• 제목/요약/키워드: fire dynamics simulation

검색결과 165건 처리시간 0.048초

공연장 무대부 화재에 대한 전산해석 연구: 자연 배연구 면적과 화원 위치 영향 (Numerical Investigation on Fire of Stage in Theater: Effects of Natural Smoke Vent Area and Fire Source Location)

  • 박민영;이치영
    • 한국안전학회지
    • /
    • 제37권1호
    • /
    • pp.1-11
    • /
    • 2022
  • This numerical study investigates the effects of the size of the natural smoke vent area (10% and 1% of the floor area) and the location of the fire source (i.e., at the side and center of the stage) on the temperature distribution in the compartment and velocity distribution and mass flow rate of flow through a natural smoke vent for a reduced-scale model of a theater stage. Then, the mass flow rate of outflow through the natural smoke vent in the event of a fire for a real-scale theater stage was examined. The case with the larger natural smoke vent area and central fire source location showed lower temperature distributions and higher mass flow rates of outflow and inflow than the case with the smaller natural smoke vent area and side fire source location. The trends of the temperature distributions were closely related to those of the mass flow rates for the outflow and inflow. Additionally, the case with the larger natural smoke vent area and central fire source location exhibited the most non-uniform flow velocity distribution in all cases tested. A bidirectional flow, in which the outflow and inflow occur simultaneously, was observed through the natural smoke vent. In the event of a fire situation in a real-scale theater stage, it was predicted that the case with the larger natural smoke vent area and central fire source location would have a mass flow rate of outflow that is 43.53 times higher than that of the case with the smaller natural smoke vent area and side fire source location. The present results indicate that the natural smoke vent location should be determined by considering the location in a theater stage where a fire can occur.

민감도 분석을 이용한 원전 주제어실의 케비닛 화재에 대한 거주성 평가 (Assessment of the Habitability for a Cabinet Fire in the Main Control Room of Nuclear Power Plant using Sensitivity Analysis)

  • 한호식;이재오;황철홍;김주성;이상규
    • 한국화재소방학회논문지
    • /
    • 제31권2호
    • /
    • pp.52-60
    • /
    • 2017
  • NUREG-1934에서 제시된 원자력발전소 주제어실의 케비닛 화재를 대상으로 운전원의 거주성을 평가하기 위하여 수치해석이 수행되었다. 이를 위해 본 연구에서는 대표적인 화재모델인 FDS가 사용되었다. 운전원의 거주성을 결정하는 기준으로서 복사 열유속, 상층부 온도, 연층높이 및 연기의 광학밀도뿐만 아니라, CO 등과 같은 독성물질의 농도가 포함되었다. 주요 결과로서, 화재모델의 확인 및 검증(V&V) 기반의 주요 입력인자 민감도 및 모델 불확실도 분석을 통해 다양한 화재시나리오에 대하여 거주성 기준의 초과 확률 및 거주 가능시간이 산출되었다. 최대 열방출률, CO 및 Soot yields의 민감도 분석을 통해, 거주시간 뿐만 아니라 거주성을 결정하는 한계기준의 변화가 발생됨을 확인하였다. 이러한 방법론은 불확실한 케비닛 화재정보를 이용한 주제어실의 거주성 평가의 신뢰성 강화를 위한 현실적인 대안이라 판단된다.

점화원 위치 및 점화시간 변화에 따른 백드래프트 거동에 관한 수치적 연구 (A Numerical Study of the Backdraft Behavior with the Variation of the Ignition Location and Time)

  • 고민욱;오창보;한용식;도규형
    • 한국안전학회지
    • /
    • 제31권4호
    • /
    • pp.1-8
    • /
    • 2016
  • The behavior of backdraft in the compartment with different ignition locations and times was numerically investigated. The Fire Dynamics Simulator (FDS) v5.5.3 with a model-free simulation option was used in the numerical simulation of backdraft. The ignition source was located near the inside wall, at the compartment center and near the window opening, respectively. The ignition was started at the instance when the fresh air reached the ignition location or when a sufficient time passed compare to the instance of the arriving of the fresh air to the ignition location. As a result, for the ignition source was located near the inside wall, a strong fire ball was observed at once and the result was similar to the previous experimental result. For the ignition source was located at the center of the compartment, a strong fire ball was occurred and two strong fire balls were observed consecutively for the ignition time was delayed. For the ignition source was located near the window opening and longer time was given for the ignition compare the duration of the fresh air arriving to the ignition location, the rapid temperature variation was not observed because there was no flame. However, for the ignition was started at the instance when the fresh air reached the ignition location, the ignition could be initiated and a intensive fire ball was observed. The pressure measured at the upper inside part of the window opening provided a similar trend with the previous experimental result of compartment backdraft.

