• Title/Summary/Keyword: effective surge impedance

Search Result 14, Processing Time 0.026 seconds

The Installation Technique of Grounding Electrode Conductors for Metal Oxide Distribution Surge Arresters (배전용 피뢰기의 접지도선 설치기법)

  • Lee, B.H.;You, I.S.;Lee, T.R.;Ahn, C.H.;Youn, J.S.;Youn, H.H.;Kim, J.S.;Kim, J.C.
    • Proceedings of the KIEE Conference
    • /
    • 2001.07c
    • /
    • pp.1718-1720
    • /
    • 2001
  • The route of surge arrester connection is very important because bends and kinds of leads increase the impedance to lightning surges and tend to nullify the effectiveness of a grounding electrode conductor. There is a need to know how effective installation of lightning surge arresters is made in order to control voltage and to absorb energy at high lightning currents. The effectiveness of a grounding conductor and bonding for 18[kV] metal oxide distribution line arresters was experimentally investigated with lightning and oscillating impulse voltages.

  • PDF

High Frequency Impedance Calculation of Grounding Meshes Installed at Power Substations (전력용 변전소에 설치된 메쉬 접지망의 고주파 임피던스 계산)

  • Han, Poong;Choi, Chang-Hyek
    • Proceedings of the KIEE Conference
    • /
    • 1998.07e
    • /
    • pp.1578-1582
    • /
    • 1998
  • The ground potential rise generated by the switching surge or lightning stroke may be dangerous to personnel and cause damage to electronic control parts. For a first step to the transient performance analysis. high frequency impedances of grounding grids have been calculated and discussed. Grounding grids include 7 square grids from $10m{\times}10m$ to $80m{\times}80m$. The high frequency current was injected into the center and a corner of the grounding grid. The calculation results indicate that the impedance of the grounding grid is significantly influenced by frequency and the point of injection of the current. and the effective radius of a large grounding grid may be represented in $15{\sim}20m$.

  • PDF

Transient Impedance Characteristics of Grounding Rods (봉상접지극의 과도임피던스 특성)

  • 김일권;송재용;길경석;권장우
    • Journal of the Korea Institute of Information and Communication Engineering
    • /
    • v.5 no.1
    • /
    • pp.133-143
    • /
    • 2001
  • This paper describes the correlation of the transient impedance and its parameters with the stationary resistance of a grounding system to a square pulse current and a lightning impulse current. In the experiment, the grounding system consists of a single grounding rod$(\Psi10[mm], 1[m])$and/or a triple-grounding rods of equilateral triangles with 5[m] spacing for operation. To analyze the transient impedance characteristics of the grounding system, a pulse generator which can produce square wave of a 30[ns] rise-time and a $20[\mus] $pulse duration is designed and fabricated. The injected content in the grounding system and the developed potential were recorded, and the time variation of the transient impedance were calculated as the ratio of the potential rising to the injected current at each time. The transient impedance and the effective surge impedance Z3 which defines economic protection level in power system were quite higher than the stationary resistance. The grounding impedance is decreased by the application of the triple-rods grounding system, and its effect is decreased as the frequency of the current is increased due to the inductance of the grounding leads.

  • PDF

Frequency-Dependant Grounding Impedances According to the Length of Grounding Electrode and the Joint Position of Ground Conductors (접지전극의 길이 및 접지도선의 접속위치에 따른 접지임피던스의 주파수의존성)

  • Choi, Jong-Hyuk;Choi, Young-Chul;Cho, Sung-Chul;Lee, Bok-Hee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.24 no.5
    • /
    • pp.37-43
    • /
    • 2010
  • When lightning surges with wide frequency spectrum and power converting devices are considered, it is desirable to evaluate grounding system performance by grounding impedances. This paper presents the measured results for frequency-dependent grounding impedance for the vertical grounding electrode and counterpoise on a scale of full size. Grounding impedances of vertical grounding electrodes and counterpoises give capacitive or inductive behaviors according to the length of grounding electrodes and soil resistivity. It is inefficient to extend the length of the grounding electrode in order to decrease the ground resistance, and when designing the grounding system, the consideration of the grounding impedance should be desirable. In order to reduce the grounding impedance of counterpoise, the grounding conductors are jointed at the center of counterpoises. It is effective to reduce the grounding impedance by connecting ground rods to counterpoises in parallel.