• 제목/요약/키워드: once-through boiler

검색결과 39건 처리시간 0.033초

관류형 보일러의 온도제어 (Temperature control for once through boiler)

  • 김은기
    • 제어로봇시스템학회:학술대회논문집
    • /
    • 제어로봇시스템학회 1991년도 한국자동제어학술회의논문집(국내학술편); KOEX, Seoul; 22-24 Oct. 1991
    • /
    • pp.900-904
    • /
    • 1991
  • It is important and difficult to control the steam temperature in the once through boiler. Generally, steam temperature of once through boiler not only is controlled by boiler spray water flow, but also is influenced by feed water flow and fuel flow. So we have to make the same gain of fuel flow controller and feed water flow controller. This paper is shown the design and test of steam temperature and feed water flow control system for once through boiler in pusan thermal power plant.

  • PDF

화력발전소 관류보일러의 과열기 온도제어에 관한 연구 (A Study of Superheater Temperature Control on an Once Through Boiler in Thermal Power Plant)

  • 이주현;정태원
    • 전기학회논문지
    • /
    • 제58권10호
    • /
    • pp.2022-2027
    • /
    • 2009
  • An supercritical once through boiler system has been used in the korea standard-type thermal power plant. It is critical in boiler operation that superheater temperature should be controlled within the specified limit. In this paper, control logic scheme is suggested for superheater temperature in once through boiler. Finally the simulation result using process model based simulator shows the validity of suggested control logic.

관류형 아임계압 배열회수보일러의 열성능 모델링과 검증 (Modelling and Verification of Once-Through Subcritical Heat Recovery Steam Generator)

  • 이채수;최영준;김현기;양옥철;정재헌
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2004년도 추계학술대회
    • /
    • pp.1692-1697
    • /
    • 2004
  • The once-through heat recovery steam generator is ideally matched to very high temperature and pressure, well into the supercritical range. Moreover this type of boiler is structurally simpler than drum type boiler. In drum type boiler, each tube play a well-defined role: water preheating, vaporization, superheating. Empirical equations are available to predict the average heat transfer coefficient for each regime. For once-through heat recovery steam generator, this is no more the case and mathematical models have to be adapted to account for the disappearance of drum type economizer, boiler, superheater. General equations have to be used for each tube of boiler, and actual heat transfer condition in each tube has to be identified.

  • PDF

초임계압 관류형 보일러의 비선형모델에 관한 연구 (A Nonlinear Dynamic Model of a Once-Through Supercritical Boiler)

  • 윤석환;이승철
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1997년도 추계학술대회 논문집 학회본부
    • /
    • pp.238-241
    • /
    • 1997
  • The recent trend toward increased use of the once-through supercritical boiler worldwide is mainly due to its rapid response. The transient behavior of the steam generator are essential in the study of the system performance of power plants as well as for the design of their appropriate control systems. In this paper, a mathmatical model of the once-through supercritical pressure boiler is obtained by simulating a set of nonlinear differential and algebraic equations.

  • PDF

Temperature Control of Ultrasupercritical Once-through Boiler-turbine System Using Multi-input Multi-output Dynamic Matrix Control

  • Moon, Un-Chul;Kim, Woo-Hun
    • Journal of Electrical Engineering and Technology
    • /
    • 제6권3호
    • /
    • pp.423-430
    • /
    • 2011
  • Multi-input multi-output (MIMO) dynamic matrix control (DMC) technique is applied to control steam temperatures in a large-scale ultrasupercritical once-through boiler-turbine system. Specifically, four output variables (i.e., outlet temperatures of platen superheater, finish superheater, primary reheater, and finish reheater) are controlled using four input variables (i.e., two spray valves, bypass valve, and damper). The step-response matrix for the MIMO DMC is constructed using the four input and the four output variables. Online optimization is performed for the MIMO DMC using the model predictive control technique. The MIMO DMC controller is implemented in a full-scope power plant simulator with satisfactory performance.

한국표준형 초 임계압 관류형 보일러의 급수제어 (Feed Water Flow Control of Super Critical Once Through Boiler in Korea Standard Power Plant)

  • 김은기;장용창;조수현
    • 제어로봇시스템학회:학술대회논문집
    • /
    • 제어로봇시스템학회 2000년도 제15차 학술회의논문집
    • /
    • pp.251-251
    • /
    • 2000
  • Tangjin Power Plant is modern Korean standard plant which is made up Once Through Super Critical Boiler, Turbin, Generator and Flue Gas Desulfarization System. INFI-90 system fur control of the 500 MW Korean standard super critical once through boiler Mark-V for Turbine, EX-2000 fer Generator, WDPF for FGD were installed in Tangiin thermal power plant. There were two BFPTs, BFPM, 25% control valve, 35% control valve to control boiler feed water flow. It is very difficult to tune the Separator Tank level control system and change the mode from Wet to Dry. This paper focuses on test results and modification control logic for feed water control system in Tangjin power plant.

