An Experimental Study on the Fire Resistance Performance of Intumescent Coating System with Time Elapse (경년변화에 따른 내화도료의 내화성능에 관한 실험적 연구)

  • Kim, Dae-Hoi;Sung, Si-Chang;Choi, Dong-Ho;Park, Soo-Young;Lee, Sea-Hyun;Lee, Jong-Chan
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2008.04a
    • /
    • pp.61-64
    • /
    • 2008
  • Applying fire resistive coating to steel members is one of the general methods to secure fire resistance performance of steel members. And intumescent coating system is currently one of methods giving fire resistance to steel members. Intumescent coating system for fire resistance, however, has undesirable weaknesses that fire resistance performance of steel members is being deteriorated due to cracks and falling-offs of the coverings as time goes after completion of the coverings to the members. This study is designed to understand changes in fire resistance performance of intumescent coating system through follow-up tests on temperature of unexposed surface for the domestic intumescent coating system.

  • PDF

An Experimental Study on the Fire Resistance Performace of Intumescent Coating System by Environmental Testing Procedure (환경시험방법에 의한 내화도료의 내화성능에 관한 실험적 연구)

  • Park, Soo-Young;Sung, Si-Chang;Choi, Dong-Ho;Kim, Dae-Hoi;Lee, Sea-Hyun;Lee, Jong-Chan
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2008.04a
    • /
    • pp.69-72
    • /
    • 2008
  • This study is designed to understand changes in fire resistance performance of intumescent coating system through follow-up tests on temperature of unexposed surface for the domestic intumescent coating system by environmental testing procedure.

  • PDF

An Experimental Study on the Durability of Intumescent Coating System with Time Elapse (경년변화에 따른 내화도료의 내구성에 관한 실험적 연구)

  • Choi, Dong-Ho;Sung, Si-Chang;Kim, Dae-Hoi;Park, Soo-Young;Lee, Sea-Hyun;Lee, Jong-Chan
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2008.04a
    • /
    • pp.65-68
    • /
    • 2008
  • Intumescent coating system for fire resistance has undesirable weaknesses that fire resistance performance of steel members is being deteriorated due to cracks and falling-offs of the coverings as time goes after completion of the coverings to the members. This study is designed to understand changes in durability of intumescent coating system through follow-up tests on bond strength and thickness for the domestic intumescent coating system.

  • PDF

The Research for the Establishment of Test Method of Durability on Intumescent Coating System (내화도료 내구성 평가 방법 설정에 관한 연구)

  • Choi, Dong-Ho
    • Fire Science and Engineering
    • /
    • v.23 no.1
    • /
    • pp.40-47
    • /
    • 2009
  • Applying fire resistive coating to steel members is one of the general methods to secure fire resistance performance of steel members. And intumescent coating system is currently one of methods giving fire resistance to steel members. Intumescent coating system for fire resistance, however, has undesirable weaknesses that fire resistance performance of steel members is being deteriorated due to cracks and falling-offs of the coverings as time goes after completion of the coverings to the members. So it is necessary to understand changes of the durability and the fire resistance performance of intumescent coating system over a time elapse and to reflect such change properly into the building design and construction. This research is performed to present the test method of durability and the maintenance of intumescent coating system through theoretical investigation of the test method of durability and the guide of maintenance & management of intumescent coating system of several countries, including the Britain, United States, Japan.

Preparation of EVA/Intumescent/Nano-Clay Composite with Flame Retardant Properties and Cross Laminated Timber (CLT) Application Technology (난연특성을 가지는 EVA/Intumescent/나노클레이 복합재료 제조 및 교호집성재(Cross Laminated Timber) 적용 기술)

  • Choi, Yo-Seok;Park, Ji-Won;Lee, Jung-Hun;Shin, Jae-Ho;Jang, Seong-Wook;Kim, Hyun-Joong
    • Journal of the Korean Wood Science and Technology
    • /
    • v.46 no.1
    • /
    • pp.73-84
    • /
    • 2018
  • Recently, the importance of flame retardation treatment technology has been emphasized due to the increase in urban fire accidents and fire damage incidents caused by building exterior materials. Particularly, in the utilization of wood-based building materials, the flame retarding treatment technology is more importantly evaluated. An Intumescent system is one of the non-halogen flame retardant treatment technologies and is a system that realizes flame retardancy through foaming and carbonization layer formation. To apply the Intumescent system, composite material was prepared by using Ethylene vinyl acetate (EVA) as a matrix. To enhance the flame retardant properties of the Intumescent system, a nano-clay was applied together. Composite materials with Intumescent system and nano - clay technology were processed into sheet - like test specimens, and then a new structure of cross laminated timber with improved flame retardant properties was fabricated. In the evaluation of combustion characteristics of composite materials using Intumescent system, it was confirmed that the maximum heat emission was reduced efficiently. Depending on the structure attached to the surface, the CLT had two stages of combustion. Also, it was confirmed that the maximum calorific value decreased significantly during the deep burning process. These characteristics are expected to have a delayed combustion diffusion effect in the combustion process of CLT. In order to improve the performance, the flame retardation treatment technique for the surface veneer and the optimization technique of the application of the composite material are required. It is expected that it will be possible to develop a CLT structure with improved fire characteristics.

