • /
    • 2000
  • The experimental study has been conducted on heat transfer characteristics of the plate heat exchangers(PHE) by several researchers. However most of all were focused on a gasket-type plate heat exchanger. Therefore further studies are need for a brazed-type. In the present study, a brazed type plate heat exchanger was tested at a chevron angle of $70^{\circ},\;55^{\circ}$ and $45^{\circ}$ with R-22 and R-410A. Condensation temperatures were $24.5^{\circ}C$, and mass flux was ranged from 35 to $60kg/m^2s$. The inlet and exit conditions are in a superheated vapor and subcooled liquid, respectively. The heat transfer coefficient increased with the chevron angle. The heat transfer coefficient of R-22 was lamer than that of R-410A for all chevron angles.

  • PDF

Effects of Plate Pitch and Chevron Angle in a Plate Heat Exchanger on Thermal Energy Performance (판형 열교환기의 피치 및 세브론각이 열에너지 성능에 미치는 영향)

  • Kang, Byung Ha;Han, Sang Kyu
    • Transactions of the Korean hydrogen and new energy society
    • /
    • v.15 no.3
    • /
    • pp.194-200
    • /
    • 2004
  • Thermal energy performance of a brazed plate heat exchanger has been evaluated experimentally. The effects of plate pitch as well as chevron angle of a plate heat exchanger on the heat transfer rate and pressure drop have been investigated in the wide range as mass flow rates in detail. This problem is of particular interest in the design of a plate heat exchanger. The results obtained indicate that both heat transfer rate and pressure drop are increased as mass flow rate is increased, as expected. It is also found that the heat transfer rate is increased with a decrease in the plate pitch while the heat transfer is decreased with a decrease in the chevron angle. Friction factor correlations are suggested based on the measured pressure drop and effectiveness of plate heat exchangers are also compared.

Effects of Flow Resonance on Heat Transfer Enhancement and Pressure Drop in a Plate Heat Exchanger (유동공진이 판형 열교환기의 열전달 향상과 압력강하에 미치는 영향)

  • Han Sang Kyu;Kang Byung Ha
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.17 no.2
    • /
    • pp.165-172
    • /
    • 2005
  • Heat transfer enhancement of three types of brazed plate heat exchangers has been evaluated experimentally. The effects of flow resonance in a plate heat exchanger on the heat transfer rate and pressure drop have been investigated in a wide range of mass flow rates in detail. The problem is of particular interest in the innovative design of a plate heat exchanger by flow resonance. The results obtained indicate that both heat transfer coefficient and pressure drop are increased as mass flow rate is increased, as expected. It is also found that the heat transfer enhancement is increased with an increase in the plate pitch, while the heat transfer is decreased with a decrease in the chevron angle. Pressure drop also increased with an increase in the plate pitch and with a decrease in the chevron angle. Heat transfer enhancement in the plate heat exchangers is maximized by flow resonance and the resonance frequency of the present plate heat exchangers is found to be in the range of $10~15\;Hz$.

An Experimental Study on Evaperation Heat Transfer and Pressure Drop in Plated cleat Exchangers with Different Chevron Angles (판형열교환기의 세브론각에 따른 증발 열전달특성 및 압력강하에 대한 실험적 연구)

  • Kim, Yun-Ho;Lee, Gyu-Jeong
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.26 no.2
    • /
    • pp.269-277
    • /
    • 2002
  • Experiments on the evaporation heat transfer and pressure drop in the brazed type plate heat exchangers were performed using refrigerants R410A and R22. To investigate the geometric effect, plate heat exchangers with the same pitch and height but different 45$^{\circ}$, 35$^{\circ}$and 20$^{\circ}$chevron angles are used. Tests were conducted fur the ranges of the mass flux of refrigerant from 13 kg/m$^2$s to 34 kg/m$^2$s, the evaporation temperatures of 15$^{\circ}C$, 1$0^{\circ}C$ and 5$^{\circ}C$, vapor quality from 0.15 to 0.95 and the heat flux from 2.5 kW/m$^2$to 8.5 kW/m$^2$. The evaporation heat transfer coefficients and pressure drops were measured. Most of flow patterns are in the chum flow regime and become close to the annular flow for increasing the mass flux and the vapor quality. The heat transfer coefficient increases with increasing the evaporation temperature at a given mass flux in all plate heat exchangers. Also, the pressure drop increases with increasing the mass flux and the quality and decreasing the evaporation temperature and the chevron angle.