• Title/Summary/Keyword: power cable insulation

Search Result 245, Processing Time 0.026 seconds

A Study on Reclosing Decision on 154kV Combined Transmission Lines (154kV 혼합송전선로 재폐로 결정에 관한 연구)

  • Jung, Chae-Kyun;Park, Hung-Sok;Kang, Ji-Won;Lee, Jong-Beom
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.59 no.10
    • /
    • pp.1761-1769
    • /
    • 2010
  • This paper describes switching surge analysis on reclosing decision in 154kV combined transmission line with power cables. Reclosing should be operated in combined transmission line based on the technical evaluation because of insulation problem of power cable section. If the surge strikes on power cable, the breakdown can occur at week point of cable insulation. Therefore the detailed analysis is required by considering several conditions such as length ratio of power cable, arrester, fault resistance, charging rate and grounding resistance, etc.. In addition, sheath voltage on IJ(Insulated Joint) is analyzed to confirm the protective level. Simulation is performed by EMTP/ATP. Analysis results show that reclosing can be operated without any special problem by the single line-to-ground fault with fault resistance of $1\Omega$ to $50\Omega$ occurred at the overhead transmission section in 154kV combined transmission lines and trap charge of 100% and 110%.

Sheath Circulating Current Analysis of a Crossbonded Power Cable Systems

  • Jung, Chae-Kyun;Lee, Jong-Beom;Kang, Ji-Won
    • Journal of Electrical Engineering and Technology
    • /
    • v.2 no.3
    • /
    • pp.320-328
    • /
    • 2007
  • The sheath in underground power cables serves as a layer to prevent moisture ingress into the insulation layer and provide a path for earth return current. Nowadays, owing to the maturity of manufacturing technologies, there are normally no problems for the quality of the sheath itself. However, after the cable is laid in the cable tunnel and is operating as part of the transmission network, due to network construction and some unexpected factors, some problems may be caused to the sheath. One of them is the high sheath circulating current. In a power cable system, the uniform configuration of the cables between sections is sometimes difficult to achieve because of the geometrical limitation. This will cause the increase of sheath circulating current, which results in the increase of sheath loss and the decrease of permissible current. This paper will study the various characteristics and effects of sheath circulating current, and then will prove why the sheath current rises on the underground power cable system. A newly designed device known as the Power Cable Current Analyser, as well as ATP simulation and calculation equation are used for this analysis.

Influence of Endurance tests on Space Charge Distribution of 160kV HVDC XLPE Cable

  • Liu, Yun-Peng;Liu, He-Chen
    • Journal of Electrical Engineering and Technology
    • /
    • v.12 no.1
    • /
    • pp.302-309
    • /
    • 2017
  • The ageing of XLPE cable insulation will lead to the accelerating accumulation of space charge, which will greatly affect the safe operation of the HVDC cable. In order to investigate the influence of different ageing modes on the space charge distribution of the HVDC cable, thermal stressed, electrical stressed and electro-thermal stressed endurance tests were carried out on the XLPE peelings. The tested XLPE peelings were obtained from 160kV HVDC cable insulation. The endurance tests were carried at thermal stress of 363K, electrical stress of 20kV/mm DC and a combination of both. The Pulsed Electro-Acoustic (PEA) method was used to measure the space charge distribution of the samples. The influences of ageing on the trap energy distribution were analyzed based on the isothermal relaxation theory and the decay characteristics of the space charge. The results showed that thermal ageing would help to improve the crystalline morphologies of the XLPE at the early stage. The total amount of space charge decreased compared to the ones before thermal ageing. The long term of electrical stress would result in the cleavage of polymer molecule chains which would intensify the accumulation of space charge and increase the density and depth of electron traps. With a combination of electrical and thermal stress, the injection and migration of space charge were more significant. Besides, the depth and density of electron traps increased rapidly with the increase of endurance time.

A INSULATING DESIGN OF $SF_6$ GAS SEALING END OF CONDENSER CONE TYPE USED FOR 345KV OF CABLE (콘덴서 콘 방식의 345KV OF 케이블용 $SF_6$ 가스중 종단접속함의 절연 설계)

  • Kim, H.J.;Lee, S.C.;Oh, O.J.;Lee, H.S.
    • Proceedings of the KIEE Conference
    • /
    • 1994.07b
    • /
    • pp.1553-1555
    • /
    • 1994
  • In this paper, we describes the research in condenser cone of $SF_6$ gas sealing end for 345KV oil-filled cable. The designed of condenser cone based on the results electric field analysis by electrostatics theory ana FEM. As a results. we have been designed the condenser cone and the inner insulation part of $SF_6$ seating end, the width and length, the number of condenser, the length of stress relief slope, the total length of condenser cone.