산불확산패턴 연구를 위한 시뮬레이션 모델 (A Simulation Model for the Study on the Forest Fire Pattern)

  • 송학수;전원주;이상희
    • 한국시뮬레이션학회논문지
    • /
    • 제22권2호
    • /
    • pp.101-107
    • /
    • 2013
  • 최근 지구 온난화 현상으로 이상기후가 세계 곳곳 에서 발생하고 있으며, 이는 빈번한 산불 발생 및 산불의 대형화에 많은 기여를 하고 있다는 것이 보고되고 있다. 산불은 재산피해, 인명피해 뿐만 아니라 특히, 생태계 파괴를 촉진시키는 매우 심각한 요인 중의 하나이다. 산불로 인한 생태계 파괴 문제를 해결하기 위한 방안으로, 다양한 산불확산 및 패턴 수리모델이 개발되어져 왔다. 본 연구에서는, 바람 요인이 고려된 산불패턴을 시뮬레이션 할 수 있는 수리 모델을 제안하였다. 모델은 격자기반위에서 구성되었으며 셀룰라오토마타 방법을 사용하였다. 모델에서, 숲은 불이 쉽게 옮겨 붙는 나무와 그렇지 않은 나무 두 종류로 구성되었다. 산불이 확산되는 과정에서 연소된 나무의 개수가 전체 시뮬레이션 격자개수의 25% (= 10,000) 되는 시점(T)을 세 개의 독립변수인, 전체 나무밀도, 불 전이 확률이 큰 나무 밀도, 그리고 바람의 세기에 대해 어떤 영향을 받는지를 조사하였다. 나무 밀도가 커질수록, T의 값은 줄어들었고, 바람의 세기가 커질수록 T의 값이 줄어들었다. 나무밀도가 너무 크거나 작은 경우, 바람의 효과가 감소하였다. 본 연구에서, 제안한 산불확산모델은 실제 산불 문제에 적용되어 효과적 대응방안 마련에 많은 도움이 될 것으로 예상된다.

수직벽화재의 수치 시뮬레이션 I. 수직벽 난류자연대류 (Numerical Simulation of Vertical Wall Fires I. Turbulent Natural Convection Along Vertical Wall)

  • 박외철;아노드 트루베
    • 한국화재소방학회논문지
    • /
    • 제22권3호
    • /
    • pp.181-187
    • /
    • 2008
  • 수직벽 화재의 연구에 사용할 전산유체역학 시뮬레이터를 검증하기 위해 수직벽 자연대류의 수치 시뮬레이션을 수행하였다. 높이 4m의 등온 수직벽에 형성된 난류 경계층에서의 속도 및 온도 분포의 계산치를 측정치와 비교하였다. 시뮬레이터에 포함된 매개변수의 기본 값을 그대로 적용한 경우, 경계층 유동이 층류로 나타남에 따라 난류 자연대류를 예측하는데 실패하였다. 매개변수의 조사를 통해 격자크기 $\Delta$x=5mm, ${\Delta}y={\Delta}z=10mm$와 대와동모사(large eddy simulation)의 스마고린스키 상수(Smagorinsky constant) $C_s$=0.1을 선정하였다. 난류혼합이 미흡하였지만, 벽면근처에서의 속도분포와 최대속도, 그리고 난류 경계층 내 온도분포가 실험과 잘 일치하였다.

단순 형상 해양플랜트 내의 수소의 분산 시뮬레이션 (Dispersion Simulation of Hydrogen in Simple-shaped Offshore Plant)

  • 석준;허재경;박종천
    • 한국해양공학회지
    • /
    • 제27권5호
    • /
    • pp.105-114
    • /
    • 2013
  • Lots of orders of special vessels and offshore plants for developing the resources in deepwater have been increased in recent. Because the most of accidents on those structures are caused by fire and explosion, many researchers have been investigated quantitatively to predict the cause and effect of fire and explosion based on both experiments and numerical simulations. The first step of the evaluation procedures leading to fire and explosion is to predict the dispersion of flammable or toxic material, in which the released material mixes with surrounding air and be diluted. In particular turbulent mixing, but density differences due to molecular weight or temperature as well as diffusion will contribute to the mixing. In the present paper, the numerical simulation of hydrogen dispersion inside a simple-shaped offshore structure was performed using a commercial CFD program, ANSYS-CFX. The simulated results for concentration of released hydrogen are compared to those of experiment and other simulation in Jordan et al.(2007). As a result, it is seen that the present simulation results are closer to the experiments than other simulation ones. Also it seems that the hydrogen dispersion is closely related to turbulent mixing and the selection of the turbulence model properly is significantly of importance to the reproduction of dispersion phenomena.

반도체 제조공정의 연기유동에 관한 연구 (A Study on Fire Hazard Analysis and Smoke Flowing for the Semiconductor Manufacturing Process)

