• 제목/요약/키워드: smoke compartment

검색결과 50건 처리시간 0.031초

건축물의 연기확산 방지 및 제어를 위한 방연구획의 법제화 제안 (Proposal of Legislation of Smoke Compartment for Prevention and Control of Smoke Diffusion in Buildings)

  • 권영진;진승현;김혜원
    • 한국건축시공학회:학술대회논문집
    • /
    • 한국건축시공학회 2019년도 추계 학술논문 발표대회
    • /
    • pp.96-97
    • /
    • 2019
  • According to building law, there are only regulations on the fire prevention compartments that can perform the function of partial smoke compartment, but the building law management of the smoke compartment for effective smoke diffusion prevention and control is not possible. The lack of control on the smoke compartment such as leakage rate on the penetrating part, and the lack of leakage rate in the design of smoke control of fire safety law resulted in the absence of fundamental safety technology. Therefore, this study seeks to find solutions to domestic problems after reviewing relevant domestic laws and regulations.

  • PDF

대형공간의 연기확산 방지를 위한 국내·외 방연구획 기준 분석에 관한 연구 -고양시 터미널 화재 사례 분석을 중심으로- (A Study on the Smoke Compartment Standards Analysis of Domestic and Abroad for Prevention of Smoke Spread in Large-Scale Buildings -Focused on the Analysis of Goyang Bus Terminal Fire Incident-)

  • 김혜원;한지우;이병흔;진승현;권영진
    • 한국건축시공학회:학술대회논문집
    • /
    • 한국건축시공학회 2018년도 춘계 학술논문 발표대회
    • /
    • pp.118-119
    • /
    • 2018
  • In this study, it analyses the problems of the Fire Compartment in Goyang Bus Terminal. Based on analysed data, it is confirmed the necessity of the Smoke Compartment installation for Protecting the Smoke Spread in Large-Scale Buildings using of FDS(Fire Dynamics Simulation). In addition it suggest that the necessity of Smoke Compartment application method and Development of Design Guideline.

  • PDF

구획화재의 출입구를 통한 광학적 연기밀도 측정의 불확실성 해석 (Uncertainty Analysis of the Optical Smoke Density Measurement through the Doorway in a Compartment Fire)

  • 김성찬
    • 한국화재소방학회논문지
    • /
    • 제27권2호
    • /
    • pp.75-79
    • /
    • 2013
  • 본 연구는 구획화재의 출입구를 통한 연기밀도를 정량적으로 측정하고 측정기법의 신뢰성을 평가하기 위해 불확실성 해석을 수행한다. 메탄 화재 강도에 따른 축소모형 구획공간의 출입구 상층부를 통해 유출되는 연기 유동에 대해 광소멸 측정을 수행하고 Bouguer's의 법칙을 적용하여 연기밀도를 산정하였다. 광투과율, 경로길이, 질량비광소멸상수에 대하여 연기밀도의 측정 불확실도를 평가하였으며 계산된 연기밀도 측정의 확장불확실도는 20% 정도이며 신뢰수준은 95% 이다. 준정상상태의 화재 발열량에 대하여 출입구에서의 평균 연기밀도를 산정하였으며 구획공간내부의 총괄당량비 증가에 따라 출입구의 연기농도가 선형적으로 증가하는 경향을 보였다.

건축물 제배연시나리오 작성을 위한 구획실 발열특성 연구 (Study on Characteristics of Heat Release Rate in Compartment of Building for Scenario of Smoke Management)

  • 김정엽;신현준
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2009년도 하계학술발표대회 논문집
    • /
    • pp.398-403
    • /
    • 2009
  • The theoretical bases on characteristics of heat release rate in compartment of building for scenario of smoke management are introduced and the numerical applications to simple compartment model are carried out. The growth stage which is important for smoke management design is modelled as t-squared fire curve including fire growth coefficient with related to growth rate. The conditions for the happening of flashover is presented such as $600^{\circ}C$ of temperature or $20kW/m^2$ of radiation heat flux. After the flashover happen, the fire in compartment changes to fully developed fire having the characteristics of ventilation-controlled fire. As the result of numerical analysis to simple compartment model, the time to reach 900K under ceiling for condition of medium growth is twice for condition of fast growth.

  • PDF

Hot smoke test 를 위한 화염 제어 방법 (Flame control method for hot smoke test)

  • 김진국
    • 한국화재소방학회:학술대회논문집
    • /
    • 한국화재소방학회 1996년도 학술발표회
    • /
    • pp.30-33
    • /
    • 1996
  • This paper presents the technical basis for hot smoke test intended to investigate the effectiveness of smoke ventilation system in both high-rise building and those containing atria and/or galleria. Smoke is particularly serious hazard in these building in which considerable time is required for complete evacuation. It is widely recognised that the effectiveness of large smoke ventilation system can be difficult to confirm by a critical analysis of the system design calculation. Thus a hot smoke test is recently introduced through the experiences of many attempts. Diffusion flames used for hot smoke test have a higher flame length, so that those can not be applied to small compartment. Therefore the objective of this paper is introducing the method of flame control which can be applied to any size of compartment

  • PDF

CFD를 이용한 단일 구획 공간에서의 연기와 CO 확산 시뮬레이션 (CFD-based simulation of fire-induced smoke and carbon monoxide transportation in the single compartment)

  • 손윤석;김형권;오형식;김태옥;신동일
    • 한국화재소방학회:학술대회논문집
    • /
    • 한국화재소방학회 2008년도 춘계학술논문발표회 논문집
    • /
    • pp.290-293
    • /
    • 2008
  • In this study, the Computational Fluid Dynamics (CFD) has been used to analyze the smoke movement and the carbon monoxide concentration distribution, both vertically and longitudinally, in a compartment, based on conservation laws. The Fire Dynamics Simulator (FDS) developed by National Institute of Standards and Technology (NIST) was used for numerical simulations using Reynolds averaged Navier-Stokes equations (RANS) model to solve for time-averaged properties. Results show, as a function of time, a detailed distribution of temperature and carbon monoxide concentration changing against the height above the floor and those changes alongside the distance away from the fire source. Fire-induced smoke and toxic gases like CO are more dangerous in a confined space. The result of study may contribute in designing the smoke evacuation system based on the precise tenable condition.

