• 제목/요약/키워드: short-circuit transformer

검색결과 114건 처리시간 0.025초

Prediction of Change in Equivalent Circuit Parameters of Transformer Winding Due to Axial Deformation using Sweep Frequency Response Analysis

  • Sathya, M. Arul;Usa, S.
    • Journal of Electrical Engineering and Technology
    • /
    • 제10권3호
    • /
    • pp.983-989
    • /
    • 2015
  • Power transformer is one of the major and key apparatus in electric power system. Monitoring and diagnosis of transformer fault is necessary for improving the life period of transformer. The failures caused by short circuits are one of the causes of transformer outages. The short circuit currents induce excessive forces in the transformer windings which result in winding deformation affecting the mechanical and electrical characteristics of the winding. In the present work, a transformer producing only the radial flux under short circuit is considered. The corresponding axial displacement profile of the windings is computed using Finite Element Method based transient structural analysis and thus obtained displacements are compared with the experimental result. The change in inter disc capacitance and mutual inductance of the deformed windings due to different short circuit currents are computed using Finite Element Method based field analyses and the corresponding Sweep Frequency Responses are computed using the modified electrical equivalent circuit. From the change in the first resonant frequency, the winding movement can be quantified which will be useful for estimating the mechanical withstand capability of the winding for different short circuit currents in the design stage itself.

전자계-기계계 결합해석에 의한 건식변압기의 단락강도 예측 (Short Circuit Electromagnetic Force Prediction by Coupled Electromagnetic-Mechanical Field Analysis of Dry-Type Transformer)

  • 안현모;한성진
    • 전기학회논문지
    • /
    • 제60권2호
    • /
    • pp.301-308
    • /
    • 2011
  • This paper deals with the coupled electromagnetic-mechanical field analysis for short-circuit electromagnetic force of the dry-type transformer. The short-circuit currents are calculated using external circuit in accordance with short-circuit test equipment. According to short-circuit current, the generated magnetic leakage flux density in dry-type transformer model is calculated by finite element method. The radially-directed electromagnetic forces in windings are calculated using electromagnetic field analysis and then axially-directed electromagnetic forces in windings are calculated using electromagnetic-mechanical field analysis. The calculated axially-directed electromagnetic forces in high voltage winding are compared to those of measured ones and showed good agreement with experimental results.

3상계통에서 단상변압기에 대한 단락전류계산 기법 (A Technique for a Short-Circuit Current Calculation to The Single-Phase Transformer in the Three-Phase Systems)

  • 박재훼;진태석
    • 전기학회논문지P
    • /
    • 제57권2호
    • /
    • pp.170-175
    • /
    • 2008
  • This paper describes the exact short-circuit current calculation technique for the single-phase transformer which is installed in the three-phase systems and shorted in the secondary side. Not only the results for a short-circuit current calculation in the existing literatures are wrong, but also little literature deals with the short-circuit current for a single-phase transformer. So, this paper presents a theoretical study and calculation method for a single-phase short current. The validity of the presented method is investigated through Simulation using "Power Tools" and "PSim" program.

전력용 변압기의 단락강도 해석 (Computational Analysis of Short-Circuit Stresses in Power Transformer Windings)

  • 최영길
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2002년도 추계학술대회 논문집 전기기기 및 에너지변환시스템부문
    • /
    • pp.147-150
    • /
    • 2002
  • This paper describes the work performed by computer simulation to achieve a satisfactory method of predicting the short circuit withstand strength of transformer which, may be too big for test due to physical or economic reasons. In fact, the windings of power transformer are subjected to extremely severe stresses under short-circuit condition. From our work, however, were computed such stresses as buckling, tending and compression occurring in transformer windings.

  • PDF

여자전류 재단에 따른 단락 시험용 변압기의 절연영향 평가 (Estimating the Effect of Overvoltage Results from Excitation Current Chopping in Short-circuit Transformer)

  • 오승렬;박지훈;박종화
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2007년도 추계학술대회 논문집 전력기술부문
    • /
    • pp.78-80
    • /
    • 2007
  • The residual flux in transformer's iron cores leads to a distortion of short-circuit current occasionally. And some considerable distortion may have effect on the validation of the test results. To avoid the substantial distortion, a suitable pretest is performed before the actual test. In case of applying this method there must be excessive overvoltage due to switching of an unloaded transformer and chopping of an excitation current. The purpose of this paper is estimate that the effect of the overvoltage results from this phenomenon on insulation performance of short-circuit transformer.

