• 제목/요약/키워드: ratio of induced voltages,

검색결과 8건 처리시간 0.023초

A Transformer Protection Relay Based on Induced Voltages

  • Kang, Yong-Cheol;Lee, Byung-Eun
    • KIEE International Transactions on Power Engineering
    • /
    • 제3A권2호
    • /
    • pp.70-78
    • /
    • 2003
  • This paper describes a transformer protection relay based on induced voltages. The ratio of the induced voltages of the primary and secondary windings is equal to the turns ratio during normal operating conditions such as magnetic inrush, overexcitation, and steady state, but it differs from the turns ratio in the case of internal faults. For a single-phase and a three-phase Y-Y transformer, the induced voltages are estimated and the ratios are compared with the turns ratio. For three-phase Y-Δ transformers, the differences between the induced voltages are estimated to use the line currents because delta-winding currents are practically unavailable. The proposed relay is tested under various conditions such as magnetic inrush, internal winding faults, overexcitation, and different core characteristics. The results evidently indicate that the relay successfully discriminates internal faults from magnetic inrush and overexcitation. This paper concludes by implementing the relay into a TMS320C6701 digital signal processor and reports satisfactory results. The relay requires no hysteresis data and can reduce the operating time of a relay.

유기전압비를 이용한 변압기 보호계전 알고리즘 (A Transformer Protective Relaying Algorithm Using the Ratio of Induced Voltages)

  • 강용철;이병은
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제49권10호
    • /
    • pp.524-530
    • /
    • 2000
  • This paper presents a transformer protective relaying algorithm using the ratio of induced voltages. The proposed algorithm calculates primary and secondary voltage from currents and voltages of primary and secondary windings. The ratio of primary and secondary induced voltages is equal to the turn ratio in case of the steady state and magnetic inrush. On the other hand, the ratio is different form the turn ratio in case of internal winding faults. The algorithm does not require B-H curve and can reduce the relay's operating time.

  • PDF

유기 전압비를 이용한 3권선 변압기 보호계전 알고리즘 (A Three-Winding Transformer Protective Relaying Algorithm Based on the Induced Voltages)

  • 강용철;이병은
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제52권3호
    • /
    • pp.173-178
    • /
    • 2003
  • This paper proposes a three-winding transformer protective relaying algorithm based on the ratio of the induced voltages (RIV). The RIV of the two windings is the same as the turn ratio for all operating conditions except an internal fault. For a single phase and a three-phase transformer containing the wye-connected windings, the induced voltages of the windings are estimated. For a three-phase transformer containing the delta-connected windings, the induced voltage differences are estimated using the line currents, because the winding currents are practically unavailable. The algorithm can identify the faulted phase and winding if a fault occurs on one phase of a winding. The test results clearly show that the algorithm successfully discriminates internal winding faults from magnetic inrush. The algorithm not only does not require hysteresis data but also can reduce the operating time of a relay.

유기전압비를 이용한 변압기 보호계전 알고리즘 (A Protective Relaying Algorithm for Transformers Using the Ratio of Induced Voltages)

  • 강용철;이병은;윤재성;옥승훈
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2000년도 추계학술대회 논문집 학회본부 A
    • /
    • pp.168-170
    • /
    • 2000
  • This paper presents a protective relaying algorithm for transformers using the ratio of induced voltages. The ratio primary and secondary induced voltages calculated calculates from currents and voltages of primary and secondary windings is used. In case of the steady state and magnetic inrush, it is equal to the turn ratio while it is different from the turn ratio in case of internal winding faults. The proposed algorithm operates satisfactorily even large residual flux.

  • PDF

응력 분포에 따른 압전 유니모프 작동기의 성능 평가 (Performance Evaluation for Piezoelectric Unimorph Actuator with Stress Distribution)

  • 이종원;강래형;한재흥;정상준;고한영
    • 한국소음진동공학회:학술대회논문집
    • /
    • 한국소음진동공학회 2008년도 춘계학술대회논문집
    • /
    • pp.127-131
    • /
    • 2008
  • This paper deals with the performance evaluation of piezoelectric unimorph actuator. In the unimorph design, the thickness ratio of substrate to piezoelectric material and the elastic modulus ratio of substrate to piezoelectric material are important parameters. There exists only one structural configuration that satisfies the optimal condition among them, and actuators using that configuration exhibit better actuating displacements. Another design parameter is the piezoelectric coefficient which can be improved due to the induced tensile stress and voltages. The application of the tensile stress to the piezoelectric material makes it get higher piezoelectric coefficient and the total displacement performance of the unimorph actuator is improved. Finally, the piezoelectric actuator system with spring elements is fabricated and it shows higher actuating displacement capability.

