• Title/Summary/Keyword: oil temperature rise

Search Result 86, Processing Time 0.028 seconds

Temperature Characteristic Analysis according to Variation of Properties of Transformer Insulating Oil (변압기 절연유의 물성치 변화에 따른 온도특성해석)

  • Kim, Ji-Ho;Rhee, Wook
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.63 no.4
    • /
    • pp.327-332
    • /
    • 2014
  • In this paper, the temperature distribution according to the property change of the insulating oil of the power transformer and max temperature were predicted through the ductility interpretation which heat-flow is coupled. By using CFD (Computation Fluid Dynamics) for the interpretation, the temperature distribution of 154kV the class single phase power transformer was predicted. The power loss causing the temperature rise of the transformer was changed to the heat source and we used as the input value for the heat-flow analysis. The temperature distribution was predicted according to the change of the density, specific heat, thermal conductivity and viscosity, that is the ingredient having an effect on the temperature rise of the transformer oil. The mineral oil of 4 kinds used in domestic and international based on the interpreted result was selected and the temperature distribution according to each load and Hot Spot temperature was predicted.

Analysis on the Temperature Distribution Characteristics of Insulating oil of Transformer Using the Vegetable oil and Mineral oil (식물성 절연유와 광유가 사용된 유입변압기의 온도분포 특성)

  • An, Jung-Sik;Shim, Meoung-Seop;Jung, Joong-Il;Kim, Nam-Ryul;Huh, Chang-Su
    • Proceedings of the KIEE Conference
    • /
    • 2009.07a
    • /
    • pp.1215_1216
    • /
    • 2009
  • Most transformer use insulating and cooling fluids derived from petroleum crude oil, but mineral oil is some possibility of environmental pollution and fire with explosion. vegetable oil fluids extracted from seed has superior biodegradation and fire-resistant properties including an exceptionally high fire point enhancing fire safety. In this study, it is aimed at the practicality of substituting natural ester dielectric fluid for mineral oil in liquid insulation system of transformers. As a rise in coil winding temperature has a direct influence on transformer life time, it is important to evaluate the temperature rise of coil winding in vegetable oil in comparison with mineral oil. Three transformers for the test are designed with 10KVA, 13.2KV, one phase unit. The temperature are directly measured in insulating oil of these transformers with the two sorts of natural ester and mineral oil dielectric fluid respectively. Temperature of vegetable oil transformers was similar to temperature of mineral oil transformer in the same design at 80% load and above.

  • PDF

Combustion Characteristics of Fish Oil in a Constant Volume Combustion Bomb (정용연소기에 있어서 어유의 연소특성)

  • 서정주
    • Journal of the Korean Society of Fisheries and Ocean Technology
    • /
    • v.28 no.2
    • /
    • pp.184-190
    • /
    • 1992
  • The combustion characteristics, ignition delay, p-t, dp/dt, Q-t of diesel oil and fish oil blended diesel oils was investigated according to pressure and temperature in a constant volume combustion bomb. The results are as follows: 1) The influence of temperature and pressure on the ignition delay was almost constant in high temperature, regardless of the blending rates, and the ignition delay was shortest in the 60% blend. 2) The maximum pressure was high in order of with pure diesel oil, with the 20% blend and the 60% blend. 3) The rate of pressure rise was high in order of with pure diesel oil, with the 20% blend and the 60% blend. The rate of maximum pressure rise was significantly higher with pure diesel oil than with two blends. 4) The amount of accumulative heat release was large in order of with pure diesel oil, with the 20% blend and the 60% blend.

