A Study on PD Detection Methods for Cast-resin Dry-type Transformers (몰드변압기의 부분방전 검출기술에 관한 연구)

  • Park, Chan-Yong;Park, Dae-Won;Choi, Jae-Sung;Kil, Gyung-Suk
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.22 no.9
    • /
    • pp.786-791
    • /
    • 2009
  • Transformer failures are mostly due to partial discharges (PDs) caused by the deteriorated insulation. It is, therefore, important to monitor PD occurrence in insulation system and prevent their deterioration. The presented paper deals with a PD detection method by a capacitive probe, which easily apply to cast - resin dry - type transformers. The PD detection system consists of a capacitive probe and a low noise amplifier having the frequency bandwidth of 500 $Hz{\sim}30$ MHz. In the experimental set-up, sensitivity of the system is 7.16 mV/pC.

Analysis of Partial Discharge in High Voltage Motor Model Coils (고압전동기 모델 코일의 부분방전 분석)

  • Kim, Hee-Dong;Kong, Tae-Sik
    • Proceedings of the KIEE Conference
    • /
    • 2005.07c
    • /
    • pp.2091-2093
    • /
    • 2005
  • Five model coils of 6.6kV motor were manufactured with several defects. These stator coils have artificial defects such as void of groundwall insulation, removal of semi-conductive coating and damage of strand insulation. Epoxy-mica coupler(80 pF) was connected to five model coil terminals, respectively The voltage applied to the coils was 3.81kV, 4.76kV, 6.0kV and 6.6kV. Partial discharge(PD) tests performed in the laboratory and shield room. Digital PD detector (PDD) and turbine generator analyzer(TGA) were used to measure PD activity. TGA summarizes each plot with two quantities such as the normalized quantity number(NQN) and the peak PD magnitude(Qm). The PD levels in pC were measured with PDD. PD patterns of model coils were indicated the internal and slot discharges. PD patterns coincide with both PDD and TGA.

  • PDF

Fundamental Study of Degradation Diagnosis using AE Signals with Void Discharge in XLPE Insulation (XLPE 절연체의 트리 채널내 보이드방전에 의한 AE신호로 절연열화 검출 기법 연구)

  • Lee, Sang-Woo
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.20 no.2
    • /
    • pp.75-80
    • /
    • 2006
  • In this paper, to detect and observation the void discharges pulse signal, AE signals and tree growth characteristics in case the high voltage is applied to a XLPE sample for a power cable. We also examined the partial discharge current pulse and AE signals with the increase of the applied voltage in XLPE insulation. The experimental results show that a branch-type tree grows in the presence of the voids, and a bush-type tree grows in the absence of the voids in both samples. A rate of tree growth increases abruptly in proportional to the deterioration time in the presence of the of the voids, but in the absence of the voids, a rate of tree growth decreases as time goes by and finally a breakdown occurs. The frequency band of AE signals that are generated from the partial discharges in a XLPE sample, one of solid dielectric materials, is about 1.0[MHz].

Prebreakdown Corona Discharge of Point-to-Plane Gap in $SF_6$ Gas ($SF_6$ 가스중에서 침대평판간극(針對平板間隙)의 전구(前驅)코로나 방전(放電))

  • Paek, Yong-Hyun;Lee, Bok-Hee;Jeon, Duk-Kyu
    • Proceedings of the KIEE Conference
    • /
    • 1992.07b
    • /
    • pp.980-982
    • /
    • 1992
  • This paper deals with the dielectric behaviors of $SF_6$ gas and prebreakdown growth caused by lightning impulse voltages In inhomogeneous field perturbed with a fixed needle-shaped protrusion on the electrode. The measuring interpretation of the external current induced by moving charges is described. The temporal growth of prebreakdown is observed by using a shunt and photomultiplier. The prebreakdown processes are initiated by the first streamer corona at a needle protrusion, the flashover of the main gap in the positive polarity is very sensitive to the local field and propagates into the gap with the leader mechanism. It Is found that the dependence of the prebreakdown phenomena on the polarity of applied voltages is caused by the effect of space charges. In addition, the proposed measuring techniques are very useful to perform the measurements of avalanche currents, corona discharges in inhomogeneous fields and partial discharges in voids.

  • PDF

Properties of PD Pulses accompanying with propagation of Bush-type tree in LDPE (LDPE에서 부시형 전기트리의 성장에 수반되는 부분방전 펄스의 특성)

  • 박영국;강성화;정수현;박철현;임기조
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 1998.06a
    • /
    • pp.293-296
    • /
    • 1998
  • Surface electrical conduction in insulator is most important factor to assess the insulation performances of outdoor insulating materials. In this paper, contamination performance of the widely used materials for outdoor insulator - porcelain, EPDM, Silicone rubber - were discussed by measuring properties of average leakage current and scintillation discharge pulses under artificial contamination conditions. The artificial contaminations used were deionized distilled water fog, 0.5wt% NaCl salt fog of light pollution and 2wt% NaCl salt fog of medium pollution. The average leakage current was appeared linearly with applied voltage at dry and clean surface condition. The magnitude of leakage current was almost same at different kinds of samples. In case of deionized distilled water fog, the characteristics of leakage current and applied voltage was most different to that in case of dry and clean condition. In case of salt fog pollution condition, The leakage current was increased above critical voltage. The scintillation discharges were also activated at the level. the leakage current and scintillation discharges were increased with increasing pollution degree. The resistance to pollution properties of silicone rubber appeared excellent among them.

