• 제목/요약/키워드: vacuum interrupter

Search Result 77, Processing Time 0.033 seconds

Simulation and Light Impulse Test Results of Shieldless Vacuum Interrupter (아크쉴드가 없는 진공인터럽터의 유한요소해석 및 뇌임펄스 성능)

  • Yoon, Jae-Hun;Kim, Sung-Il;Kim, Boung-Ouk;Moon, Ki-Lim;Lim, Gee-Jo
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2010.06a
    • /
    • pp.45-45
    • /
    • 2010
  • This paper discusses the simulation and LI(light impulse) test of the shieldless vacuum interrupter concept. The shields of vacuum interrupter play an important role in absorbing the metal vapor. But shield distort the electric field distribution of inner vacuum interrupter. Therefore, the insulation efficiency will improve. if shield of vacuum interrupter inside does not exist. As a result, FEM simulation show that improve distribution of electrical field and equi-potential line. But LI test result dissimilar to FEM simulation result. Shieldless vacuum interrupter model lower BIL(breakdown impulse light) than vacuum interrupter have installed shield. Because conditioning process occurred metal vapor. This paper compared that FEM analysis and LI test of installed shield model and shieldless model.

  • PDF

Discharge Phenomena of Glass Tube Vacuum under AC Applied Voltage (AC 전압하에서 유리진공관의 방전현상)

  • Choi, Yong-Sung;Hwang, Jong-Sun;Lee, Kyung-Sup
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2008.06a
    • /
    • pp.371-372
    • /
    • 2008
  • In this paper, we experimentally investigated discharge phenomena inside vacuum interrupter at 1 to 20 Torr to simulate the vacuum leakage. We used glass type of vacuum interrupter where the internal pressure and the type of gasses can be varied according to requirement. The experiment is conducted under ac applied voltage and the experimental circuit is constructed to simulate the actual circuit used in cubical type insulated switchgear. We used two types of gases such as air and $SF_6$. The use of glass type vacuum interrupter allowed us to measure discharges occurring in vacuum interrupter optically. We measured and discussed the discharge occurring in both gases with a current transformer and ICCD camera. We also revealed that electromagnetic wave spectra emitted by the discharge have same frequency range for both gasses.

  • PDF

An Electric Field analysis of a Vacuum Interrupter by 3 Dimensional Finite Element Method (3차원 유한요소법에 의한 진공 인터럽터의 전계해석)

  • Choi, Seung-Kil;Shim, Jae-Hak;Kang, Hyung-Boo
    • Proceedings of the KIEE Conference
    • /
    • 1998.11c
    • /
    • pp.913-915
    • /
    • 1998
  • This paper describes the application of two and three dimensional electric field analysis for vacuum interrupter with spiral contacts. The electric potentials of floating arc shield and electric fields in a vacuum interrupter are analysed at various gap distances from 1mm to 12mm. The electric potentials of floating shield is increased with the gap distance, which is because the relative position of shield is closer to the fixed contact so that the capacitance distribution inside interrupter is varied. The calculated results show that the maximum value of electric field in a vacuum interrupter with floating shield is nearly same to that without shield at short gap distance below 5mm, however at longer gaps more intensive electric field is achieved in interrupter with shield comparing with the model without shield, which is due to the influence of charged floating shield.

  • PDF

A Finite Element Analysis on the Influence of Floating Shield of a Vacuum Interrupter to the Insulation (진공 인터럽터의 차폐판이 절연에 미치는 영향의 유한요소해석)

  • 최승길;심재학;강형부
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 1998.11a
    • /
    • pp.113-116
    • /
    • 1998
  • This study should investigate to what extent the electric field of a vacuum interrupter might be influenced by the electric potential of floating arc shield. The electric potentials of floating shield and electric fields of a vacuum interrupter are analysed by a finite element method against variation of gap distances from 1mm to 12mm. The electric potentials of floating shield was increased with the gap distance, which is because the relative position of shield is closer to fixed contact so that the capacitance distribution inside interrupter is varied. The calculated results show that the maximum value of electric field of a vacuum interrupter with floating shield is nearly same to that without shield at shorter gap distance(below 5mm), however at larger gaps a significant increment of electric field is achieved in interrupter with shield companying with model without shield, which is due to the influence of charged floating shield.

  • PDF

Three-Dimensional Finite Element Analysis of a Vacuum Interrupter (진공 인터럽터의 3차원 유한요소해석)

  • Choi, Seung-Kil;Kang, Hyung-Boo
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.48 no.10
    • /
    • pp.693-698
    • /
    • 1999
  • Vacuum interrupters have a special asymmetric electrode structure to generate an magnetic field and consequently to increase the interrupting ability. Accordingly 2-dimensional analysis has a large analysis error because radial flux can not be considered. In this paper, in order to analyse the electric field distribution of a vacuum interrupter with arc shield more accurately, 3-dimensional finite element method(FEM) is used. The induced electric potentials of floating shield was increased with the gap distance, which is because the relative position of shield is closer to the fixed contact so that the capacitance distribution inside interrupter is varied. The calculated results also show that the induced potential of shield causes electric field distortion so that the maximum value of electric field in a vacuum interrupter with arc shield is higher than that without one.