  • 한수진;강경식
    • 대한안전경영과학회지
    • /
    • 제9권1호
    • /
    • pp.197-211
    • /
    • 2007
  • The power of semiconductor, Korea is continuously constructing semiconductor production line for keeping a front-runner status. however, studies and data about potential risks in semiconductor factory are still short. If fire does not initially suppressed, the fire causes a great damage. To decrease fire risk factors, in addition to fire fighting safety equipment, more important thing is how to design and construct fire protection system. The current fire protection codes about semiconductor factory come under functional law, and this law is short of consideration about particularity of factory. The existing prescriptive fire codes depending on experience compose without evident engineering verifications, thus equipments which is created by the current prescriptive fire code may bring about a variety of problems. For example, the design under the current regulation can not cope with the excessive investments, low efficiencies, and the diversifying construction designs and be applied to the quick changes of new technologies. Ergo, an optimal design for fire protection is to equip fire protection arrangements with condition and environment of production field. Manufacturing factory of semiconductors is a windowless airtight space. And for cleanliness, there exists strong flow of cooperation. Therefore, there is a need for fire safety design that meets the characteristic of a clean room. Accordingly, we are to derive smoke flow according to cooperation process within a clean room and construction plan of an optimal sensor system. In this study, in order to confirm the performance of proposed smoke-exhaust equipment and suggest efficient smoke exhaust device when there is a fire of 1MW of methane in the clean room of company H, we have implemented fire simulation using fluid dynamics computation.

성능위주설계를 위한 가연물의 열발생률 및 화재성장률 측정 - 판매시설의 플라스틱 화재를 중심으로 - (Measurements of the Heat Release Rate and Fire Growth Rate of Combustibles for the Performance-Based Design - Focusing on the Plastic Fire of Commercial Building)

  • 장효연;남동군
    • 한국화재소방학회논문지
    • /
    • 제32권6호
    • /
    • pp.55-62
    • /
    • 2018
  • 국내 성능위주소방설계(PBD)에 신뢰성이 향상된 예측결과를 기여하고자 판매시설 가연물 중 플라스틱으로만 이루어진 제품을 대상으로 실규모 화재실험이 수행되었다. 이때 판매시설의 경우 다양한 가연성 물질이 진열된 판매대의 간섭 또는 상품 적재 등으로 인한 화재확산의 검토를 위하여 단일 및 다수가연물로 분리되어 실험조건이 선정되었다. 이에 따라 최대 열 발생률에 따른 가연물의 노출 면적 및 중량은 대략 93%와 89%의 매우 선형적인 관계를 확인할 수 있다. 또한 다양한 가연물에 대한 가스농도의 분석 결과 이산화탄소($CO_2$)는 최대 열 발생률에 대하여 선형적인 관계를 나타내는 반면 일산화탄소(CO)는 지수함수의 형태를 나타낸다. 이러한 결과는 판매시설에서 발생되는 플라스틱 화재의 PBD에 신뢰성있는 화원정보로서 적용될 수 있다. 추후 실제 판매시설에서 적용되는 진열대의 면적이 적용된 추가적인 실험을 통하여 판매시설의 플라스틱 화재에 대표되는 화원 정보로서 적용할 수 있을 것이라 기대된다.

환기부족 구획화재에 대한 FDS 해석 및 검증 (FDS Simulation and Validation on the Under-Ventilated Compartment Fires)

  • 고권현;김성찬;;유홍선
    • 한국화재소방학회논문지
    • /
    • 제23권5호
    • /
    • pp.103-109
    • /
    • 2009
  • 본 연구에서는 환기부족 조건의 구획화재에 대하여 FDS(Ver. 5.2)를 이용하여 수치해석을 수행하였고 열적 특성 및 연소 가스 생성 특성에 대한 예측성능을 평가하였다. ISO-9705 표준화재실의 2/5 크기 모형에 대한 메탄 및 헵탄, 톨루엔 화재를 모사하였으며 고온 상층부의 온도, 연소가스 농도 등에 대하여 기존의 실험 결과와 비교하였다. 실험결과와의 비교를 통해 FDS가 천정의 온도와 과환기 조건의 혼합분율의 예측에 있어서 좋은 성능을 보임을 확인할 수 있었다. 그러나 화재 크기에 비해 산소의 유입량이 충분치 않은 환기부족 조건에서는 일산화탄소 및 그을름의 발생량을 실험값에 비해 크게 하향 예측하였다.

공동주택 화재 시 화재크기 및 실내 개구부 크기가 화재풍속에 미치는 영향에 관한 수치해석적 연구 (Numerical Study on the Effect of Heat Release Rate and Interior Opening on Fire Flow Velocity in the Case of Interior Fire in an Apartment Building)

  • 서찬원;신원규
    • 한국화재소방학회논문지
    • /
    • 제28권5호
    • /
    • pp.37-43
    • /
    • 2014
  • 재실자가 부속실로의 피난 시 부속실 송풍기가 작동하기 전단계에서는 실내화재로 인한 풍속이 발생하여 부속실 개방과 더불어 연소생성물이 부속실을 오염시켜 피난장애의 결과를 가져올 수 있다. 이로인한 화재크기 및 실내 개구부 크기가 화재풍속에 미치는 영향을 확인하기 수치해석 연구를 수행하였다. 수치해석에서는 화재크기 및 실내 개구부 크기를 달리하였고, 실제의 공동주택 형상과 치수를 반영하였다. 수치해석 결과, 화재크기별 실내의 개구부 크기에 따라서 중성대 높이가 변화하여 부속실로 흐르는 화재풍속 특성이 다르게 나타남을 확인할 후 있었다. 또한, 실내 중성대가 높은 곳에 형성된 경우에는 방화문 상 하부에서 화재풍속의 차이가 나타남을 확인할 수 있었다.