  • PDF

Hydrophobicity and tracking resistance of SIR for outdoor Insulators (초고압 옥외용 실리콘 고무의 발수성 및 트래킹 특성)

  • Han, D.H.;Kang, D.P.;Park, H.Y.;Lee, K.H.;Lee, K.C.;Min, K.E.
    • Proceedings of the KIEE Conference
    • /
    • 2000.07c
    • /
    • pp.1560-1562
    • /
    • 2000
  • The paper reports on a study of the influence of the silicone oils on the tracking and erosion resistance and hydrophobicity of SIR. Two silicone oils(A, B) having different chemical structure were selected in consideration of goof hydrophobicity and processability. Tracking and erosion resistance of SIR was investigated by the rotating wheel dip test (RWDT). In this test tracking and erosion areas due to glow and partial arc discharges cause an increase in the leakage current with an increase in time. Leakage current of SIR was decreased with increasing ratio of oil A/B. SIR was exposed to corona discharges in air and the specimens were analyzed with contact angle. It was observed that the contact angle of SIR was increased gradually in time. The recovery of hydrophobicity was increased with increasing ratio of oil A/B.

  • PDF

Optimal Design of an Antenna for the Detection of Partial Discharges in Insulation Oil (절연유중 부분방전 검출을 위한 안테나의 최적 설계)

  • Lee, Jung-Yoon;Jo, Hyang-Eun;Park, Dae-Won;Kil, Gyung-Suk;Oh, Jae-Geun
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.26 no.4
    • /
    • pp.309-314
    • /
    • 2013
  • This paper dealt with the radiated electromagnetic wave detection of partial discharge (PD) in oil for insulation diagnostics of oil-immersed transformers. Three types of electrode system were fabricated to simulate the insulation defects that could occur in oil-immersed transformers. Frequency components of radiated electromagnetic wave in oil was measured by broadband bi-conical antennas of 300 MHz~2 GHz and a spectrum analyzer of 9 kHz~3 GHz. Frequency component of electromagnetic waves from PD in oil were highly distributed at 500 MHz. From the result, a narrow-band monopole antenna with the center frequency of 500 MHz was fabricated. We could detect PD signal in insulation oil without an influence of external noise by a measurement system which consists of the prototype monopole antenna, a LNA (Low Noise Amplifier), an oscilloscope and a spectrum analyzer.

Cavity and Interface effect of PI-Film on Charge Accumulation and PD Activity under Bipolar Pulse Voltage

  • Akram, Shakeel;Wu, Guangning;Gao, GuoQiang;Liu, Yang
    • Journal of Electrical Engineering and Technology
    • /
    • v.10 no.5
    • /
    • pp.2089-2098
    • /
    • 2015
  • With the continuous development in insulation of electrical equipment design, the reliability of the system has been enhanced. However, in the manufacturing process and during operation under continues stresses introduce local defects, such as voids between interfaces that can responsible to occurrence of partial discharge (PD), electric field distortion and accumulation of charges. These defects may lead to localize corrosion and material degradation of insulation system, and a serious threat to the equipment. A model of three layers of PI film with air gap is presented to understand the influence of interface and voids on exploitation conditions such as strong electrical field, PD activity and charge movement. The analytical analysis, and experimental results are good agreement and show that the lose contact between interfaces accumulate more residual charges and in consequences increase the electric field intensity and accelerates internal discharges. These residual charges are trapped charges, injected by the electrodes has often same polarity, so the electric field in cavities increases significantly and thus partial discharge inception voltage (PDIV) decreases. Contrary, number of PD discharge quantity increases due to interface. Interfacial polarization effect has opposite impact on electric field and PDIV as compare to void.

Detection of Partial Discharges by a Monopole Antenna in Insulation Oil (모노폴 안테나를 이용한 유중 부분방전의 검출)

  • Park, Dae-Won;Lee, Jung-Yoon;Kil, Gyung-Suk
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.25 no.9
    • /
    • pp.727-731
    • /
    • 2012
  • This paper dealt with the measurement and analysis of electromagnetic waves radiated from a partial discharge (PD) source in insulation oil to apply condition monitoring of oil-immersed transformers. Two types of narrow-band monopole antennas with the resonant frequency of a 500 MHz and a 1 GHz were designed and fabricated. Also, a needle-plane electrode system was manufactured to simulate PDs and the curvature radius of the needle is 10 ${\mu}m$ and the diameter of the plane is 60 mm. Electromagnetic wave was measured by the PD measurement system with the monopole antennas. Detection sensitivity of the fabricated antenna was compared for the same PD magnitude; 620 $mV_{peak}$ for the 500 MHz antenna and 960 $mV_{peak}$ for the 1 GHz antenna to the PD magnitude of 74 pC. Consequently, the 1 GHz monopole antenna is more effective to detect PDs in oil-immersed transformers.

Analysis of Partial Discharge in High Voltage Motor Model Coils (고압전동기 모델 코일에서 부분방전 분석)

  • Kim, Hee-Dong
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.55 no.4
    • /
    • pp.178-182
    • /
    • 2006
  • Five model coils of 6.6 kV motor were manufactured with several defects. These stator coils have artificial defects such as void of groundwall insulation, removal of semi-conductive coating and damage of strand insulation. Epoxy-mica coupler(80 pF) was connected to five model coil terminals. The voltage applied to the coils was 3.81 kV, 4.76 kV, 6.0 kV and 6.6 kV, respectively. Partial discharge(PD) tests performed in the laboratory and shield room. Digital PD detector(PDD) and turbine generator analyzer(TGA) were used to measure PD activity. TGA summarizes each plot with two quantities such as the normalized quantity number(NQN) and the peak PD magnitude(Qm). The PD levels in pC were measured with PDD. PD patterns of model coils were indicated the internal and slot discharges. PD patterns are consistent with the result of measurement using PDD and TGA instruments. AC breakdown test was performed on five model coils in order to confirm the result of PD measurements. All the failures were located in a line-end coil at the exit from the core slot.