  • PDF

A Study on Scoring Resistance In Lubricated Sliding Contact (윤활 마찰면의 스코링 저항성에 관한 연구)

  • 김해원;홍재학;허준영
    • Transactions of the Korean Society of Mechanical Engineers
    • /
    • v.14 no.2
    • /
    • pp.358-366
    • /
    • 1990
  • As a basic study to clarify the scoring resistance in lubricated sliding contact, the temperature rise on frictional surface was analyzed by theoretical method and the effects of various factors on the temperature rise were examined. On the basic of the results obtained theoretically, the practical equations to calculate the maximum average temperature of the contact surface were proposed which are applicable to sliding contact. Then, the effects of sliding velocity and oil temperature on the seizure behavior, and the relation between seizure and temperature rise were investigated. The following conclusions are deduced : The maximum average temperature rise and the other bulk temperature. The former is affected by the size of heat supply region and the sliding velocity, the latter is affected by heat transfer coefficient. Without regard to the operating condition such as sliding velocity, oil temperature and operating time at each load-step, the maximum average temperature just before seizure is nearly constant except in the region of lower velocity. Consequently, the maximum average temperature of the contact surface in boundary lubrication is a useful criterion to predict the scoring of sliding contact.

Temperature Characteristics of High Speed Angular Contact Ball Bearing (고속 앵귤러 컨택트 볼 베어링의 온도특성)

  • Hyeon, Jun-Su;Park, Tae-Jo
    • Journal of the Korean Society for Precision Engineering
    • /
    • v.18 no.2
    • /
    • pp.96-101
    • /
    • 2001
  • This paper shows the temperature characteristics of a high speed angular contact ball gearing which is 7004C type with ISO P2 tolerance class. A built-in motor type high speed spindle which adopts an oil-air lubrication system was used to measure the temperature rise up to 60,000rpm. The gearing temperature was measured using thermocouples that were attached to the outside surfaces of the outer rings. The result showed that the continuous test method which was suggested in this paper is more effective than on and off method and the lubrication oil supply rate should be reduced in high speed rolling bearings as long as the seizure does not occur. And the result were confirmed that the bearings packed with ceramic balls are superior to those with steel balls in temperature characteristics.

  • PDF

A Study of Coupled Electromagnetic-Thermal Field Analysis for Temperature Rise Prediction of Power Transformer (전력용 변압기의 온도상승 예측을 위한 전자계-열계 결합해석기법 연구)

  • Ahn, Hyun-Mo;Kim, Min-Soo;Song, Jae-Sung;Hahn, Sung-Chin
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.60 no.10
    • /
    • pp.1838-1845
    • /
    • 2011
  • This paper deals with coupled electromagnetic-thermal field analysis for thermal fluid analysis of oil immersed power transformer. Electric power losses are calculated from electromagnetic field analysis and are used as input source of thermal field analysis based on computational fluid dynamics(CFD). Particularly, In order to accurately predict the temperature rise in oil immersed power transformer, the thermal problem should be coupled with the electromagnetic problem. Moreover, to reduce analysis region, the heat transfer coefficient is applied to boundary surface of the power transformer model. The coupling method results are compared with the experimental values for verifying the validity of the analysis. The predicted temperature rises show good agreements with the experimental values.

A Study on the Optimum Clearance Selection of Fuel Pump Journal Bearing with Elasto-hydrodynamic Lubrication Analysis (탄성유체윤활해석에 의한 연료 펌프 저널베어링 최적간극 선정 연구)

  • An, Sung Chan;Lee, Sang Don;Son, Jung Ho;Cho, Yong Joo
    • Tribology and Lubricants
    • /
    • v.33 no.1
    • /
    • pp.23-30
    • /
    • 2017
  • The electric controlled marine diesel engine has fuel pump generating the high pressurized fuel for fuel injection to combustion chamber via a common rail. Fuel pump consists of a cam-roller system. Journal bearing installed between a roller and a cam-roller pin is subjected to fluctuating heavy and instant loads by cam lift. First, Kinematic analysis is carried out to predict bearing loads during one cycle acting on the journal bearing. Second, flexible multi-body dynamic analysis and transient elasto-hydrodynamic(EHD) lubrication analysis for journal bearing considering elastic deformation of cam-roller pin, roller and bearing are conducted using AVL EXCITE/PU software to predict lubrication performance. The clearance ratio and journal groove shape providing lubrication oil are important parameter in bearing design having good performance and can be changed easier than other design parameters such as diameter, width, oil supply pressure and bearing material grade. Generally, journal bearing performance is represented by the minimum oil film thickness(MOFT) and peak oil film pressure(POFP). As well as the traditional design parameters(MOFT, POFP), in this study, temperature rise of lubrication oil is also evaluated through the side leakage flow of supplied oil. By the evaluating MOFT, POFP and temperature rise, the optimum bearing clearance ratio is decided.

