• Title/Summary/Keyword: real-scale fire test

Search Result 84, Processing Time 0.029 seconds

An Experimental Study on Fire Safety Performance of Glass Wool Sandwich Panel (그라스울 샌드위치패널의 화재 안전 성능에 대한 실험적 연구)

  • Kweon, Oh-Sang;Yoo, Yong-Ho;Kim, Heung-Youl;Min, Se-Hong
    • Fire Science and Engineering
    • /
    • v.26 no.5
    • /
    • pp.21-27
    • /
    • 2012
  • A real A real scale fire test was performed in accordance with KS F ISO 9705 test method to investigate the combustion characteristics of glass wool sandwich panels. To do this, six kinds of specimens having different density and thickness were examined. The glass sandwich panels were installed inside the room, which had internal dimensions of 2.4 m wide${\times}3.6m$ deep${\times}2.4m$ high. also, combustion characteristic are determined through the exposure of specimens to flame by the propane gas burner has a capacity of 100 kW (10 minutes) and 300 kW (10 minutes) for total 25 minutes of test time. Results of the real sale fire test, it was found that maximum HRR of each specimen was 333.2~365.5 kW, maximum heat flux was 12.4~12.9 kW/$m^2$ And, maximum internal temperature for all specimens was not over $500^{\circ}C$. During the real scale fire test, flash-over didn't occur and the difference by density and thickness of specimen was not found from the results of HRR, heat flux, and internal temperature measurement.

An Experimental Study for Vertical Flame Spread Analysis of Aluminum Composite Panel (알루미늄 복합 패널의 수직 화염전파속도 분석을 위한 실험적 연구)

  • Kim, Il-Kwon;Kim, Bong-Chan;Ku, In-hyuck;Seo, Dong-Gu;Lim, Nam Gi;Kwun, Young-Jin
    • Proceedings of the Korean Institute of Building Construction Conference
    • /
    • 2013.05a
    • /
    • pp.315-317
    • /
    • 2013
  • To analyze vertical fire spreadability of aluminum composite panel, real scale test of aluminum composite panel and fire retardant aluminum composite panel was conducted as well as analysis of domestic code, test and domestic reaserch resulted in following conclusion. Fire spread risk assessment of aluminum Composite Panel is impossible with the current regulations (Cone Calorimeter Test). It need to changes of regulatory and combustion expanded risk assessment and regulatory changes in the test methods need to be judged. Also, there is quite a big different between the general aluminum Composite Panel and semi-non combustible of aluminum Composite Panel. However it is also deemed to be danger when present in the sidewall to the top consisting of fire spread. From now on, it is needed the study about interpretation of fire spread and sidewall of vertical fire spread analysis not only experiments for aluminum Composite Panel.

  • PDF

A real scale test on performance of water spray systems in tunnel fire (터널화재시 물분무소화설비의 성능에 대한 실대시험)

  • Park, Kyung-Hwan;So, Soo-Hyun
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.12 no.4
    • /
    • pp.341-347
    • /
    • 2010
  • The performance of water spray system installed to reduce risks of tunnel fire is investigated by a real tunnel fire test. In case of A class fire, Pool fire, and car fire, the nozzle of water spray has had a marvelous effect to reduce the temperature of hot smoke. And it is verified to have remarkable cooling effects when there is the air flow in a tunnel. Though this results, water spray system will be able to prevent a fire jump to decrease the air temperature in a tunnel and to protect tunnel facilities by the fire control.

Temperature distribution in a full-scale steel framed building subject to a natural fire

  • Wald, Frantisek;Chladna, Magdalena;Moore, David;Santiago, Aldina;Lennon, Tom
    • Steel and Composite Structures
    • /
    • v.6 no.2
    • /
    • pp.159-182
    • /
    • 2006
  • Current fire design codes for determining the temperature within the structural elements that form part of a complete building are based on isolated member tests subjected to the standard fire. However, the standard time-temperature response bears little relation to real fires and doesn't include the effects of differing ventilation conditions or the influence of the thermal properties of compartment linings. The degree to which temperature uniformity is present in real compartments is not addressed and direct flame impingement may also have an influence, which is not considered. It is clear that the complex thermal environmental that occurs within a real building subject to a natural fire can only be addressed using realistic full-scale tests. To study global structural and thermal behaviour, a research project was conducted on the eight storey steel frame building at the Building Research Establishment's Cardington laboratory. The fire compartment was 11 m long by 7 m wide. A fire load of $40kg/m^2$ was applied together with 100% of the permanent actions and variable permanent actions and 56% of live actions. This paper summarises the experimental programme and presents the time-temperature development in the fire compartment and in the main supporting structural elements. Comparisons are also made between the test results and the temperatures predicted by the structural fire Eurocodes.

Fire Resistance of Concrete Filled Double Skin Tubular Columns under Axial Load (일정 축력을 받는 Double CFT기둥의 내화성능 평가)

  • Chung, Sang-Keun;Kim, Sun-Hee;Lee, Seong-Hui;Choi, Sung-Mo
    • Journal of Korean Society of Steel Construction
    • /
    • v.23 no.1
    • /
    • pp.51-59
    • /
    • 2011
  • Although an uncoated CFT column with a high axial-force ratio can be used to secure fire resistance for two hours or less in low-rise buildings, it does not satisfy the three-hour-long fire resistance required in high-rise buildings. Accordingly, so that the uncoated CFT column could be used for high-rise buildings, additional measures for the improvement of its fire resistance should be proposed. In this regard, the use of a Double CFT column as a measure for improving the fire resistance of the uncoated CFT column was proposed in this paper. A fire resistance test was conducted on an uncoated CFT column and a Double CFT column in real scale, under a load. Through such test, the effect of the Double CFT column on fire resistance was evaluated and then compared with that of a variant shape of the cross-section of a steel column.

