• 제목/요약/키워드: grounding resistance

검색결과 246건 처리시간 0.028초

메쉬접지전극의 축척모형에 관한 추정 (Presumption for Reduced Scale Model of Mesh Electrod)

  • 고희석;김주찬;이충식;최종규
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2002년도 학술대회 논문집 전문대학교육위원
    • /
    • pp.29-33
    • /
    • 2002
  • There are a lot of errors and little accuracy when calculating the grounding resistance with the transposition methods in the equivalent surface of hemisphere electrode. Therefore we should calculate the grounding resistance by using the mesh factor, In this paper, we would estimate the grounding value of mesh electrode with water tank model & estimation method using the reduced scale ratio of mesh electrode based on the theory of model electrode & proportional factor according to the reduced scale ratio. And also we have confirmed the accuracy of the empirical formula of model electrode by using the regression analysis.

  • PDF

대지 저항률이 접지 특성에 미치는 영향 (Effects of Soil Resistivity on the Grounding Characteristics)

  • 정연하;장태준;곽희로;노영수;최충석
    • 조명전기설비학회논문지
    • /
    • 제19권5호
    • /
    • pp.74-79
    • /
    • 2005
  • 본 논문에서는 전국4개 도시에서 측정한 대지 저항률을 바탕으로 지층구조를 분석하고 접지시스템의 특성을 조사하였다. 그 결과 대지 저항률은 접지 저항 뿐만 아니라 안전과 직접 관련되는 지표면 전위, 접촉전압, 보폭전압에 영향을 미치는 것으로 밝혀졌다.

접지전류의 주파수에 따른 수직 접지전극 주변에서 전위간섭 영향 분석 (An Analysis of Potential Interference Effects in the Vicinity of Ground Rod Depending on Frequency of Ground Currents)

  • 이복희;조용승;최종혁;양순만
    • 조명전기설비학회논문지
    • /
    • 제25권12호
    • /
    • pp.88-93
    • /
    • 2011
  • When the ground current is injected into the adjacent ground electrode, the potential interference is caused between ground electrodes, the ground potential interferences have been largely studied with power frequency fault currents. Many attempts to find the frequency-dependent grounding impedance report that the high frequency grounding impedance is very different with the ground resistance. This paper presents experimental data on the frequency-dependent potential interference effects in the vicinity of ground rod. The ground potential rises around the test ground rod of 4 or 6[m] were measured and discussed. As a result, the ground potential rises and potential interference factor are decreased with decreasing the grounding impedance. It was found that the lowering of grounding impedance is critical to reduce the ground potential interference effects.

변전소 접지설계를 위한 대지저항율 측정시 전극간격이 해석결과에 미치는 영향 (Effects of Maximum Probe Spacing of Wenner Method on Substation Grounding)

  • 최종기;기현찬;정길조;김범진
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 하계학술대회 논문집 E
    • /
    • pp.2355-2357
    • /
    • 1999
  • Estimating equivalent soil model which represents an actual soil structure and its electrical characteristics, is extremely improtant for good substation grounding system design and analysis. Since the equivalent soil model is deduced based on the measured apparent soil resistivity - generally obtained from Wenner's 4-point method, reasonable and accurate measuring technique and procedure guarantee good grounding system design and analysis. The paper aims to show the importance of reasonable enough probe spacing by presenting the influence of soil modelling to estimation and measurement of grounding resistance of substation grounding grid.

  • PDF

임펄스 전류에 대한 대규모 접지시스템의 정상상태 및 과도상태의 접지임피던스 특성 (Charicteristics of Stationary and Transient Ground Impedance of Large-Scale Grounding Piles)

  • 이복희;이승칠;박종순
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 하계학술대회 논문집 E
    • /
    • pp.2296-2298
    • /
    • 1999
  • The stationary ground resistance and the transient ground impedance of grounding system are very important parameters in the field of lightning and surge protection. But, it is very difficult to obtain correct values of them in large-scale grounding system. In this paper, the stationary and transient ground impedances of a large-scale grounding system have been measured and analyzed under impulse currents. In order to obtain correct values of them, we have described Z-v(impedance vs ground potential rise) distributions and Z-t waveforms. The transient ground impedance of 36 [m] long three-parallel grounding piles have showed the inductive aspects and the hysterisis region under impulse currents.