  • PDF

배전용 변압기의 단락시험 불량원인 및 그 대책에 관한 연구 (A Study on the Cause and Countermeasures of the Short-Circuit Test Failures of the Distribution Transformer)

  • 박병락;박훈양;신희상;김재철
    • 조명전기설비학회논문지
    • /
    • 제25권6호
    • /
    • pp.75-81
    • /
    • 2011
  • This study aims to research and analyze the cause and countermeasures of the short-circuit test failures of the distribution transformer, which captures failure share at the highest level when carrying out its performance test. For this purpose, the research was done on the basis of 77 failure cases out of 998 tests in total performed by the Korea Electrotechnology Research Institute(KERI) from 2004 to 2010. Based on the research, the paper also includes analysis of the causes of the short-circuit test failures in its early stage of transformer development and proposes its countermeasures accordingly.

단락시험용 대전류변압기 돌입전류특성에 관한 연구 (THE STUDY 01 CHARACTERISTICS OF INRUSH CURRENTS FOR HIGH POWER SHORT-CIRCUIT TESTING TRANSFORMER)

  • 노창일;나대열;김선구;정흥수;김원만;이동준;김선호
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2006년도 제37회 하계학술대회 논문집 B
    • /
    • pp.695-696
    • /
    • 2006
  • The inrush current of transformer cause saturation effects of recovery voltage for short-circuit power testing. the inrush current depends on the residual flux of the transformer core. when inrush current occurs, it is contains a d.c. component and the high harmonic content of the current are of importance to relay protection of testing circuit. this paper describes of decrease method of inrush current for high power short-circuit testing transformer.

  • PDF

Couette 흐름현상을 이용한 초고압변압기의 유동대전 기구 연구 (A Study on the Electrification Mechanism in UHV Transformer by Couette Flow)

  • 곽희로;정용기;권동진
    • 한국조명전기설비학회지:조명전기설비
    • /
    • 제9권4호
    • /
    • pp.93-102
    • /
    • 1995
  • The purpose of this paper is to analyze the streaming electrification mechanism (SEM) generated in UHV transformer. This experiment used Couette Charger and interpreted the mechanism hydromechanically and electromagnetically. This work estimated the turbulent core density ($\rho$o) by measuring the short circuit current (isc) and the open circuit voltage (νoc) generated in Couette Charger and also studied the changes of the short circuit (isc), the open circuit voltage (νoc), the turbulent core density ($\rho$o) and the conductivity ($\sigma$) with adding BTA to restrain streaming electrification. as a result adding BTA increased the conductivity of oil and decreased the turbulent core density($\rho$o).

  • PDF

단락 전류 왜형방지를 위한 변압기 잔류자속제어 (Controlling the Residual Flux in Transformer to Prevent the Distortion of Short-circuit Current)

  • 오승렬;박지훈;박종화
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2006년도 추계학술대회 논문집 전력기술부문
    • /
    • pp.237-239
    • /
    • 2006
  • The residual flux(${\psi}_r$) in transformer's iron cores cause the distortion of short-circuit current occasionally. And some considerable distortion effect on the validation of test results. To prevent this situation, there needs some suitable control of residual flux through the pretest. This paper deals with the how to control the residual flux in pretest and the comparison between the two test results which were obtained by different test method.

  • PDF

Zig-Zag 귄선에 의한 내철형 주상변압기 개발에 관한 연구 (A study on the Development of the Shell-type Pole Transformer Using the Zig-Zag Winding)

  • 민윤홍;신대철
    • 조명전기설비학회논문지
    • /
    • 제21권8호
    • /
    • pp.121-128
    • /
    • 2007
  • 본 논문에서는 세계최초로 내철형 주상변압기 코일의 권선을 일반적인 권선방법에서 Zig-Zag(가칭) 권선방법으로 설계 제작하는 방법을 제안하였으며, 또한 바니시 함침공정을 생략하고 단락강도 및 절연내력을 향상시킬 수 있는 내철형 변압기용 권선의 신프레임 구조개발 내용을 제안하였다. 기존의 주상변압기 권선방법에 비하여 전기절연 측면에서 층간 절연지의 사용매수 및 두께를 획기적으로 절감할 수 있는 장점이 있다. 또한 원가절감과 손실저감 및 단락기계력 대처능력이 우수함을 검증하였으며 국내전력회사 배전계통 주상변압기에 유용하게 활용할 수 있다.