• 제목/요약/키워드: fault current limiter

검색결과 563건 처리시간 0.025초

이중퀜치를 이용한 삼상변압기형 초전도한류기의 삼상지락 고장 종류에 따른 고장전류 제한 특성 분석 (Analysis on Fault Current Limiting Characteristics of Three-Phase Transformer Type SFCL using Double Quench According to Three-Phase Ground-Fault Types)

  • 이신원;한태희;임성훈
    • 한국전기전자재료학회논문지
    • /
    • 제36권6호
    • /
    • pp.614-619
    • /
    • 2023
  • The fault current limiting characteristics of three-phase transformer type superconducting fault current limiter (SFCL), which consisted of three-phase primary and secondary windings wound on E-I iron core, one high-TC superconducting (HTSC) element connected with the secondary winding of one phase and another HTSC element connected in parallel with other two secondary windings of two phases, were analyzed. Unlike other three-phase transformer type SFCLs with three HTSC elements, three-phase transformer type SFCL using double quench has the merit to perform fault current limiting operation for three-phase ground faults with two HTSC elements. To verify its proper three-phase ground fault current limiting operation, three-phase ground faults such as single-line ground, double-line ground and triple-line ground faults were generated in three-phase simulated power system installed with three-phase transformer type SFCL using double quench. From analysis of its fault current limiting characteristics based on tested results, three-phase transformer type SFCL using double quench was shown to be effectively operated for all three-phase ground faults.

삼상 분리형 자속구속형 전류제한기의 동작 특성 분석 (Analysis of Operational Characteristics of Separated Three-Phase Flux-Lock SFCL)

  • 두승규;두호익;박충렬;김민주;김용진;한병성
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2008년도 하계학술대회 논문집 Vol.9
    • /
    • pp.289-289
    • /
    • 2008
  • We investigated the operational characteristics of the separated three-phase flux-lock type superconducting fault current limiter (SFCL). The single-phase lock type SFCL consist of two coils, which are wound in parallel through an iron core. The high-$T_c$ superconducting(HSTC) thin film connected in series with secondary coil. The separated three-phase flux-lock type SFCL consist of three single-phase flux-lock type SFCL. In a normal condition, the SFCL is not operate. When a fault occurs, the current of a HSTC thin film exceeds its critical current by fault current, the resistance of the HSTC thin film generated. Therefore fault current was limited by SFCL. The separated three-phase flux-lock type SFCL are operated in fault condition such as the the single line-to-ground fault, the double line-to-ground fault and the triple line-to-ground fault. The experimental results, the SFCL operational characteristics was dependent on fault condition.

  • PDF

배전변전소에 대용량변압기로 교체 적용시 보호협조를 위한 초전도 전류제한기의 임피던스 분석 (Analysis on SFCL's Impedance for Protective Coordination in Large Transformer installed in Distribution Substation)

  • 김진석;김명후;류일경;문종필;임성훈;김재철;안재민
    • 전기학회논문지
    • /
    • 제58권8호
    • /
    • pp.1479-1484
    • /
    • 2009
  • The introduction of the large transformer due to the large power demand has increased the fault current in power distribution system. The increased fault current can exceed the cut-off ratings of the circuit breaker. As the methods to solve this problem, the superconducting fault current limiter(SFCL) has been notified. However, the limited fault current by SFCL affects the operational characteristics of the protective device such as overcurrent relay. Therefore, the selection of the proper impedance for the SFCL is required to keep overcurrent relay's protective coordination with the SFCL when a large transformer is introduced into the distribution system. In this paper, the SFCL's impedance for protective coordination was investigates in that a large transformer is introduced.

Monte Carlo Simulation을 이용한 초전도 한류기 EMTDC 모델의 파라메터 최적 설계 (Optimal Design of HTS Fault Current Limiter using Monte Carlo Simulation Method)

  • 윤재영;김종율;이승렬
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제53권3호
    • /
    • pp.135-139
    • /
    • 2004
  • Nowadays, one of the serious problems in KEPCO system is large fault current which exceeds the SCC(Short Circuit Capacity) of circuit breaker, As the superconductivity technology has been developed, the HTS-FCL(High Temperature Superconductor-Fault Current Limiter) can be one of the attractive alternatives to solve the fault current problem. However, the parameters of HTS-FCL should be designed optimally to have a best performance. Under this background, this paper presents the optimal design method of parameters for resistive type HTS-FCL using stochastic analysis technique.

