• Title/Summary/Keyword: fire control system

Search Result 731, Processing Time 0.024 seconds

A Study on the Development of Integrated Type Fire Alarm Control Panel for Ubiquitous Environment (유비쿼터스 환경을 위한 통합형 화재수신기 개발에 관한 연구)

  • Park, Se-Hwa
    • Fire Science and Engineering
    • /
    • v.24 no.1
    • /
    • pp.24-30
    • /
    • 2010
  • An integrated type fire alarm control panel which is for the purpose of the ubiquitous environment application is reported. For the ubiquitous environments, mainly three additional functions upon its inherent capabilities are implemented. That is, wireless technology with ZigBee capability is applied for the interface of ZigBee detectors. Camera images can be displayed in the fire alarm control panel in which images are transferred via ethernet. For the time synchronization of the distributed fire alarm control panel, GPS module is introduced and implemented in the system.

A Study on the Operation Method of Emergency Power System with Reserved Firefighting Power (RFP) (소방전원보존형 발전기(RFP)의 작동 방법에 관한 연구)

  • Lee, Won-Kang;Choi, Chung-Seog
    • Fire Science and Engineering
    • /
    • v.26 no.3
    • /
    • pp.29-34
    • /
    • 2012
  • The purpose of this study is to propose an effective operating method of a power generator used by the Emergency Power System in case of a simultaneous fire and of the limitations of the interlock system the power supply from the emergency power generator. On the Emergency Power System with Reserved Fire-fighting Power (RFP), in case of an overload, the collective control Emergency Power System signals the main circuit breaker to shut off the supply to the emergency load, leaving the supply to the firefighting load uninterrupted to the end. The sequential control Emergency Power System signals the firefighting power supply to shut off the fire stage of the emergency load and continues to monitor the power supply. If an overload happens again from increased firefighting load, the sequential control Emergency Power System sends a secondary signal to shut down the second stage of the emergency load.

A real scale test on performance of water spray systems in tunnel fire (터널화재시 물분무소화설비의 성능에 대한 실대시험)

  • Park, Kyung-Hwan;So, Soo-Hyun
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.12 no.4
    • /
    • pp.341-347
    • /
    • 2010
  • The performance of water spray system installed to reduce risks of tunnel fire is investigated by a real tunnel fire test. In case of A class fire, Pool fire, and car fire, the nozzle of water spray has had a marvelous effect to reduce the temperature of hot smoke. And it is verified to have remarkable cooling effects when there is the air flow in a tunnel. Though this results, water spray system will be able to prevent a fire jump to decrease the air temperature in a tunnel and to protect tunnel facilities by the fire control.

A Study on the Development of a Duct-dedicated Intelligent Fire Detection System (덕트전용 지능형 화재감지시스템 개발에 관한 연구)

  • Kim, Si-Kuk;Lee, Gun-Ho;Lee, Chun-Ha;Lim, Woo-Sub
    • Fire Science and Engineering
    • /
    • v.29 no.4
    • /
    • pp.39-48
    • /
    • 2015
  • This research was done to develop a duct-dedicated intelligent fire detection system to prevent fires and minimize fire damage of the industrial duct having a high fire risk. To understand the fire hazards of the ducts, the analysis was centered on the Daegu Textile Industrial Complex, where industrial ducts are used frequently. With this in the background, dedicated fire detectors and fire alarm control panel, which can prevent fires and to minimize fire damages to the ducts, were designed and produced, after which the performance was confirmed. As a result of performance experiments, it was shown that a duct-dedicated intelligent fire detection system had excellent adaptability and temperature accuracy. Through real-time temperature monitoring of the inside of the ducts, it was confirmed that duct fires could be efficiently extinguished by stepwise control of linkage facilities according to the setting temperature.

Gun-oriented Engagement Simulation System (함포교전 시뮬레이션 시스템)

  • Lee, Dong-Hoon;Kim, Cheol-Ho;Kim, Tae-Su
    • Journal of the Korea Institute of Military Science and Technology
    • /
    • v.10 no.1
    • /
    • pp.78-85
    • /
    • 2007
  • A gun is still one of the major weapons of a combat ship. To assess the ship's fire control capability which is influenced by tracking system, fire control algorithm, gun, the ship itself, target behavior, environment and engagement situation, simulation system for gun-oriented engagement for surface ship is needed. This paper proposes the process for designing and implementing a gun-oriented engagement simulation system using DEVS(Discrete Event Simulation Specification), which is a formalism based on the set theory. It consists of the following activities : 1) analyzing the characteristics of a gun-oriented engagement, 2) constructing the deterministic model of the combat ship of study with DEVS, 3) modeling properties of each entity showing as stochastic errors. With this process, the gun-oriented engagement simulation system is developed and applied for the combat system under development.