The Study on Compartment Fire Experiment According to Fire Load (화재하중에 따른 구획화재 실험 연구)

  • Kweon, Oh-Sang;Kim, Heung-Youl
    • Fire Science and Engineering
    • /
    • v.31 no.6
    • /
    • pp.16-22
    • /
    • 2017
  • In Korea, performance-based fire safety designs are being discussed to deal with the various risks of fire in complex and diverse types of structure. However, performance-based fire safety designs are not actively employed because it is difficult to estimate the fire characteristics related to the various factors in buildings. In this study, real scale fire tests were conducted based on fire severity levels and fire loads provided in He New Zealand Building Code, in order to use the results as guidelines and fundamental data for performance-based designs. In the real scale fire tests conducted in a 10MW full-scale calorimeter, wood cribs were placed in a $2.4(L){\times}3.6(W){\times}2.4(H)m$ mock-up of a compartment which had one $0.8(L){\times}2.0(H)$ opening for different fire loads and heating was continued until all of the wood cribs were burned down. The heat release rate started to increase rapidly 90 seconds after the wood cribs caught fire. In the test with a fire load level 1, the maximum heat release rate of 4743.4 kW was reached at 244 second. In the test with fire load level 2, a maximum heat release rate of 5050.9 kW was reached at 497 second. In the test with fire load level 3, a maximum heat release rate of 4446.9 kW was reached at 677 second.

A Study on the evaluation of the auditory guide facility under emergency situation (비상시 청각형 유도시설의 유도성능 평가에 관한 연구)

  • Na, Wook-Jung;Jeon, Gyu-Yeob;Hong, Won-Hwa
    • Proceedings of the SAREK Conference
    • /
    • 2006.06a
    • /
    • pp.1205-1208
    • /
    • 2006
  • Today, our city structure is being complicated from the development of industry. Invisible losses, life and fortune loss caused by arson is embossed in our society. The preparation of counter plan about increasing factors of fire damage is not easy. With respect to mankind life, however, it is very important. Therefore, the focus of this research examine refuge degree in each smoke density level when a fire break out in the space. I evaluated auditory guide facility thorough real scale test. In this thesis, I will propose the efficient refuge deriving facilities.

  • PDF

An Experimental Study on Fire Spreading External Wall of Buildings Using Dry Construction Method (건식공법을 이용한 건축물의 외벽 화재 확산의 실험적 연구)

  • Park, Jung-Woo;Cho, Nam-Wook
    • Fire Science and Engineering
    • /
    • v.32 no.4
    • /
    • pp.75-85
    • /
    • 2018
  • The Grenpell tower fire in England in June of 2016 is a representative example of damage caused by a vertical fire spreading through external insulation. Organic insulation materials, which are widely used in external insulation, have the disadvantage that they have good insulation performance but are vulnerable to fire. Aluminum composite panels are used as exterior wall finishing materials, and plastics used in aluminum are regarded as the cause of vertical fire spread. Due to the steel frame used to secure the aluminum composite panel to the outer wall, a cavity is formed between the outer wall and outer wall finish. When a fire occurs on the outer wall, the flammable outer wall as well as the flame generated from the heat-insulating material spreads vertically through the cavity, resulting in damage to people and property. In Korea, material unit performance tests are carried out by the Ministry of Land, Infrastructure and Transport notice 2015 - 744. However, in the UK, the BS 8414 test is used to measure the vertical fire spreading time on the outer wall in real scale fire tests. In this study, the risk of external wall fire was evaluated in an actual fire by conducting a real scale wall fire test (BS 8414), which was carried out in Europe, using aluminum composite panels of semi-noncombustible materials suitable for current domestic standards. The purpose of this study was to confirm the limitations of material unit evaluation of finishing materials and to confirm the necessity of introducing a system to prevent the spread of outer wall fire through an actual scale fire test.

Experimental investigation of the behaviour of a steel sub-frame under a natural fire

  • Santiago, Aldina;Simoes da Silva, Luis;Vaz, Gilberto;Vila Real, Paulo;Lopes, Antonio Gameiro
    • Steel and Composite Structures
    • /
    • v.8 no.3
    • /
    • pp.243-264
    • /
    • 2008
  • This paper details a testing facility ("NATURAL FIRE FACILITY") that allows closely-controlled experimental testing on full-scale sub-frames while reproducing the spatially transient temperature conditions measured in real fires. Using this test facility, an experimental investigation of six steel sub-frames under a natural fire was carried out at the Department of Civil Engineering of the University of Coimbra. The main objective of these tests was to provide insight into the influence of these connection types on the behaviour of steel sub-structures under fire. The experimental layout is defined by two thermally insulated HEA300 columns and an unprotected IPE300 beam with 5.7 m span, supporting a composite concrete slab. Beam-to-column connections are representative of the most common joint type used on buildings: welded joints and extended, flush and partial depth plate. Finally, the available results are presented and discussed: evolution of the steel temperature; development of displacements and local deformations and failure modes on the joints zone.