  • PDF

Insulation Diagnosis Study of Power XLPE Cable by Used Atenna (안테나를 이용한 전력용 케이블의 절연진단 연구)

  • Lee, H.C.;Choie, U.H.;Park, K.S.;Yoon, D.H.;Jee, S.W.;Lee, S.H.;Kim, C.N.;Lee, K.S.
    • Proceedings of the KIEE Conference
    • /
    • 2004.07c
    • /
    • pp.1805-1807
    • /
    • 2004
  • This simulated partial discharge caused by 22.9[kV] power cable using XLPE(Peroxide Crosslinkable Polyethylene) insulation having the outside damage. Asone of the insulation diagnostic method a radiated electromagnetic waves were measured by an UHF method using a BiconiLog antenna(EMCO-3142) and a spectrum analyzer used to measure EMl, EMC. From results of this study, It was confirmed that discharge progress were possible to be estimated by the proposed method.

  • PDF

Life Expectancy for Power Cable Insulation(XLPE) Using Statistical Method (통계적 기법을 이용한 전력 케이블 절연층(XLPE)의 수명 예측)

  • 이승엽;조대희;이인호;박완기
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 1999.05a
    • /
    • pp.57-61
    • /
    • 1999
  • Electrical stress makes insulating materials aged finally resulting in the dielectric failure. It becomes more and more important to recognize the degree of aging and the life time of the insulating materials since it is directly concerned with the reliability of the insulation system. In this paper, the life time of the Cross-linked Polyethylene(XLPE), the insulation layer in the 154kV-grade power cable, is expected and calculated using statistical and mathematical methods. The simulated results are compared with experimental ones and the life exponent of the material is obtained.

  • PDF

Effects of Hot Water on the Aging of URD Power Cables (지중 배편케이블의 열화에 미치는 온수의 영향)

  • 한재홍;송일근;김주용;이병성;정종욱
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.15 no.7
    • /
    • pp.609-614
    • /
    • 2002
  • In this study, we investigated the effects of hot water on the aging of URD power cables due to the hot water ingress to power distribution lines. Hot water contacted and non-contacted cables extracted from 2 distribution lines were characterized by the measurement of oxidation induction time(OIT) and chemical structure. In OIT measurement, hot water contacted cables showed the shorter OIT than non-contacted ones. Especially, hot water contacted insulation layer near insulation shield showed the shortest OIT. In chemical structure analysis, the antioxidant content was decreased and the acid concentration was increased by hot water ingress. From this results, it can be concluded that the hot water ingress to power cable may be accelerate the aging by means of antioxidant consumption.

Breakdown Voltage and Partial Discharge Characteristics at the Simulated Interface in a Prefabricated Joint for Ultra High Voltage Cable (초고압용 조립형 접속함 모의계면에서 압력에 따른 절연파괴 및 부분방전 특성)

  • Kim, J.N.;Baek, J.H.;Shin, D.S.;Lee, C.Y.;Kim, C.S.;Kim, D.W.;Park, W.K.
    • Proceedings of the KIEE Conference
    • /
    • 1999.11d
    • /
    • pp.1099-1101
    • /
    • 1999
  • PJB(Prefabricated Joint Box) is consisted of three major components ; an epoxy unit, a stress relief cone and a spring unit. The insulation structure of PJB is maintained by the interfacial pressure, and the dielectric performance at the interface depends on the interfacial pressure which is regarded as the most important factor for preventing breakdown failure. This experiment was performed to investigate breakdown voltage characteristic and partial discharge patterns under the controlled pressure conditions at the simulated interface. Finally, this paper presents the optimal pressure conditions at the interface by analyasing the PD patterns.

  • PDF

Electric Field Analysis of Power Cable Joint Point using Boundary Element Method (경계요소법을 이용한 전력케이블 접속부의 전계해석)

  • 조경순
    • Journal of the Korea Computer Industry Society
    • /
    • v.4 no.4
    • /
    • pp.579-588
    • /
    • 2003
  • There are many unfavorable conditions that lead to shortening life of cable by causing dielectric breakdown and aging such as field concentrations occurring in intermediate materials linking each cables, penetration of various impurities, and undermining of cable insulation layers. This paper simulated investigated partial discharge properties of XLPE which is widely used for ultra high voltage cable insulation materials and EPDM which is being used as insulation layer of cable joint materials kit, using Boundary Element Method. The result of computer simulation showed that inner-Void defect caused silicone oil to weaken the E-field effect. and we also found that E-field distribution in EPDM remained relatively lower than that in XLPE.

  • PDF

Analysis and Model Establishment of OF Cable Underneath a Bridge on Underground Power Cable Systems (지중송전계통에서 OF케이블의 교량 첨가시 모델 수립 및 해석)

  • Lee, Hyun-Suk;Lee, Jong-Beom
    • Proceedings of the KIEE Conference
    • /
    • 2008.07a
    • /
    • pp.2245-2246
    • /
    • 2008
  • This paper analyses crossbonded cable system underneath a bridge. The simulation is performed under various system configuration such as cable length, iron frame size, lightning surge. The simulation models are established by EMTP/ATPDRraw. In this paper, the crossboneded cable system underneath a bridge is also analyzed for insulation coordination of iron frame and cables.

  • PDF