DOI QR코드

DOI QR Code

Voltage Quality Analysis in Power Distribution System with Superconducting Fault Current Limiter at Grounding Line

초전도 한류기를 주변압기 접지선에 설치시 배전계통의 순간전압품질 분석

  • 문종필 (한국교통대 전기공학과)
  • Received : 2013.08.20
  • Accepted : 2013.10.01
  • Published : 2013.12.01

Abstract

In this paper, voltage quality improvement is analyzed in case of Superconducting Fault Current Limiter (SFCL) installed in grounding line of main transformer in power distribution system. First, a resistive-type SFCL model is used. Next, Korean power distribution system is modeled. Finally, when SFCL is installed in the starting point of feeder and grounding line of main transformer, voltage qualities are evaluated according to various fault locations and resistance values of SFCL using PSCAD/EMTDC. The voltage quality results in case of grounding line are compared with the voltage in case of feeder.

Keywords

References

  1. J. F. Moon, S. H. Lim, J. C. Kim, S. Y. Yun, "Assessment of the Impact of SFCL on Voltage Sags in Power Distribution System," IEEE Trans. on Applied Superconductivity, Vol. 21, No. 3, pp. 2161-2164, June 2011. https://doi.org/10.1109/TASC.2010.2093592
  2. Lin Ye, LiangZhen Lin, and Klaus-Peter Juengst, "Application Studies of Superconducting Fault Current Limiters in Electric Power Systems," IEEE Trans. on Applied Superconductivity, Vol. 12, No. 1, March 2002.
  3. J. C. Das, "Limitations of Fault-Current Limiters for Expansion of Electrical Distribution Systems," IEEE Trans. on Industry Application, Vol. 33, No. 4, July/Aug. 1997.
  4. Fabio Tosato and Stefano Quaia, "Reducing Voltage Sags Through Fault Current Limitation," IEEE Trans. on Power Delivery, Vol. 16, No. 1, Jan. 2001.
  5. H. R. Kim, H. S. Choi, H. R. Lim, I. S. Kim, and O. B. Hyun, "Resistance of superconducting fault current limiters based on YBa2Cu3O7 thin films after quench completion," Physical C, Vol. 372-376, pp. 1606-1609, Aug. 2002. https://doi.org/10.1016/S0921-4534(02)01083-3
  6. S. H. Lim, S. R. Lee, H. S. Choi, and B. S. Han, "Analysis of operational characteristics of flux-lock type SFCL combined with power compensator," IEEE Trans. Applied Superconductivity, Vol. 15, No. 2, pp. 131-134, June 2005.
  7. H. R. Kim, S. W. Yim, S. Y. Oh, and O. B. Hyun, "Recovery in Superconducting Fault Current Limiters at Low Applied Voltages," IEEE Trans. Applied. Superconductivity, Vol. 18, No. 2, pp. 656-659, June 2008. https://doi.org/10.1109/TASC.2008.920809
  8. H. R. Kim, S. W. Yim, S. Y. Oh, and O. B. Hyun, "Analysis on recovery in Au/YBCO thin film meander lines," Progress Superconductivity, Vol. 9, No. 1, pp. 119-125, 2007.
  9. J. S. Kim, S. H. Lim, J. F. Moon, et. al, "Analysis on the Protective Coordination on Neutral Line of Main Transformer in Power Distribution Substation with Superconducting Fault Current Limiter," The Trans. on the Korean Institute of Electrical Engineers, Vol. 58, No. 11, pp. 2089-2094, Nov. 2009.
  10. H. R. Kim, S. W. Yim, O. B. Hyun, et. al, "Anlaysis on Recovery Characteristics of Superconducting Fault Current Limiters," MT-20 Conference on Magnet Technology, Philadelphia, Aug. 27-31, 2007.
  11. J. F. Moon, J. S. kim, "Voltage Sag Analysis in Loop Power Distribution System with SFCL," IEEE Trans. on Applied Superconductivity, Vol. 23, No. 3, June 2013, will be published