  • PDF

Ion Transport and High Frequency Dielectric of the Hollandite Nax$(Ti_{8-x}Cr_x)O_{16}$ (교류전압 인가 상태에서 저압 진공관의 방전현상)

  • Wang, Gang;Choi, Yong-Sung;Lee, Kyung-Sup
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2008.11a
    • /
    • pp.243-244
    • /
    • 2008
  • We experimentally investigated discharge phenomena inside vacuum interrupter at 1 to 20 Torr to simulate the vacuum leakage. We used glass type of vacuum interrupter where the internal pressure and the type of gasses can be varied according to requirement. The experiment is conducted under ac applied voltage and the experimental circuit is constructed to simulate the actual circuit used in cubical type insulated switchgear. We used two types of gases such as air and $SF_6$. The use of glass type vacuum interrupter allowed us to measure discharges occurring in vacuum interrupter optically. We measured and discussed the discharge occurring in both gases with a current transformer and ICCD camera. We a1so revealed that electromagnetic wave spectra emitted by the discharge have same frequency range for both gasses.

  • PDF

Discharge Phenomena of Low Pressure Vacuum under AC Applied Voltage (교류전압하에서 저압 진공관의 방전현상)

  • Jun, Jin;Choi, Yong-Sung;Lee, Kyung-Sup
    • Proceedings of the KIEE Conference
    • /
    • 2008.07a
    • /
    • pp.2301-2302
    • /
    • 2008
  • We experimentally investigated discharge phenomena inside vacuum interrupter at 1 to 20 Torr to simulate the vacuum leakage. We used glass type of vacuum interrupter where the internal pressure and the type of gasses can be varied according to requirement. The experiment is conducted under ac applied voltage and the experimental circuit is constructed to simulate the actual circuit used in cubical type insulated switchgear. We used two types of gases such as air and SF6. The use of glass type vacuum interrupter allowed us to measure discharges occurring in vacuum interrupter optically. We measured and discussed the discharge occurring in both gases with a current transformer and ICCD camera. We also revealed that electromagnetic wave spectra emitted by the discharge have same frequency range for both gasses.

  • PDF

A Study on the Effect of the Contact Electrode Slits in the Vacuum Interrupter with Axial Magnetic Field Type (종자계형 진공 인터럽터에서 접점전극 슬릿의 영향에 관한 연구)

  • 하덕용;강형부;최승길;최경호
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.15 no.9
    • /
    • pp.822-829
    • /
    • 2002
  • This paper deals with the distribution characteristics of the current density and axial magnetic flux density for each slits made on the contact electrode in the vacuum interrupter with axial magnetic field type using 3-dimension finite element analysis. It has been known that the presence of an axial magnetic field parallel to the current flow in the arc plasma can increase the high current breaking capacity of vacuum interrupter by carrying out the arc plasma from constricted mode to diffusion mode. The axial magnetic field is created of itself by current flow in the segments of coil electrode behind the contact electrode. The analyzed results show that if the slits are made in the contact electrode, they can increase the current density and axial magnetic flux density in the contact electrode surface and at the gap distance, which is due to decrease the effect of eddy currents flowing in the contact electrode. The phase shift due to eddy currents, defined 3s time difference between the maximum value of current and axial magnetic field, is decreased still more by increasing the number of slits made in the contact electrode at the center point of gap distance. These results demonstrate that 3-dimension finite element analysis has a great deal of merits in the development and evaluation of new electrode at the design of vacuum interrupter.

Analysis of the electromagnetic phenomena in vacuum interrupter with axial magnetic field type for Safety break (안전차단을 위한 축자계형 진공인터럽터의 전자계 현상 해석)

  • 서상현
    • Journal of the Korea Safety Management & Science
    • /
    • v.5 no.4
    • /
    • pp.87-95
    • /
    • 2003
  • The purpose of this paper is analyses about in 12kV/50kA vacuum interrupter with an axial magnetic field type electrode system through the studies of electromagnetic phenomena for the possess of Safety break. Vacuum interrupter is important in electric safety part. In this paper, we performed analysis of electric field, magnetic field, current density in AMF electrode using the Maxwell 3D simulation.

Effects of Electrode Configurations on the Characteristics of Axial Magnetic Fields in Vacuum Interrupter (전극형상 변화가 진공차단기내 축방향 자기장 특성에 미치는 영향)

  • Hwang, Jung-Hoon;Lee, Jong-Chul;Kim, Youn-Jea
    • Transactions of the Korean Society of Mechanical Engineers A
    • /
    • v.32 no.1
    • /
    • pp.7-12
    • /
    • 2008
  • The vacuum interrupter (VI) is used for medium-voltage switching circuits due to its abilities and advantages as a compacted environmental friendly circuit breaker. In general, the application of a sufficiently strong axial magnetic field (AMF) permits the arc to be maintained in a diffused mode to a high-current vacuum arc. A full understanding of the vacuum arc physics is very important since it can aid to improve the performance of vacuum interrupter. In order to closely examine the vacuum arc phenomena, it is necessary to predict the magnetohydrodynamic (MHD) characteristics by the multidisciplinary numerical modeling, which is coupled with the electromagnetic and hydrodynamic fields, simultaneously. In this study, we have investigated the effect of changing geometrical parameters for electromagnetic behaviors of high-current vacuum arcs with two different types of AMP contacts, which are coil-type and cup-type, using a commercial finite element analysis (FEA) package, ANSYS. The present results are compared with those of MAXWELL 3D, a reliable electromagnetic analysis software, for verification.