  • PDF

급기가압 조건에서 복합 구획 공간 화재의 연기 거동에 대한 수치해석 연구 (Numerical Simulation on Smoke Movement in Multi-Compartment Enclosure Fires under Pressurized Air Supply Conditions)

  • 고권현
    • 한국화재소방학회논문지
    • /
    • 제32권6호
    • /
    • pp.15-21
    • /
    • 2018
  • 본 연구에서는 급기가압 조건에서 거실, 부속실 및 계단실로 구성된 복합 구획 공간에 대해 화재해석을 수행하고 가압 및 환기 조건에 따른 화재 연기의 유동 특성을 분석하였다. 화재 해석은 유효누설면적을 측정하기 위해 제작된 누기율 시험설비에 대하여 수행하였으며, 화재의 거시적 특성과 각 구획에 대한 유동 및 압력 특성의 분석을 통해 급기가압 조건에서의 화염 및 연기 거동에 대한 이해를 증진시키고자 하였다. 화재 해석 결과는 화재 발열량의 크기가 환기 시스템에 의해 공급되는 공기량에 의해서 민감하게 영향을 받게 됨을 보여주었다. 거실과 부속실에서의 속도분포 분석 결과를 통해 급기가압의 조건에서도 화재 연기가 문의 상층부를 통해 부속실로 유출될 수 있음을 확인하였다. 이를 통하여 급기가압 제연시스템의 설계와 적용에 있어서 화재 크기와 공간적 특성과 같은 요인을 고려하는 것이 매우 중요하다는 것을 확인할 수 있었다.

구획화재에서의 스프링클러 작동시간 예측 연구 (Prediction of sprinkler activation time in compartment fire)

  • 김명배;한용식
    • 한국화재소방학회논문지
    • /
    • 제10권4호
    • /
    • pp.13-18
    • /
    • 1996
  • 구획화재에서 스프링클러 작동순간의 연층온도와 연층높이를 구하는 모델링 방법을 기술하였다. 스프링클러 작동모델에서의 시정수는 실험으로부터 얻어진 RTI(Response time index)와 스프링클러 주위의 유속을 평가할 수 있는 실험식으로부터 구하였고, 시간에 따른 연층온도 변화는 기존의 2층 zone model을 이용하였다. 모델에 의한 계산결과를 검증하기 위하여 가솔린 pool 화재를 이용한 실험을 수행하여 계산결과와 실험결과를 비교하였다. 본 연구의 결과인 스프링클러 작동순간의 연층온도와 높이는 스프링클러 분무와 화재 Plume의 상호작용을 해석하기 위한 필요한 입력자료로 사용할 수 있다.

  • PDF

수정된 체적열원모델을 이용한 실내 화재의 연기농도 예측 (Numerical Prediction of Smoke Concentration in a Compartment Fire by Using the Modified Volumetric Heat Source Model)

  • 김성찬;이성혁
    • 설비공학논문집
    • /
    • 제18권4호
    • /
    • pp.344-350
    • /
    • 2006
  • The present study investigates the characteristics of fire-driven heat flows and gas concentration in a compartment fire by using the modified VHS model (MVHS). The main idea of this model is to add some source terms for combustion products and oxygen consumption to the original VHS model for providing more accurate and useful information on gas concentration distributions as well as thermal fields. It is found that the present MVHS model shows fairly good agreement with the experimental data and the eddy breakup combustion model. The tilting angle of fire plume calculated by MVHS is larger than that of EBU model because the fire source of VHS is affected by ventilating flow less than EBU. However, this discrepancy is apparently reduced in the downstream region of fire source.

업무용 빌딩의 피난 성능 검토에 관한 연구 (A Study on the Evacuation Performance Review for the Office Buildings)

  • 오혁진;백승태;김우석;이수경
    • 한국화재소방학회논문지
    • /
    • 제17권3호
    • /
    • pp.1-6
    • /
    • 2003
  • 본 연구에서는 특정의 업무용 건축물에 대해서 화재 및 피난 시나리오를 선정하여 FAST 3.1.7(전실화재 예측), SIMULEX 32-bit(피난시간의 예측), JASMINE 3.25d(특정시간까지의 연기 유동성 평가)등의 S/W를 이용하여 이를 평가했으며 그 결과는 다음과 같다. Scenario #1 결과, 화재실에서 전실화재가 발생하지 않았고, 층 피난시간은 25.2 sec로 나타났으며 이때까지의 FAST 3.1.7결과에서 연기층은 2.4m를 기록, 연기유동성 평가에서도 재실자들은 연기의 피해(가시거리, 독성)없이 피난이 완료될 것으로 나타났다. Scenario #2 결과, 화재실에서 6 min 33.2 sec에 전실화재가 발생했으며, 수계산에 의한 피난시간은 5 min 23sec로 나타났다. 본 대상건물에 대해서 선정한 Scenario #1, #2 모두 인명안전설계는 적정하게 설계되었다고 판단된다.