단거리송전선에서 투입저항이 없는 차단기적용에 관한 연구 (The Study on Application of Circuit Breaker without Closing Resistor in Short Transmission Line)

  • 김정배;정영환;송원표
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제53권1호
    • /
    • pp.31-37
    • /
    • 2004
  • In this paper, the analysis result of the switching surge in substation including GIS(Gas Insulated Switchgear) has been described using the EMTP(Electro Magnetic Transient Program) program. After performing the modeling of the input data, we have reviewed the energization overvoltages of GCB(Gas Circuit Breaker) without closing resistor in 345kV network, according to the conditions of simultaneously operating switch and statistically operating switch. Firstly, it can be known that the energization overvoltage of single line is higher than that of parallel energized line. Secondly, the maximum energization overvoltage obtained in statistics switch is higher than one in simultaneous switch. From these results, it can be known that the phase-to-earth energization overvoltages of $\alpha$-$\beta$ section are less than 2.2 p.u when closing resistor is eliminated. Therefore, it is possible to consider the circuit breaker eliminated the closing resistor in $\alpha$-$\beta$ section.

PSCAD/EMTDC를 이용한 시송전계통의 고조파 공진현상 분석 (Analysis of the Harmonic Resonance of Primary Restorative Transmission System Using PSCAD/EMTDC)

  • 이흥재;조병관;이경섭;박성민;배주천;황봉환;이낭호;송인준
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 추계학술대회 논문집 전력기술부문
    • /
    • pp.31-33
    • /
    • 2003
  • Power system restoration following a partial or complete blackout starts with energizing of primary transmission lines. Because system changed rapidly during early restoration process, transformer energization and load pickup is executed to maintain the power system stability. However unexpected problem such as harmonic overvoltage may be arisen during energizing transformer. The reason of harmonic overvoltage is known as transformer saturation and magnetizing in-rush current and so on, but it is difficult to estimate the condition of occurrence. This paper describes the analysis of the harmonic overvoltage while unloaded transformer is energized using PSCAD/EMTDC.

  • PDF

PSCADI/EMTDC를 이용한 시송전계통의 고조파 공진현상 분석 II (Analysis of the Harmonic Resonance of Primary Restorative Transmission System Using PSCAD/EMTDC PART II)

  • 이흥재;유원근;이경섭;박성민
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 하계학술대회 논문집 A
    • /
    • pp.48-50
    • /
    • 2004
  • The energization of high voltage transmission lines and transformers, that is an inevitable process in most countries as the first restorative action for wide-area blackout, may induce overvoltages such as sustained overvoltage, transient overvoltage and harmonic resonant overvoltage. And these may cause damages to power system equipments or failure of surge arresters. The harmonic resonant overvoltage originates in switching operations and nonlinear characteristics of equipments. Actually it is difficult to predict the occurrence of harmonic overvoltage, since they result from nonlinear characteristics of transformers and other equipments. This paper describes the analysis of domestic primary restorative transmission system using PSCAD/EMTDC. The harmonic resonance is verified and the solution to prevent harmonic resonance is proposed in this paper. As a result, the PSCAD/EMTBC simulation showed slightly conflictive results that had been presented by IEEE Power System Restoration Working Group report.

  • PDF

765kV 선로 편단가압 시 전압상승 분석 (Overvoltage Analysis for One Side Energization of 765kV Line)

  • 서훈철;여상민;김철환;유영식;조범섭
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2007년도 제38회 하계학술대회
    • /
    • pp.608-609
    • /
    • 2007
  • 본 논문에서는 765kV 선로의 편단가압 시 기존 운전중인 선로에서의 전압상승에 대하여 분석하였다. EMTP-RV를 이용하여 당진T/P$\sim$신서산S/S$\sim$신안성S/S의 실계통 모델을 구현하여, 선로길이 및 전원용량을 변경시키면서 시뮬레이션 하였으며 그 결과를 분석하였다.