Compensation Method of Parameters to Evaluate a Sheilding Coefficient of Electromagnetic Induction Voltage

전자유도전압 차폐계수 산정을 위한 파라미터 보정 방법

  • Lee, Sangmu (Electronics and Telecommunications Research Institute) ;
  • Choi, Mun Hwan (Electronics and Telecommunications Research Institute) ;
  • Cho, Pyung-dong (Electronics and Telecommunications Research Institute)
  • Published : 2013.05.22

Abstract

The shielding coefficient of a conductive length structure is calculated by a ratio of induced voltage with that structure to without that structure. The environments are different between with a structure and without a structure. Beside the corresponding structure, all the parameters related to induced voltage should be normalized to a presumable same environment conditions. Basically each parameter must be compensated, which is a bottom-up type method. In this case, some parameter is not possible to be so because of its unknowing function. Then as a calculated voltage already has all characteristics of parameters, seeking a ratio of calculated induction voltages themselves will include the compensation of all parameters automatically. This is a top-down method.

전력선 전자유도 전압에 대한 어떤 시설물의 차폐계수를 산정하려면 그 시설물이 있는 장소에서의 유도전압과 없는 장소에서의 유도전압을 비교한다. 장소의 차이에 기인한 파리미터들을 동일한 환경에서의 것으로 정규화시켜 주어야 한다. 파라미터별로 정규화를 하는 요소별 보정 방식이 기본이지만 함수 관계의 미지성으로 어떠한 파라미터의 보정율 산정이 곤란하다면 유도전압 계산의 결과 값은 모든 파라미터의 영향이 이미 반영되어 있는 것이므로 계산된 유도전압의 기준값을 두고 보정하고자 하는 환경의 유도전압 계산값과의 비를 산정하면 전체 파라미터에 대한 보정이 내포적으로 이루어지는 통합보정 방식을 사용할 수 있다.

Keywords