Experimental study on the performance of a brazed plate heat exchanger

용접식 판형 열교환기의 성능에 관한 실험적 연구

  • Published : 2001.06.27

Abstract

An experimental study on the performance evaluation of a brazed plate heat-exchanger with 10RT of normal cooling capacity has been carried out. In the present study, a brazed type plate heat exchanger was tested at a chevron angle $25^{\circ}$ with refrigerant R-22. Mass flux was ranged from $23\;to\;58kg/m^{2}s$ in condensation, and from $22\;to\;53kg/m^{2}s$ in evaporation. The heat transfer coefficient and pressure drop increased with the mass flux increases. The water side pressure drop increased with the cooling water flow rate and chilled water flow rate increases, while mass flux has little affect. It is also shown that the system performance can be improved by enlarging condensation heat transfer area.

Keywords