  • PDF

500MW급 초임계압 관류형 보일러 온도제어에 대한 기술 (Temperature Control Technology for Once Through Boiler)

  • 이광훈;이주현
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1998년도 하계학술대회 논문집 B
    • /
    • pp.719-721
    • /
    • 1998
  • In this paper, we reviewed the steam temperature control in an once through boiler. The steam temperature control is very difficult. Generally, steam temperature of an once through boiler is not only controlled by boiler spray water flow, but also influenced by feed water flow and fuel flow. An advanced control strategy has been developed by experienced engineer. Specifically, We reviewed temperature control strategy for Taian power plant in this paper. This control strategy is represented by state control observer. This state control observer algorithm for temperature control has been used since the late 1980's. This paper describes control strategy employed and observed benefits from advanced steam temperature control.

  • PDF

Compensation Logics of Controller in Korean Standard Super Critical Once Through Boiler

  • Kim, Eun-Gee
    • 제어로봇시스템학회:학술대회논문집
    • /
    • 제어로봇시스템학회 2001년도 ICCAS
    • /
    • pp.65.2-65
    • /
    • 2001
  • There are not only lots of controllers such as UMC(Unit Master Controller), BMC(Boiler Master Controller), Fuel Flow controller, Air flow controller, Feed water flow controller, S/H R/H Temperature controller and so on, but also compensation controller such as BTU compensator, Fuel/Water ratio controller and O2 Co controller to take automatic control in the super critical once through boiler. It is important to make complete automation of boiler to use the compensation controller like BTU compensator. For example, In case of some boiler condition, operator has to change combustion parameter for changing the coal, on the contrary BTU compensator can calculate set value of the fuel flow and reset the fuel flow demand by itself. This paper shows us the logic and instruction regarding compensation controller of boiler that can be operated automatically.

  • PDF

스프레이와 댐퍼를 이용한 관류 보일러 스팀 온도의 (2X2) 동역학 행렬 제어에 관한 연구 (A Study on Dynamic Matrix Control using Spray and Damper to Once-through Boiler Steam Temperature)

  • 김우헌;문운철
    • 조명전기설비학회논문지
    • /
    • 제24권1호
    • /
    • pp.91-97
    • /
    • 2010
  • 동역학 행렬 제어(Dynamic Matrix Control) 기법은 각종 산업 현장에서 가장 활발하게 적용되고 있는 고급 제어 기법으로, 최근에는 공정제어의 표준 기법으로 인식되고 있다. 일반적으로 동역학 행렬 제어에서는 대상 플랜트의 거동을 묘사하기 위하여 계단 응답 모델을 이용한다. 본 논문에서는 화력발전의 관류 보일러-터빈 시스템에 동역학 행렬 제어 기법을 적용한 결과를 제시한다. 먼저 제어를 위해 두 개의 입력변수로 스프레이와 댐퍼를 선정한 후, 두 개의 주요 출력 변수에 대한 계단 응답 모델을 생성하였다. 그 후, 생성된 2 입력 - 2 출력 계단 응답 모델을 바탕으로 한, 동역학 행렬 제어의 최적화 계산을 통해 매 순간 보일러 스팀 온도를 제어하는 구조의 제어기를 설계하였다. 제시된 제어기를 두산(주)의 보일러 시뮬레이션 모델인 APESS에 적용한 결과 만족할 만한 제어 성능을 나타냄을 확인하였다.

The Simulation of Boiler System for HADONG Fossil Power Plant

  • Choi, Jin-Ho;Ma, Sam-Sun;Lee,Yong-Kwan
    • 한국시뮬레이션학회:학술대회논문집
    • /
    • 한국시뮬레이션학회 1999년도 추계학술대회 논문집
    • /
    • pp.56-61
    • /
    • 1999
  • The Simulation of Boiler System for Hadong Fossil power plant has been made by Korea Electric Power Research Institute (KERRI) in an attempt to develop Windown NT based full scope replica simulator for Hadong Fossil power plant, 500MWe once-through boiler. In the project KERRI developed Once Through, Super Critical type Boiler System, the core part of the Simulation and integrated the system with other process systems such as BOP System, and AUX System. This paper is to introduce the basic concept of the simulation for the Boiler System. It will also introduce PRO-TRAX System, for used as a modeling tool.

  • PDF