Abstract
Recently, multi-room type heat pump system has aroused much attention, because it can achieve much reduction of installation cost and space as well as energy saving in companion with the single room type heat pump system. In the present study, performance characteristics of a 3 room type inverter driven heat pump system, which is widely spread in Japanese market, are measured.. In the single room operation, performances of a heat pump system such s the difference of compressor outlet and inlet pressures and the mass flowrate may increase with the increase of cooling capacity so that COP of the system decrease with the increase of cooling capacity. However, in the 2 room operation, mass flowrate and COP of the total system increase markedly as compared with the single room operation.