• 제목/요약/키워드: polymeric insulator

검색결과 61건 처리시간 0.036초

EPDM 및 실리콘 재질의 폴리머현수애자의 특성 비교 (The Comparison of EPDM and Silicone in Housing Materials of Polymeric Suspension Insulators)

  • 이병성;이재봉;송일근;한상옥
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2003년도 춘계학술대회 논문집 유기절연재료 방전 플라즈마연구회
    • /
    • pp.6-10
    • /
    • 2003
  • In our country, the housing materials of polymeric outdoor insulators have mainly been used EPDM or silicone rubber. EPDM housing materials had been widely used in the field for the first time. The reason why silicone has the high cost of production. But recently, most of the manufacturers that newly developed polymeric insulators make its choice of silicone housing. EPDM showed a good resistance to tracking. We compared the various characteristics for EPDM and silicone insulators that have similar type and design. Silicone insulators have more performance in flashover voltage test and leakage current measurement because of a good water repellent than EPDM ones. Also, the property of EPDM compared with silicone insulators greatly decreased after aging test in combined acceleration ageing facilities for 1000 hours.

  • PDF

옥외에서 사용되는 배전급 폴리머 현수애자의 오손특성에 관한 연구

  • 이병성;한상옥
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제50권7호
    • /
    • pp.340-345
    • /
    • 2001
  • Because they have superior insulating properties and lower in price than their ceramic equivalents, polymeric insulators have been used in outdoor insulators. But polymeric insulators mainly using in an heavy contamination area of outdoor could be easily attached to contaminants such as salt and by-products of industrial processes. To understand its effect on contaminants adhered to these insulators, we dismounted polymeric insulators adhered contaminant in the field, and evaluated its electrical characteristics, CA, and ESDD. We also manufactured slurry mixed by some kaolin and salt for the artificial contamination test and measured the degree of contaminant, AC leakage current for these contaminated samples. Consequently, the adhered contaminants to its surface is likely to be affected the performance of insulation.

  • PDF

실 포설 환경에 노출된 송전용 고분자애자의 평가 (Analysis of Polymeric Insulators Exposed to In-service Conditions)

  • 이상진;연복희;배경무;전승익
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 추계학술대회 논문집 전기물성,응용부문
    • /
    • pp.248-250
    • /
    • 2004
  • We have investigated the surface state of 154kV polymeric insulators exposed to in-service conditions for about five years. In order to evaluate surface aging of silicone rubber exposed to real field environments, we used various analytic methods such as contact angle, ATR-FTIR, SEM-EDS. Although contaminants were accumulated on weathershed surface, polymeric insulator has retained its intrinsic surface hydrophocity. In addition, ATR-FTIR confirmed the diffusion layer of a low molecular weight silicone fluid on surface layer and no surface cracking and chalking were Indicated by SEM. Polymeric insulators have still retained their improved pollution performance over porcelain insulators. That will lead to very low frequency of flashovers throughout their useful life, often under contaminated conditions.

  • PDF

폴리머 현수애자의 신뢰성 평가 및 복합가속열화 방법 (Reliability Evaluation Criteria and Multi-Stress Aging Test for Polymer Insulator)

  • 박효열;강동필;안명상
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2004년도 하계학술대회 논문집 Vol.5 No.1
    • /
    • pp.469-472
    • /
    • 2004
  • There have been numerous accelerated aging laboratory tests for evaluating suitability of polymeric materials and devices. Aging test for materials and its full scale device has been conducted, but poor correlation of aging test such as service experience were observed. Service experience plays a key role in the utility section of composite insulators. A meaningful and reliable accelerated aging test is needed for evaluating composite insulator. During the service these insulators are subjected to aging stress such as humidity, pollution, and electrical field, and erosion and tracking of the weathershed occurs. This paper presents the criteria of reliability evaluation and evaluation facilities for 22.9 kV suspension composite insulator. We adopt the criteria of reliability evaluation consist of two test methods. One is CEA tracking wheel test for examining the tracking and erosion performance of composite insulator. The other is multi-stress aging test for examining effects of environmental factors such as UV, temperature, humidity, etc on composite insulator.

  • PDF

Investigation on Flashover Development Mechanism of Polymeric Insulators by Time Frequency Analysis

  • Muniraj, C.;Krishnamoorthi, K.;Chandrasekar, S.
    • Journal of Electrical Engineering and Technology
    • /
    • 제8권6호
    • /
    • pp.1503-1511
    • /
    • 2013
  • This paper deals with the analysis of leakage current characteristics of silicone rubber insulator in order to develop a new condition monitoring tool to identify the flashover of outdoor insulators. In this work, laboratory based pollution performance tests are carried out on silicone rubber insulator under ac voltage at different pollution levels and relative humidity conditions with sodium chloride (NaCl) as a contaminant. Min-Norm spectral analysis is adopted to calculate the higher order harmonics and Signal Noise Ratio (SNR). Choi-Williams Distribution (CWD) function is employed to understand the time frequency characteristics of the leakage current signal. Reported results on silicone rubber insulators show that the flashover development process of outdoor polymer insulators could be identified from the higher order harmonics and signal noise ratio values of leakage current signals.