  • PDF

2회선 배전계통에서 가공지선 접지 및 피뢰기 설치환경에 따른 뇌과전압 해석 (Analysis of Lightning Overvoltage with Earth of Overhead Grounding Wire and Installation Types of Arrester in Double Circuits Distribution Systems)

  • 정채균;김상국;이종범;정영호
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 하계학술대회 논문집 A
    • /
    • pp.497-499
    • /
    • 2003
  • This paper analyses the lightning overvoltage with earth of grounding wire and installation types of arresters in double circuits distribution systems. First, the model for analysis is selected severer case between upper line and lower line when the direct lightning surge strikes on the overhead grounding wire. The lightning overvoltage is variously calculated with earth distance between overhead grounding wires. This paper also analyses the effect of the installation distance between arrestors and the earth resistance of overhead grounding wire. From these results, authors examine the rationality of BIL that is applied in distribution system.

  • PDF

임펄스전류에 의한 매설지선의 과도임피던스특성에 대한 모의해석 (Simulated Analysis for the Transient Impedance Behaviors of Counterpoises Subjected to the Impulsive Currents)

  • 조정현;이복희
    • 전기학회논문지
    • /
    • 제58권10호
    • /
    • pp.1861-1868
    • /
    • 2009
  • A ground electrode subjected to lightning surge current shows the transient impedance behaviors. The ground electrode for protection against lightning should be evaluated in view of the transient grounding impedance and conventional grounding impedance, not ground resistance. The transient impedance characteristics of ground electrodes are influenced by the shape of ground electrode and the soil characteristics, as well as the waveform of lightning surge current. In order to propose a simulation method of analyzing the transient impedance characteristics of the grounding system in practical use, this paper suggests a theoretical analysis method of distributed parameter circuit model to simulate the transient impedance characteristics of counterpoise subjected to lightning surge current. EMTP and Matlab programs were employed to compute the transient grounding impedances of three counterpoises with different lengths. As a consequence, the simulated results using the proposed distributed parameter circuit model are in good agreement with the measured results.

접지시스템 주파수 특성의 측정과 해석 (Measurement and Analysis of Frequency Characteristics of Grounding Systems)

  • 최종기;안용호;구선근;박기준;윤진열;정길조;류보혁;김정훈
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제53권5호
    • /
    • pp.248-252
    • /
    • 2004
  • Since DC ground resistance, which is a good index of the performance of a grounding system in low frequency. does not show the performance in transient state. We measured ground impedances in frequency domain ranging from 0.1 Hz to 900 KHz maximum to quantify the transient grounding performance of 4 types of grounding system. Transfer function was derived from the measured frequency-dependant ground impedance of a grounding grid. A simulation has been performed to verify the transfer function using EMTP (Electro-Magnetic Transient Program).

초전도 한류기를 주변압기 접지선에 설치시 배전계통의 순간전압품질 분석 (Voltage Quality Analysis in Power Distribution System with Superconducting Fault Current Limiter at Grounding Line)

  • 문종필
    • 전기학회논문지P
    • /
    • 제62권4호
    • /
    • pp.159-163
    • /
    • 2013
  • In this paper, voltage quality improvement is analyzed in case of Superconducting Fault Current Limiter (SFCL) installed in grounding line of main transformer in power distribution system. First, a resistive-type SFCL model is used. Next, Korean power distribution system is modeled. Finally, when SFCL is installed in the starting point of feeder and grounding line of main transformer, voltage qualities are evaluated according to various fault locations and resistance values of SFCL using PSCAD/EMTDC. The voltage quality results in case of grounding line are compared with the voltage in case of feeder.

메쉬접지전극과 차폐패넬을 이용한 접지저항 및 접지전극간의 영향에 관한 연구 (Study on the Between the Grounding Resistance and Grounding Electrode using Mesh Grounding Electrodes and a Shielding Panel)

  • 이충식;조문택;나승권
    • 한국항행학회논문지
    • /
    • 제19권3호
    • /
    • pp.230-236
    • /
    • 2015
  • 본 논문에서는 접지전극이 상호 간섭의 문제가 발생했을 때 파급효과가 큰 차폐시스템의 패넬과 접지전극으로 널리 사용되고 있는 봉상전극, 메쉬전극, 판상전극을 2차원에 점 전류원의 집합체로 가정하여 이에 대한 전극표면전위를 이용하였다. 실험에 사용한 수조모델의 유한성과 축척에 의해 제작된 모델전극의 축척한계를 수조모델의 크기에 대해 실험오차에 따른 중단오차를 최대한 줄이는 수법으로 실험모델전극을 선정하였다. 복수의 접지도체가 동일 접지저항구역 내에 존재할 경우 도체의 형상 및 매설 조건에 따른 간섭효과의 척도로 사용되는 전위간섭계수의 도출 방법을 제시하였다. 또한 실험에 사용한 접지전극의 수치시뮬레이션을 통해 이론의 타당성을 검증하고, 검증된 이론과 모의실험을 통해 본 연구를 구체화 하였다.