Experimental study of air side pressure drop and heat transfer characteristics of wave and wave-slit fin-tube heat exchangers

웨이브 및 웨이브-슬릿 열전달촉진 휜-관 열교환기의 공기측 압력강하 및 열전달 특성에 관한 실험

  • 윤백 (삼성전자(주) 공조기기사업부) ;
  • 길용현 (삼성전자(주) 공조기기사업부) ;
  • 박현연 (삼성전자(주) 공조기기사업부) ;
  • 유국철 (삼성전자(주) 공조기기사업부) ;
  • 김영생 (삼성전자(주) 공조기기사업부)
  • Published : 1998.09.01

Abstract

Air side heat transfer and pressure drop for fin-tube heat exchanger with wave and wave-slit fins were measured for various fin spacings and number of tube rows. Outer diameter of the tube including fin collar is 10.07mm, and experiments were done with dry surface condition. Longitudinal and transverse tube spacings of the heat exchangers are 21.65mm and 25mm respectively, and wave depth of the wave fin is 2mm. Experiments were conducted for 1, 2 and 3 rows and 3 different fin spacings, 1.3, 1.5 and 1.7mm. An attempt was made to demonstrate advantage of the enhanced fins over the plane fin by introducing the concept of fan power, Effect of the number of tube rows on heat transfer was discussed in connection with general mechanisms of heat transfer enhancement for fin-tube heat exchanger. Also the effect of hydrophilic coating was investigated. Lastly, correlations for Colburn j-factor and friction factor were developed.

Keywords