전력케이블용 전기절연재료의 열적, 전기적 파괴현상 (Thermal and Electrical Breakdown Phenomena in Electrical Insulator of Power Cable)

  • 조영신;심미자;김상욱
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1997년도 추계학술대회 논문집 학회본부
    • /
    • pp.187-189
    • /
    • 1997
  • Thermal and electrical breakdown phenomena in XLPE insulator of power cable were investigated. At high temperature the polymeric insulator was thermally deteriorated. Under the magnified high electric field, electrical tree was initiated at the sharp tip of needle electrode which was inserted to simulate the defects and impurities such as void, crack, metallic particles, dusts, and so on.

  • PDF

코로나 대전을 통한 옥외용 고분자 절연재료의 자외선 열화특성 연구 (Study on UV degradation in Polymeric Insulating Materials for Use in Outdoor Insulators by Corona-Charging)

  • 연복희;안종식;이상용;허창수
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2001년도 춘계학술대회 논문집 유기절연재료 전자세라믹 방전플라즈마 연구회
    • /
    • pp.106-109
    • /
    • 2001
  • In this paper, we have investigated the degradation of shed materials of outdoor insulators by UV-radiation by using corona-charging and XPS analysis. The accumulated charges on polymeric surface having intrinsic hydrophobic property have a negative impact on retaining its hydrophobicity. Therefore, shorter decay times of surface charges are preferred. The surface voltage decay on UV-treated silicone rubber and EPDM show a different decay trend with UV treated time. From the XPS analysis, the oxidized groups of silica-like structure in silicone rubber increase with UV treatment time. For EPDM, the oxidized carbon groups of C=O, O=C-O increase as elapse of UV radiation time. These oxidized surface for each material have different electrostatic characteristics, so deposited charges may be expected to have different impacts on their surface hydrophobicity. The degradation mechanism based on our results is discussed.

  • PDF

고분자 절연재료에서 전기트리 열화 및 절연파괴 현상 (Electrical Treeing Deterioration and Dielectric Breakdown Phenomena in Polymeric Insulator)

  • 조영신;김상욱
    • 한국재료학회지
    • /
    • 제9권4호
    • /
    • pp.398-403
    • /
    • 1999
  • 폴리에틸렌과 에폭시 수지계 고분자 정연재료에서 발생하는 전기트리 열화 및 절연파괴 현상에 대해 연구하였다. 침-평판 전극구조를 갖는 블럭상 시편에 전기적 응력을 가하고 침 선단에서 발생하는 전기트리를 관찰하였다. 저밀도 폴리에틸렌에서 발생하는 전기트리 형상은 밀도가 매우 높은 부시상이었으며, 가교 풀려에틸렌에서는 가지형 전기트리가 관찰되었다. 에폭시 수지 에서는 첨가제 SN의 함량과 온도가 증가함에 따라 절연파괴 강도는 감소하였으며 전기트리는 더욱 복잡해졌다. 가교밀도가 높아 딱딱한 DGEBA/MDA 에폭시 수지계에서는 전도성 트리 경로 주위에 일련의 부채꼴 크랙이 관찰되었다.

  • PDF

옥외용 실리콘 절연재료의 발수성에 미치는 표면전하의 영향과 표면 상태에 따른 표면전위 감쇠 (Effects of Surface Charges on Hydrophobicity and Surface Potential Decay with Various Surface States of Silicone Rubber for Outdoor Insulator)

  • 연복희;박충렬;허창수
    • 한국전기전자재료학회논문지
    • /
    • 제15권8호
    • /
    • pp.678-686
    • /
    • 2002
  • This paper presents the effects of accumulation of surface charges on hydrophobic level and the changes of surface potential decay with various artificial environment treatments on high temperature vulcanized (HTV) silicone rubber used for outdoor insulating material. For this study, the charging apparatus by corona discharge, in which grid electrode was installed between the main corona and ground electrode, was used. From this study, it was found that the accumulation of surface charges above a critical surface potential on silicone insulating materials could lead to the temporary loss of surface hydrophobicity. In addition, corona stress and water absorption stress increase the decay rate of surface charges of HTV silicone rubber, while ultraviolet (UV) stress causes longer decay time. We could conclude that the effects of surface charges on hydrophobicity level and the changes of surface state by various artificial treatments were found through a trend of surface potential decay.