Evaluation of Mechanical Performance and Flame Retardant Characteristics of Biomass-based EVA Composites using Intumescent Flame Retardant Technology

  • Park, Ji-Won;Kim, Hoon;Lee, Jung-Hun;Jang, Seong-Wook;Kim, Hyun-Joong
    • Journal of the Korean Wood Science and Technology
    • /
    • v.46 no.2
    • /
    • pp.189-201
    • /
    • 2018
  • Intumescent system is a highly effective flame retardant technology that takes advantage of the mechanism of foaming and carbonization. In order to materialize Intumescent system, it is necessary to use reinforcement material to improve the strength of the material. In this study, we used kenaf as a natural fiber to manufacture intumescent/EVA (ethylene vinyl acetate) composites to improve mechanical and flame retardant performance. Finally two materials with different particle shape are applied to one system. Therefore, the influence factors of the particles with different shapes on the composite material were analyzed based on the tensile test. For this purpose, we have used the tensile strength analysis model and confirmed that it can only act as a partial strength reinforcement due to weak binding force between the matrix and particles. In the combustion characteristics analysis using cone calorimeter and UL 94, the combustion characteristics were enhanced as the content of Intuemscent was increased. As the content of kenaf increased, combustion characteristics were strengthened and carbonization characteristics were weakened. Through the application of kenaf, it can be confirmed that elastic modulus improvement and combustion characteristics can be strengthened, which confirmed the possibility of development of environmentally friendly flame retardant materials.

Finite element study on composite slab-beam systems under various fire exposures

  • Cirpici, Burak K.;Orhan, Suleyman N.;Kotan, Turkay
    • Steel and Composite Structures
    • /
    • v.37 no.5
    • /
    • pp.589-603
    • /
    • 2020
  • This paper presents an investigation of the thermal performance of composite floor slabs with profiled steel decking exposed to fire effects from floor. A detailed finite-element model has been developed by representing the concrete slab with steel decking under of it and steel beam both steel parts protected by intumescent coating. Although this type of floor systems offers a better fire resistance, passive fire protection materials should be applied when a higher fire resistance is desired. Moreover, fire exposed side is so crucial for composite slab systems as the total fire behaviour of the floor system changes dramatically. When the fire attack from steel parts, the temperature rises rapidly resulting in a sudden decrease on the strength of the beam and decking. Herein this paper, the fire attack side is assumed from the face of the concrete floor (top of the concrete assembly). Therefore, the heat is transferred through concrete to the steel decking and reaching finally to the steel beam both protected by intumescent coating. In this work, the numerical model has been established to predict the heat transfer performance including material properties such as thermal conductivity, specific heat and dry film thickness of intumescent coating. The developed numerical model has been divided into different layers to understand the sensitivity of steel temperature to the number of layers of intumescent coating. Results show that the protected composite floors offer a higher fire resistance as the temperature of the steel section remains below 60℃ even after 60-minute Standard (ISO) fire and Fast fire exposure. Obtaining lower temperatures in steel due to the great fire performance of the concrete itself results in lesser reductions of strength and stiffness hence, lesser deflections.

Strength Characteristics of Passive Fire Protection Material Applied Structural Members on Fire Load (수동화재보호 재료가 적용된 구조부재의 화재하중에 대한 강도 특성)

  • Jo, Sang Chan;Yu, Seung Su;Seo, Jung Kwan
    • Journal of the Society of Naval Architects of Korea
    • /
    • v.59 no.1
    • /
    • pp.29-38
    • /
    • 2022
  • In offshore installations, fires cause the structure to lose its rigidity and it leads to structural integrity and stability problems. The Passive Fire Protection (PFP) system slows the transfer rate of fire heat and helps prevent the collapse of structures and fatality. Especially, intumescent epoxy coating is widely used in the offshore industry, and not only is the material cost expensive, but it also takes a lot of time and cost for construction. Several studies have been conducted on the efficient application and optimal design of the PFP system. However, the mechanical properties and the strength of the PFP material have not been considered. In addition, researches on the correlation between the thickness of PFP and the structural behavior were insufficient. Therefore, this study aims to analyze the thermal and mechanical effects of the PFP on the structure when it is applied to the structural member. In particular, it is intended to resolve the change in strength characteristics of the structural members as the thickness of the PFP increases.