• 제목/요약/키워드: grounding method

검색결과 293건 처리시간 0.026초

접지전류 측정에 의한 다중 접지계통의 접지저항 측정 (Measurement of Resistance of Multi-Grounded System by Ground Current Measurement)

  • 최종기;안용호;정길조;한병성;김경철
    • 대한전기학회논문지:전기기기및에너지변환시스템부문B
    • /
    • 제53권4호
    • /
    • pp.234-234
    • /
    • 2004
  • Measuring ground resistance has been a popular method of evaluation of the grounding electrode performance. If some portions of grounding electrodes are lost by corrosion, aging or other reasons, consequent deteriotation of the grounding performance would be resulted. It is one of the reasons why it is required to evaluate the performance of grounding systems regularly. However, in case of the electric facilities with multi-grounded system such as power substations with multi-grounded overhead ground wires and/or distribution line neutrals, it is practically difficult to disconnect neutrals or skywires from the substation grounding mesh for the ground resistance measurement. In this paper, a method for the grounding performance measurement of multi-grounded systems, which is based on the measuring ground current distributions, has been proposed. A field test results has shown the validity of the proposed test method.

전자계 시뮬레이션 도구를 이용한 복합 형상의 접지 시스템 해석 (Analysis of Complex Ground Systems using Electromagnetic Simulation Method)

  • 김영진;김재형;김성주
    • 한국안전학회지
    • /
    • 제31권1호
    • /
    • pp.48-53
    • /
    • 2016
  • This paper deals with analysis of complex grounding system using electromagnetic simulation method. Electrical devices could be damaged by transient voltage such as a lightning surge. Therefore the measures to protect the equipments from transient, such as a lightning are required. The ground system is important in this respect. The representative parameter of grounding system performance is earth ground resistance. Precise prediction of earth resistance is required, because it is difficult to modify and change after the completion of the grounding system construction. Numerical modeling is often used in numerical analysis to identify the electrical characteristics of the grounding system. However complex systems are difficult to predict grounding characteristics by numerical analysis. If the total electric field of the earth in general is similar to the antenna model, in that the incident electric field and expressed as a sum of the scattering field. In this study, the electromagnetic field simulation tool "ANSYS HFSS" module containing the antenna model was used to analyze performance of ground system. Both the simple and complex grounding system were analyzed by simulation tool and experimental method. As a result simulation method is effective to predict performance of a complex ground system.

접지임피던스의 변동이 최소가 되는 동축형 탄소접지전극의 길이의 산정 (Determination of the Length of Coaxial Type Carbon Grounding Electrode to Minimize the Fluctuation of Grounding Impedance)

  • 이강수;김종호;이복희
    • 조명전기설비학회논문지
    • /
    • 제24권12호
    • /
    • pp.164-170
    • /
    • 2010
  • For the surge currents like lightning or ground fault currents containing high frequency components which cause the electromagnetic interferences for the electronic devices and communication equipment, the grounding impedances give the significantly composite characteristics which are dependent on the frequency of surge currents. In this paper, the analytical model and method for determining the optimal length of the newly developed coaxial type carbon ground electrode which has a little fluctuation in grounding impedance with frequency. The length of minimizing the fluctuation of grounding impedance by changing frequency from 100[Hz] to 1[MHz] was determined, and the validity of this proposed method was confirmed by comparing with the simulated and measured data.

접지설비 절차에 따른 개선된 접지실비 모델 (An Improved Model for Grounding System Using process of Grounding Design)

  • 송영주
    • 조명전기설비학회논문지
    • /
    • 제22권6호
    • /
    • pp.50-60
    • /
    • 2008
  • 국내 접지시스템 설계시 가장 널리 사용되는 것은 ANSI/IEEE Std. 80-2000이나 국내 접지설계 환경의 적정성 여부는 검토되고 있지 않다. 따라서 본 논문에서는 국내 접지설계 환경을 고려한 새로운 접지도체의 굵기 산정방법과 접지도체의 위험전압 산정방법, 접지도체의 Grid간격 산정방법을 적용하여 ANSI/IEEE Std.80-2000을 보완한 새로운 접지시스템 설계 방법을 제시하였다. 또한 ANSI/IEEE Std. 80-2000 Annex B의 사례연구를 통해 IEEE Std. 80에 의한 방식과 비교 검토하여 신뢰성과 경제성을 검증하였다.

전기철도의 공용접지 시스템에 대한 안정성 평가에 관한 연구 (Safely Evaluation on Common Grounding System for Electric Railway)

  • 송진호;황유모
    • 대한전기학회논문지:전기기기및에너지변환시스템부문B
    • /
    • 제51권6호
    • /
    • pp.298-306
    • /
    • 2002
  • We performed an safety evaluation on constructing of a common grounding system for electrical railway in view of its efficacy and technical fit. In order to compare the conventional grounding method, which has been individually conducted, with the common grounding with all ground wires connected in common to the counterpoise buried below the surface of the earth in parallel with rail, we set up scenarios with several cases of fault and load conditions in Chungbuk railway sections with the common grounding system. Based on models for railway conductors including the grounded system, line Parameters of railway power system are computed. The circuit model for power system with up and down lines, auto-transformers and railway substations is used to compute impedances of counterpoise and substation ground net. For each scenario with faults and operation conditions of railway, the induced potentials on signal and communication lines are also computed. It is shown that the common grounding for Chungbuk railway is superior experimentally to the conventional method in three respects: (1) the lower rail potentials during operation of railway in line, (2) the lower rail potentials for short-circuit faults between catenary and rail, and (3) the lower stress voltages on signal and communication lines for short-circuit or ground faults. The analysis results confirm that the grounding system for electric railway is required to be built by the common grounding and be evaluated on its safety in design.