두 개의 자속경로를 갖는 직렬연결형 초전도한류기의 이중 피크전류제한 특성 (Double Peak Current Limiting Properties of Series Connection-Type SFCL with Two Magnetic Paths)

  • 고석철;한태희;임성훈
    • 조명전기설비학회논문지
    • /
    • 제28권7호
    • /
    • pp.62-68
    • /
    • 2014
  • We proposed a series connection-type superconducting fault current limiter(SFCL) using E-I core that can prevent the internal magnetic flux generation of cores during normal operation, and prevent the saturation of cores due to a sudden magnetic flux generation at the initial stage of fault occurrence while limiting the peak current. Through a short-circuit simulation experiment, we analyzed the operating status of the two superconducting elements and limiting characteristics according to the size of the fault current peak before and after the failure. Further, the double peak current limiting characteristics according to the winding directions as well as the current and the voltage of each coil were compared and analyzed.

YBCO 박막을 이용한 배전급 저항형 초전도 한류기 (Resistive Superconducting Fault Current Limiters for Distribution systems using YBCO thin films)

  • 이방욱;박권배;강종성;김호민;오일성;심정욱;현옥배
    • Progress in Superconductivity
    • /
    • 제7권2호
    • /
    • pp.114-119
    • /
    • 2006
  • High critical current density, high n value, multiple faults endurances, and fast recovery characteristics of YBCO thin films are very attractive characteristics for developing resistive type superconducting fault current limiters. But due to the limited current and voltage ratings of one YBCO module, it is needed to construct series and parallel module connections for high capacity electric networks. Especially for distribution network, more than 30 units should be connected in series to meet voltage level. So in order to construct distribution-level superconducting fault current limiter, simultaneous quench in one YBCO thin films should be realized, and furthermore, quench should be occurred in all fault current limiting units equally to avoid local heating and failures. In this paper, we proposed optimum design of YBCO thin films for fault current limiting module and technical method using shunt resistor to achieve simultaneous quench between multi current limiting units. From the analytical and the experimental results, optimal current path and thickness of shunt material was determined for YBCO thin films and shunt resistor between modules was developed. Finally, 14 kV one phase resistive fault current limiter using multi YBCO thin films was constructed and it was possible to get satisfactory test results.

  • PDF

초전도 한류기의 실계통 적용 시의 한류 특성 해석 (Performance of Superconducting Fault Current Limiter for Real Substation)

  • 김홍규;이병윤;박경엽
    • 한국초전도저온공학회:학술대회논문집
    • /
    • 한국초전도저온공학회 2003년도 추계학술대회 논문집
    • /
    • pp.201-204
    • /
    • 2003
  • This paper presents the analysis of current limiting performance of superconducting fault current limiter(SCFCL) for real substation. The resistive and inductive type SCFCLs are investigated for 154㎸ substation. The current limiting performance of SCFCL is evaluated with respect to the time constant of SCFCL and impedance of SCFCL.

  • PDF

YBCO film을 이용한 저항형 초전도 한류기의 전류제한 특성 (Current limiting characteristics of the resistive SFCL using YBCO film)

  • 최효삼;김혜림;황시돌;현옥배;김상준
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 하계학술대회 논문집 A
    • /
    • pp.277-280
    • /
    • 1999
  • We fabricated a resistive superconducting fault current limiter of two stripe meander type based on a YBCO film, and performed current limitation experiments. In order to disperse the heat generated at hot spots in the YBCO film the film was coated with a gold shunt layer. At $0^{\circ}$ fault angle the minimum quench current was $9.6 A_{peak}$(meander line cross section: $5{\times}10^{-6}cm^2$) and the fast quench time was 0.63 msec. The resistance of the limiter continued to increase for three cycles due to heat generation in the gold layer and was stabilized afterwards. At $45^{\circ}$ and $90^{\circ}$ the fast quench time were 0.56 msec and 0.26 msec, respectively. The quench time is believed to be reduced because faults occurred when the current was increasing or was at the peak value. With the limiter we could effectively limit the fault current about 1/5 times right after the fault and about 1/8.5 times three cycles after.

  • PDF

션트리액터가 초전도 한류기의 퀜치에 미치는 효과 (Effects of Shunt Reactors on Quench Performance of the Superconducting Fault Current limiter)

  • 이나영;남긍현;박형민;조용선;최효상;황종선;한병성
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2005년도 하계학술대회 논문집 Vol.6
    • /
    • pp.296-297
    • /
    • 2005
  • We have investigated the quench performance of shunt reactors in the parallel connection of resistive type superconducting fault current limiter (SFCL) components based on YBCO films. To increase voltage rating, components are connected in series and to increase current level, they are connected in parallel. This method has cauesd the unbalanced quench between each components. To improve the problem, we have compared the quench properties between the current limiting components without and with shunt reactors connected in parallel. To improve the quench performance, across individual SFCL components connected the shunt reactor in parallel. The components with shunt reactors successfully produced simultaneous quench, resulting from the bypass of the fault current in the direction of the shunt reactor.

  • PDF