• Title/Summary/Keyword: once-through boiler

Search Result 39, Processing Time 0.03 seconds

Temperature control for once through boiler (관류형 보일러의 온도제어)

  • 김은기
    • 제어로봇시스템학회:학술대회논문집
    • /
    • 1991.10a
    • /
    • pp.900-904
    • /
    • 1991
  • It is important and difficult to control the steam temperature in the once through boiler. Generally, steam temperature of once through boiler not only is controlled by boiler spray water flow, but also is influenced by feed water flow and fuel flow. So we have to make the same gain of fuel flow controller and feed water flow controller. This paper is shown the design and test of steam temperature and feed water flow control system for once through boiler in pusan thermal power plant.

  • PDF

A Study of Superheater Temperature Control on an Once Through Boiler in Thermal Power Plant (화력발전소 관류보일러의 과열기 온도제어에 관한 연구)

  • Lee, Jo-Hyun;Jeong, Tae-Won
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.58 no.10
    • /
    • pp.2022-2027
    • /
    • 2009
  • An supercritical once through boiler system has been used in the korea standard-type thermal power plant. It is critical in boiler operation that superheater temperature should be controlled within the specified limit. In this paper, control logic scheme is suggested for superheater temperature in once through boiler. Finally the simulation result using process model based simulator shows the validity of suggested control logic.

Modelling and Verification of Once-Through Subcritical Heat Recovery Steam Generator (관류형 아임계압 배열회수보일러의 열성능 모델링과 검증)

  • Lee, Chae-Soo;Choi, Young-Jun;Kim, Hyun-Gee;Yang, Ok-Chul;Chong, Chae-Hon
    • Proceedings of the KSME Conference
    • /
    • 2004.11a
    • /
    • pp.1692-1697
    • /
    • 2004
  • The once-through heat recovery steam generator is ideally matched to very high temperature and pressure, well into the supercritical range. Moreover this type of boiler is structurally simpler than drum type boiler. In drum type boiler, each tube play a well-defined role: water preheating, vaporization, superheating. Empirical equations are available to predict the average heat transfer coefficient for each regime. For once-through heat recovery steam generator, this is no more the case and mathematical models have to be adapted to account for the disappearance of drum type economizer, boiler, superheater. General equations have to be used for each tube of boiler, and actual heat transfer condition in each tube has to be identified.

  • PDF

A Nonlinear Dynamic Model of a Once-Through Supercritical Boiler (초임계압 관류형 보일러의 비선형모델에 관한 연구)

  • Yoon, S.H.;Lee, S.C.
    • Proceedings of the KIEE Conference
    • /
    • 1997.11a
    • /
    • pp.238-241
    • /
    • 1997
  • The recent trend toward increased use of the once-through supercritical boiler worldwide is mainly due to its rapid response. The transient behavior of the steam generator are essential in the study of the system performance of power plants as well as for the design of their appropriate control systems. In this paper, a mathmatical model of the once-through supercritical pressure boiler is obtained by simulating a set of nonlinear differential and algebraic equations.

  • PDF

Temperature Control of Ultrasupercritical Once-through Boiler-turbine System Using Multi-input Multi-output Dynamic Matrix Control

  • Moon, Un-Chul;Kim, Woo-Hun
    • Journal of Electrical Engineering and Technology
    • /
    • v.6 no.3
    • /
    • pp.423-430
    • /
    • 2011
  • Multi-input multi-output (MIMO) dynamic matrix control (DMC) technique is applied to control steam temperatures in a large-scale ultrasupercritical once-through boiler-turbine system. Specifically, four output variables (i.e., outlet temperatures of platen superheater, finish superheater, primary reheater, and finish reheater) are controlled using four input variables (i.e., two spray valves, bypass valve, and damper). The step-response matrix for the MIMO DMC is constructed using the four input and the four output variables. Online optimization is performed for the MIMO DMC using the model predictive control technique. The MIMO DMC controller is implemented in a full-scope power plant simulator with satisfactory performance.

