• Title/Summary/Keyword: Electronic expansion valve

Search Result 68, Processing Time 0.024 seconds

Expansion Valves Characteristics for Development of Control System on Air Conditioning and Refrigeration Systems (공조.냉동장치의 제어시스템 개발을 위한 팽창밸브 특성)

  • Kim, J.D.;Jang, J.E.;Yoon, J.I.
    • Journal of Power System Engineering
    • /
    • v.2 no.3
    • /
    • pp.34-40
    • /
    • 1998
  • Performance characteristics of a refrigeration systems with various expansion valves and superheat changes were investigated experimentally. Experimental data have been taken utilizing three different devices; a thermostatic expansion valve, a linear type electronic expansion valve and a solenoid type electronic expansion valve. The data taken from tile three types of expansion valves were discussed with the temperature distribution of each zone in the evaporator and the superheat changes of the evaporator outlet In each zone temperature distribution fluctuated larger with the thermostatic expansion valve than with the electronic expansion valves. The optimum superheat ranged from $5^{\circ}C\;to\;15^{\circ}C$, and the superheat with the thermostatic expansion valve showed hunting phenomenon, which affected the evaporating and condensing temperature.

  • PDF

A Study on the Possibility for the Replacement of a Thermal Expansion Valve to an Electronic Expansion Valve (온도식팽창밸브의 전자식팽창밸브로의 대체 가능성에 관한 연구)

  • Han, Do-Young;Jeong, Seong-Woock
    • Proceedings of the SAREK Conference
    • /
    • 2006.06a
    • /
    • pp.695-700
    • /
    • 2006
  • For the precise superheat temperature control of an air conditioner, an electronic expansion valve may be used instead of a thermal expansion valve. In this paper, technical and economical aspects of expansion valves were studied in order to find out the possibility to use an electronic expansion valve to replace a thermal expansion valve.

  • PDF

Characteristics of Capacity Control of Variable Speed Water Cooler with the Electronic Expansion Valve Open/Close Degree (전자팽창밸브 개도에 따른 가변속 수냉각기의 용량제어 특성)

  • Beak, Seung-Moon;Moon, Choon-Geun;Kim, Hyun-Woo;Jeong, Seok-Kwon;Yoon, Jung-In
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.34 no.2
    • /
    • pp.282-288
    • /
    • 2010
  • The paper presents the characteristics of capacity control of variable speed water cooler with the electronic expansion valve open/close degree. It is a preliminary study on the optimum control of the water cooler system using a variable speed compressor controlled by inverter. The electronic expansion valve controlled by the variation of compressor speed maintains the constant degree of superheat at the evaporator outlet, which aims to find the degree of superheat obtaining the optimum refrigeration effect. The investigation indicates that there is a point achieving the maximum cooling capacity by the variation of the electronic expansion valve open/close degree with constant compressor speed.

Fuzzy Control Algorithms for the Compressor and the Electronic Expansion Valve of a Multi-type Air-conditioning System using Multiple Input Variables (다입력변수를 사용한 멀티형 공조시스템 압축기와 전자팽창밸브의 퍼지 제어 알고리즘)

  • Han, Do-Young;Park, Kwan-Jun
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.18 no.2
    • /
    • pp.163-171
    • /
    • 2006
  • In order to control multi-zone temperatures, a multi-type air-conditioning system may be used. In this study, control algorithms for the compressor and the electronic expansion valve of a multi-type air-conditioning system were developed by using fuzzy logics. The compressor control algorithm was composed of a compressor pressure setpoint algorithm, a compressor pressure setpoint reset algorithm, and a compressor frequency setpoint algorithm. The electronic expansion valve control algorithm was composed of an indoor temperature control algorithm, and a superheat control algorithm. These algorithms were applied to a multi-type air-conditioning system. Test showed good results for the control of a multi-type air-conditioning system.

Control of Compressor and Electronic Expansion Valve for a Tandom-type Air-conditioner (텐덤형 냉방시스템의 압축기와 전자팽창밸브 제어)

  • Jung, Nam-Chul;Han, Do-Young
    • Proceedings of the SAREK Conference
    • /
    • 2005.11a
    • /
    • pp.469-473
    • /
    • 2005
  • Capacities of a tandom-type air-conditioner may be modulated by turning on/off multiple compressors and adjusting positions of a electronic expansion valve. In this study. control algorithms for compressors and a electronic expansion valve were developed by using fuzzy’ logics. There algorithms were implemented in a test lab and proved to be effective for the control of indoor air temperature and superheat temperature.