Influence of Parameter Setting in an Oil Cooler on the Temperature Characteristics of an Ultra-precision Hydrostatic Table (초정밀 유정압 테이블에서 냉각장치의 변수 설정이 온도특성에 미치는 영향)

  • Khim, Gyungho;Kim, Chang Ju;Oh, Jeong Seok;Park, Chun Hong
    • Journal of the Korean Society for Precision Engineering
    • /
    • v.32 no.6
    • /
    • pp.571-576
    • /
    • 2015
  • Temperature characteristics of supply oil in an ultra-precision hydrostatic table are largely influenced by parameter setting in an oil cooler such as the location of reference sensor and cooling temperature. In this paper, influences of the parameter setting on the temperature variation in the hydrostatic table are experimentally analyzed to suggest the guidelines for practical application. In case of using temperature of inlet oil as a reference sensor in the oil cooler, temperature rise of the supply oil is smaller and thermal settling time is faster than that of using temperature of outlet oil as a reference sensor. The experimental results also show that temperatures of table, rail and return oil can be made almost same, and thermal settling time can be decreased by setting cooling temperature in the oil cooler to be lower than atmospheric temperature.

Analysis of Accelerated Aging Natural Ester Oil and Mineral Oil in Distributional Transformers (배전용 변압기에서의 고온열화와 열 사이클 열화에 따른 식물유와 광유의 특성 분석)

  • An, Jung-Sik;Choi, Sun-Ho;Bang, Jeong-Ju;Jung, Joong-Il;Huh, Chang-Su
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.60 no.6
    • /
    • pp.1163-1168
    • /
    • 2011
  • Most transformers use insulating and cooling fluids derived from petroleum crude oil, but mineral oil has some possibility of environmental pollution and fire with explosion. vegetable oil fluids extracted from seed has superior biodegradation and fire-resistant properties including an exceptionally high fire point enhancing fire safety. In this study, it is aimed at the practicality of substituting natural ester dielectric fluid for mineral oil in liquid insulation system of transformers. As a rise in coil winding temperature has a direct influence on transformer life time, it is important to evaluate the temperature rise of coil winding in vegetable oil in comparison with mineral oil. Four transformers for the test are designed with 10KVA, 13.2KV, one phase unit. The temperature are directly measured in insulating oil of these transformers with the two sorts of natural ester and mineral oil dielectric fluid respectively. Experiment for aging carry out two means. First means remained $120^{\circ}C$ that transformer of mineral oil were operated at 185% load. Second means is that insulating oils of two natural ester and mineral oil were aged by thermal cycles repeating from $30^{\circ}C$ to $120^{\circ}C$. For the heating, Transformers were operated at 185% load. For the cooling, cooling system was operated in the chamber. Samples were analyzed at 42, 63, 93, 143, 190, 240 300cycles. Analysis contents are dielectric strength, total acid value. Mineral oils compared results of first means with results of second means. And compared two sort natural esters respectively with mineral oil in second means.

Multi-physics Analysis for Temperature Rise Prediction of Power Transformer

  • Ahn, Hyun-Mo;Kim, Joong-Kyoung;Oh, Yeon-Ho;Song, Ki-Dong;Hahn, Sung-Chin
    • Journal of Electrical Engineering and Technology
    • /
    • v.9 no.1
    • /
    • pp.114-120
    • /
    • 2014
  • In this paper, a method for multi-physics analysis of the temperature-dependent properties of an oil-immersed transformer is discussed. To couple thermal fields with electromagnetic and fluid fields, an algorithm employing a user defined function (UDF) is proposed. Using electromagnetic analysis, electric power loss dependent on temperature rise is calculated; these are used as input data for multi-physics analysis in order to predict the temperature rise. A heat transfer coefficient is applied only at the outermost boundary between transformer and the atmosphere in order to reduce the analysis region. To verify the validity of the proposed method, the predicted temperature rises in high-voltage (HV) and low-voltage (LV) windings and radiators were compared with the experimental values.