전력사용 시설물의 Pattern Search 법을 이용한 최적 접지 설계에 관한 연구 (A Study on the Optimal Grounding Design using Pattern Search Method for Electric Power Facilities)

  • 김경철;최병숙
    • 조명전기설비학회논문지
    • /
    • 제16권1호
    • /
    • pp.58-66
    • /
    • 2002
  • 전력사용 시설물은 사고시 대지에 전류를 흘려 보내고, 시설물의 손상, 화재와 인체의 감전 충격을 방지하기 위해서 반드시 효과적인 접지를 하여야 한다. 본 논문에서는 Pattern Search법을 이용하여 접지시스템의 최적의 각종 파라메터를 구하고자 한다. Pattern Search법을 이용하여 구한 파라메터를 입력으로 하여 시뮬레이션한 결과 최적의 접지 시스템을 확인하였다.

위험전압 검토에 의한 메시접지설계 (Mesh Grounding Grid Design of Dangerous Voltage Review)

  • 손석금;김재철
    • 전기학회논문지P
    • /
    • 제60권3호
    • /
    • pp.120-125
    • /
    • 2011
  • When we design the grounding grid, dangerous voltage ANSI/IEEE Std. 80 method has been commonly used in the domestic area. However, the suitability of the ground rules for the design environment available. However, the suitability of the ground rules for the design environment available. In this paper, sticks according to the electrode conductor in combination with the mesh in order to design the ground by the IEEE Std.80 was designed. So in this paper, we examined of IEEE Std. 80 touch voltage method marginal utility and we induced for those problems by comparison between IEEE Std. 80 touch voltage value and simulation experimentation value. Furthermore, this paper presents a new design grounding system method that complements the IEEE Std. 80 method.

현장실측에 의한 메시(Mesh)접지저항 출정기법 연구 (A Study on the Measurement Technique of the Grounding Mesh Resistance by Field Measurements)

  • 한기붕;김삼수;정세중;이상익
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 1999년도 춘계학술대회 논문집
    • /
    • pp.426-429
    • /
    • 1999
  • In this paper, we have provided the measurement technique of the grounding mesh resistance by field measurements. The standard of measurement is specified in the IEEE Std 81.2-1991 and JEAC 5001-1988, which is the the fall-of-potential method by test-current injection, but this method is difficult to apply at field, where is small around a electric power substation of domestic. For the convenient measurement method, space of assistant probe and quantity of test-current injection are changed step for step. As the result, ' the proposed measurement technique of grounding mesh resistance is that the space of current and potential probes must be fixed at 150rn from a grounding mesh, the test-current injection has to keep 5A or more.

  • PDF

매설지선 방식을 적용한 에너지 자립마을용 수상 태양광 발전 시스템의 접지저항 분석 (Analysis of Grounding Resistance for Zero Energy Town Floating PV System Using Underground Wiring)

  • 고재우;임종록;;차혜림;김시한;이창구;안형근
    • 한국전기전자재료학회논문지
    • /
    • 제29권5호
    • /
    • pp.303-306
    • /
    • 2016
  • Floating PV system is installed on the water such as artificial lake, reservoir, river for the purposes of zero energy town and/or large scale of PV station. There are electrical gains from cooling effect by water and reflection of water surface. Particularly, floating PV power station with high efficiency solar cell modules receives a lot of attention recently. Floating PV system is installed on the water, which means grounding method to the frame of solar cell and electrical box such as connector band and distribution panelboard should be applied in different way from grounding method of PV system on land. The grounding resistance should be 10[${\Omega}$] in case the voltage is over 400[V] in accordance with Korean Standard. The applicable parameters are the resistivity of water in various circumstances, depth of water, and length of electrode in order to meet 10[${\Omega}$] of grounding resistance. We calculated appropriate length of the electrode on the basis of theoretical equation of grounding resistance and analyzed the relation between each parameters through MATLAB simulation. This paper explains grounding system of floating PV power station and presents considerations on grounding design according to the resistivity of water.

Investigation on the Spot for Grounding Systems in Buildings

  • Gil, Hyoung-Jun;Kim, Dong-Woo;Kim, Dong-Ook;Kim, Hyang-Kon
    • 조명전기설비학회논문지
    • /
    • 제24권3호
    • /
    • pp.39-45
    • /
    • 2010
  • This paper deals with investigation on the spot for grounding systems of buildings based on international standards at construction sites. The investigation was carried out for grounding method, grounding type, shape of grounding electrode, grounding for a lightning protection system, continuity of steelwork in reinforced concrete structures, etc. The investigation on the spot was performed by a researcher and engineer with over fifteen years of industry experience all over the country. As a result of the investigation on the spot in 13 buildings, common grounding and structure grounding methods were dominant. The safety improvement methods include installation of equipotential bonding conductors for the connection to the main earthing terminal, equipotential bonding conductors for supplementary bonding, use of Surge Protective Devices (SPD), and safe connections between earthing conductors and the rebar.