  • PDF

Inductive Micro Displacement Detecting System with High Sensitivity and Low Linearity Error

  • Park, Dong-June;Park, In-Mook;Kim, Soo-Hyun
    • International Journal of Precision Engineering and Manufacturing
    • /
    • 제2권3호
    • /
    • pp.54-60
    • /
    • 2001
  • A newly designed inductive micro displacement detecting system is presented. The proposed inductive system consists of driving coils, position-detecting coils, cores, and closed-loop formed magnetic blocks. The cores and magnetic blocks are made of Mn-Zn ferrite. When AC sine wave is applied to the driving coils, the time derivative flux is generated within the system, and then induced voltages arise in the position-detecting coils according to the core\`s position. Putting the cores to be moved proportionally to the input displacement, the induced voltage is proportional to input displacement. The parameters that affect the system characteristics are turn ratio, air-gap size, excitation frequency, overlap area, load resistance, capacitance effect, and so forth. Based on the experimental results, the system parameters are selected in such a way as to have high sensitivity ad stable responses. The sensitivity of the proposed inductive displacement-detecting system is greater than 2800mV.V-1mm-1 and the linearity error is below $\pm$0.10% in the range of $\pm$200㎛.

  • PDF

전자유도전압 차폐계수 산정을 위한 파라미터 보정 방법 (Compensation Method of Parameters to Evaluate a Sheilding Coefficient of Electromagnetic Induction Voltage)

  • 이상무;최문환;조평동
    • 한국정보통신학회:학술대회논문집
    • /
    • 한국정보통신학회 2013년도 춘계학술대회
    • /
    • pp.503-506
    • /
    • 2013
  • 전력선 전자유도 전압에 대한 어떤 시설물의 차폐계수를 산정하려면 그 시설물이 있는 장소에서의 유도전압과 없는 장소에서의 유도전압을 비교한다. 장소의 차이에 기인한 파리미터들을 동일한 환경에서의 것으로 정규화시켜 주어야 한다. 파라미터별로 정규화를 하는 요소별 보정 방식이 기본이지만 함수 관계의 미지성으로 어떠한 파라미터의 보정율 산정이 곤란하다면 유도전압 계산의 결과 값은 모든 파라미터의 영향이 이미 반영되어 있는 것이므로 계산된 유도전압의 기준값을 두고 보정하고자 하는 환경의 유도전압 계산값과의 비를 산정하면 전체 파라미터에 대한 보정이 내포적으로 이루어지는 통합보정 방식을 사용할 수 있다.

  • PDF

Arsenic의 첨가량에 따른 방사선 검출센서 (a-Se)의 전기적 특성 비교 (The Comparison of Electric Characteristics of Radiation Detective Sensor(a-Se) with changing composition ratio of Arsenic)

  • 석대우;강상식;이동길;김재형;남상희
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2002년도 추계학술대회 논문집 Vol.15
    • /
    • pp.391-394
    • /
    • 2002
  • There has recently been much interest and research in developing digital x-ray systems based on using amorphous selenium(a-Se) photoconductors as the image receptor. The amorphous selenium layer that is currently being studied for use as an x-ray photoconductor is not pure a-Se but rather amorphous selenium alloyed with arsenic. We fabricated samples using the selenium and arsenic alloy with various concentrations of the arsenic. In this work, x-ray photoconductor using amorphous selenium alloyed with arsenic were fabricated with different concentrations of the arsenic (0.1 wt.%, 0.3wt.%, 0.5wt.%, 1wt.%, 1.5wt.%, 3wt.%, 5wt.%). The seven kind of samples was fabricated with a-Se alloyed with arsenic through vacuum thermal evaporation. We also investigate the arsenic concentration dependence on the device performance in radiation detector. The electric characteristics of radiation detector devices with changing additive ratio of the arsenic is performed by measuring the x-ray induced photocurrent and integrating it over time to find the total charge. The thickness of a-Se is $100{\mu}m$. Bias voltages $3V/{\mu}m$, $6V/{\mu}m$$9V/{\mu}m$ are applied at the samples. As results, the net charge of a-Se 0.3% As sample is $526.0pC/mR/cm^2$ at $9V/{\mu}m$ bias. The net charge is decreased as with the increasing additive ratio of arsenic.

  • PDF