A Study on the Effect of Inflammable Materials on the Control Characteristics of Thermal and Smoke Fluid of Water Curtain System (가연성 물질에 따른 워터커튼 시스템의 열 및 연기유동 제어특성에 관한 연구)

  • You, Woo-Jun;Nam, Jun-Seok;Kim, Dong-Joon;Lee, Jeong-Kyoon;Ryou, Hong-Sun
    • Fire Science and Engineering
    • /
    • v.26 no.2
    • /
    • pp.53-58
    • /
    • 2012
  • In this study fire control characteristics for inflammable materials of water curtain system are experimentally analyzed. Heat release rate for pinewood and gasoline was calculated using Room Corner Tester (RCT) and fire test apparatus for water curtain system is manufactured. Nozzles (180 degree of injection angle, 8.2 mm of orifice diameter) are installed at the nearby ceiling of place at 5 m distance from fire originate and temperature profile as well as transmission are obtained from the fire experiment of pinewood and gasoline in the water curtain system. Based on the results, parameters of engineering importance for fire control characteristics of water curtain system such as generation of high temperature smoke and thermal phenomena of fluid flow by injection nozzle are identified.

A Numerical Simulation of Smoke Control in Daegu Subway Stations II. Air Flowrate of Extraction System (대구 지하철역 제연의 문제점과 대책 II. 배기방식 제연설비의 풍량)

    • Fire Science and Engineering
    • /
    • v.17 no.4
    • /
    • pp.105-110
    • /
    • 2003
  • In Part II, the temperature and smoke particle distributions of the extraction system, which yielded the best smoke removal performance among the three smoke control systems in Part I, for extraction flowrates of 0.6∼2.4 ㎥/s and two fire sizes of 200 ㎾ and 2 ㎿ were presented. The same numerical method was utilized to the same computational domain and configurations as Part I. It was shown that the extraction flowrate affects the smoke control performance significantly, and that a similar trend in improving the smoke removal performance with the increasing extraction flowrate between the two fire sizes. An extraction flowrate of 2.4 ㎥/s or higher was required for the temperature in the escape route less than $^{\circ}C$ for the given situations.

Research on the Reliability Improvement of Automatic Fire Alarm System (자동화재탐지설비의 신뢰성 개선에 관한 연구)

  • Son, Young-Jin;Lee, Young-Il;Lee, Sang-Hyeon
    • Fire Science and Engineering
    • /
    • v.22 no.4
    • /
    • pp.42-49
    • /
    • 2008
  • This research is to provide a scheme for an automatic fire alarm system with higher reliability through solving problems of malfunctioning (false or missing fire alarm) and power interruption (result from frequently unwanted activation, etc) of an automatic fire alarm system. A digital control system with microprocessor-based is proposed to reduce the possibility of malfunctioning through a combinational use of heat, smoke and CO sensors. Higher reliability could be achieved by these multiple sensors based fire detection system and fire distinction algorithm. In this research, we implemented actual fire detection system and conducted fire test to verify improvement on reliability.

Fire Simulations for the Abandonment Risk Assessment of Main Control Room Fire in Domestic Nuclear Power Plant (국내 원자력발전소의 주제어실 화재 피난 리스크 평가를 위한 화재 시뮬레이션)

  • Kang, Dae Il;Kim, Kilyoo;Jang, Seung-Cheol;Yoo, Seong Yeon
    • Journal of the Korean Society of Safety
    • /
    • v.29 no.4
    • /
    • pp.199-207
    • /
    • 2014
  • In this paper, to systematically assess the abandonment risk of main control room (MCR) fire, fire simulations with Fire Dynamics Simulator were performed and abandonment probabilities were estimated for the MCR bench-board fire of domestic reference nuclear power plant. The fire simulation scenarios performed in this study included propagating and non-propagating fires of the MCR bench-board, and the availability and unavailability of heating, ventilation, and air conditioning system (HVACS). The following results were obtained. First, temperature was the major abandonment impact factor for the MCR bench-board fire if the HVACS was available and optical density was that if the HVACS was unavailable. Second, the fire scenario contributing the MCR bench-board fire abandonment risk was identified to be only the propagating fire. Third, it was confirmed that the abandonment probability of the MCR bench-board fire for domestic reference nuclear power plant could be reduced by using the fire modeling.

Application of developed DCS to test furnace (국산 개발 DCS의 시험 연소로 적용)

  • 김은기;변승현;이찬주
    • 제어로봇시스템학회:학술대회논문집
    • /
    • 1997.10a
    • /
    • pp.840-843
    • /
    • 1997
  • We applied a DCS which was developed in Korea to test furnace. Test furnace is a pilot-scale plant made for finding combustion in firing coal. In this paper, we describe control system which was implemented in test furnace in detail. Finally, we describe the fire box temperature control loop, and show fire box temperature control result during commissioning stage using implemented control system.