  • PDF

Control of Compressors and Electronic Expansion Valve considering the Safe Operation of a Tandem-type Air-conditioning system (텐덤형 냉방시스템의 안전운전을 고려한 압축기와 전자팽창밸브 제어)

  • Han, Do-Young;Kim, Jae-Hyun
    • Proceedings of the SAREK Conference
    • /
    • 2006.06a
    • /
    • pp.675-680
    • /
    • 2006
  • Capacities of a tandem-type air-conditioner may be modulated by turning on and off of multiple compressors, and adjusting the position of a electronic expansion valve. In this study, control algorithms for compressors and a electronic expansion valve were developed by using fuzzy logics. The pressure control algorithm was also developed for the safe operation of compressors. There algorithms were implemented in a test lab and proved to be effective for the control of indoor air temperature and superheat temperature,

  • PDF

Study on Control of Refrigerant Flow Rate and Characteristics of Superheat in Evaporator using Electronic Expansion Valve (전자(電子) 팽창밸브를 이용(利用)한 증발기(蒸發器)의 냉매(冷媒) 流量(유량) 제어(制御) 및 과열도(過熱度) 특성(特性)에 관한 연구(硏究))

  • Choi, S.O.;Kim, J.H.;Yang, H.S.;Kim, J.S.
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.6 no.4
    • /
    • pp.380-387
    • /
    • 1994
  • An experimental study was performed to investigate the characteristics of refrigerant flow rate control and superheat in an evaporator with an electronic expansion valve(EEV). The EEV used in this study was devised using a needle valve coupled with a stepping motor controlled by a personal computer. A Pill control equation was used to control the superheat of the evaporator and to set the superheat to $5^{\circ}C$. In order to determine an optimum running condition for the system, Pill parameters were varied for the wide range of values. The running condition of an air conditioning system with a PI control was reasonably stable compared with that of the Pill control. Experimental results for the PI control using parameter values, $K_p=1.5$, $T_i=400(sec)$ and $T_s=6(sec)$ show that the superheat reached its target value. When external disturbances were introduced to the system, the superheat target value was reached within about 3 minutes. When the EEV was applied to the air conditioning system driven by an inverter, room temperature control was excellent.

  • PDF

A Study on Dynamic Characteristics of a Refrigeration System by Controlling the Evaporator Superheat (증발기 과열도제어에 따른 냉동장치의 동특성에 관한 연구)

  • 김재돌;오후규;윤정인
    • Transactions of the Korean Society of Mechanical Engineers
    • /
    • v.19 no.8
    • /
    • pp.2012-2021
    • /
    • 1995
  • An experimental study was performed for the analysis of dynamic characteristics of refrigeration system by controlling the evaporator superheat. Experimental data have been taken utilizing two different devices, thermostatic expansion valve(T.E.V.) and electronic expansion valve(E.E.V.), for the control of the evaporator superheat. The ranges of parameters, such as superheat, mass flow rate of refrigerant and inlet temperature of evaporator were 5-30.deg. C 90-170 kg/h and 10-25.deg. C, respectively. The data taken from the T.E.v.and E.E.v.were discussed with the control of the superheat, pressure drop, refrigerating capacity, compression work, evaporating temperature, condensing temperature and COP affecting performance characteristics of refrigeration system. In case of the refrigerant flow control with T.E..V., the superheat and pressure drop of the evaporator varied periodically, but the control with E.E.V., the parameters were very stable. In E.E.v.control, refrigerating capacity, compression work and evaporating temperature were decreased with increasing superheat, and the highest COP was obtained in the range of superheat from 5.deg. C to 15.deg. C.

Studies on the Performance of a Cam Driving Electronic Expansion Valve for Vehicles (캠구동 방식을 적용한 자동차 공조시스템용 전자팽창밸브의 성능에 관한 연구)

  • Kim, Sung Chul
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.17 no.9
    • /
    • pp.732-736
    • /
    • 2016
  • Air conditioning part designs are moving towards higher efficiency and productivity. The expansion device is one of the core parts of an air conditioning system and controls the refrigerant quantity, evaporation load, compression capacity, and condensation capacity. In this study, an electronic expansion valve for two working fluids ($CO_2$ and R134a) was developed for air conditioning systems in vehicles. The valve uses an eccentric cam driving structure instead of a lead screw to decrease manufacturing costs and increase productivity. The pressure resistance and flow rate performance was evaluated using numerical analysis. At maximum operation conditions and burst pressure conditions with $CO_2$, the maximum stresses on the valve model were about 98 MPa and 223 MPa, respectively. The maximum flow rates of $CO_2$ and R134a with different orifice openings were about 550 kg/h and 386 kg/h, respectively. The performance with R134a was verified by experiments.