Cooling Performance Test of 2-stage Heat Pump System Using River Water as a Heat Source

하천수율원이용 2단압축 열펌프시스템 냉방성능평가

  • Published : 2004.04.28

Abstract

The present study has been conducted to develop a heat pump system using river water of temperature energy which not only belongs to unutilized energy but is a kind of good heat source due to maintain its temperature in a certain degree regardless of seasonal variation. The system did not meet the proposed performance after setup. In this paper, the system performance affected by refrigerant Oil, by pressure drop, or by other factors has been discussed. The followings were obtained : (1) Refrigerant Oil mixture rate was 2.5 in weight percentage, (2) Pressure drop through evaporator was 29.1kPa($3.1^{\circ}C$ in saturated tempearture) (3) Pressure drop from the end of evaporator to compressor inlet was 39.8kPa($4.0^{\circ}C$ in saturated tempearture). (4) The system performance can to be improved by modifying a part of pipe line to compressor, and reducing pressure drop through heat exchangers.