Feed Water Flow Control of Super Critical Once Through Boiler in Korea Standard Power Plant (한국표준형 초 임계압 관류형 보일러의 급수제어)

  • 김은기;장용창;조수현
    • 제어로봇시스템학회:학술대회논문집
    • /
    • 2000.10a
    • /
    • pp.251-251
    • /
    • 2000
  • Tangjin Power Plant is modern Korean standard plant which is made up Once Through Super Critical Boiler, Turbin, Generator and Flue Gas Desulfarization System. INFI-90 system fur control of the 500 MW Korean standard super critical once through boiler Mark-V for Turbine, EX-2000 fer Generator, WDPF for FGD were installed in Tangiin thermal power plant. There were two BFPTs, BFPM, 25% control valve, 35% control valve to control boiler feed water flow. It is very difficult to tune the Separator Tank level control system and change the mode from Wet to Dry. This paper focuses on test results and modification control logic for feed water control system in Tangjin power plant.

  • PDF

Temperature Control Technology for Once Through Boiler (500MW급 초임계압 관류형 보일러 온도제어에 대한 기술)

  • Lee, Kwang-Hoon;Lee, Joo-Hyun
    • Proceedings of the KIEE Conference
    • /
    • 1998.07b
    • /
    • pp.719-721
    • /
    • 1998
  • In this paper, we reviewed the steam temperature control in an once through boiler. The steam temperature control is very difficult. Generally, steam temperature of an once through boiler is not only controlled by boiler spray water flow, but also influenced by feed water flow and fuel flow. An advanced control strategy has been developed by experienced engineer. Specifically, We reviewed temperature control strategy for Taian power plant in this paper. This control strategy is represented by state control observer. This state control observer algorithm for temperature control has been used since the late 1980's. This paper describes control strategy employed and observed benefits from advanced steam temperature control.

  • PDF

Compensation Logics of Controller in Korean Standard Super Critical Once Through Boiler

  • Kim, Eun-Gee
    • 제어로봇시스템학회:학술대회논문집
    • /
    • 2001.10a
    • /
    • pp.65.2-65
    • /
    • 2001
  • There are not only lots of controllers such as UMC(Unit Master Controller), BMC(Boiler Master Controller), Fuel Flow controller, Air flow controller, Feed water flow controller, S/H R/H Temperature controller and so on, but also compensation controller such as BTU compensator, Fuel/Water ratio controller and O2 Co controller to take automatic control in the super critical once through boiler. It is important to make complete automation of boiler to use the compensation controller like BTU compensator. For example, In case of some boiler condition, operator has to change combustion parameter for changing the coal, on the contrary BTU compensator can calculate set value of the fuel flow and reset the fuel flow demand by itself. This paper shows us the logic and instruction regarding compensation controller of boiler that can be operated automatically.

  • PDF

A Study on Dynamic Matrix Control using Spray and Damper to Once-through Boiler Steam Temperature (스프레이와 댐퍼를 이용한 관류 보일러 스팀 온도의 (2X2) 동역학 행렬 제어에 관한 연구)

  • Kim, Woo-Hun;Moon, Un-Chul
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.24 no.1
    • /
    • pp.91-97
    • /
    • 2010
  • In this paper, we present simulation results of Dynamic Matrix Control (DMC) to a Once-through boiler steam temperature. In order to control the steam temperatures, we choose spray and damper as two input variables. Then, the step response model is generated for the two major output variables by step test. After that, on-line optimization is performed using $(2\times2)$ step response model. Proposed controller is applied to the APESS (Doosan company's boiler model simulator) and the simulation results show satisfactory performance of proposed control.

The Simulation of Boiler System for HADONG Fossil Power Plant

  • Choi, Jin-Ho;Ma, Sam-Sun;Lee,Yong-Kwan
    • Proceedings of the Korea Society for Simulation Conference
    • /
    • 1999.10a
    • /
    • pp.56-61
    • /
    • 1999
  • The Simulation of Boiler System for Hadong Fossil power plant has been made by Korea Electric Power Research Institute (KERRI) in an attempt to develop Windown NT based full scope replica simulator for Hadong Fossil power plant, 500MWe once-through boiler. In the project KERRI developed Once Through, Super Critical type Boiler System, the core part of the Simulation and integrated the system with other process systems such as BOP System, and AUX System. This paper is to introduce the basic concept of the simulation for the Boiler System. It will also introduce PRO-TRAX System, for used as a modeling tool.

  • PDF