• 제목/요약/키워드: arrester

검색결과 303건 처리시간 0.025초

AC 전철변전소의 피뢰기카운터 과동작에 관한 연구 (A Study of LA Counter Over-activation in AC Electric railway Substation)

  • 천희승;장우진
    • 한국철도학회:학술대회논문집
    • /
    • 한국철도학회 2008년도 추계학술대회 논문집
    • /
    • pp.132-139
    • /
    • 2008
  • In an electric railway feeding system, transient over-voltage often appears due to the feeder's direct lightning and induced lightning, while switching over-voltage also frequently occurs during operation of electric feeding in substation facilities. Such over-voltage is several times larger than the regular power, and accordingly leads to the dieletric breakdown of eletric power products such as invasion transformers and circuit breakers. Arresters are installed to protect these machines, while arrester counters are installed to observe the arrester's activation. This thesis aims to explore the status of an arrester counter that is being activated several thousand times, determine whether the arrester has actually been activated in relation to the counter, and investigate the over-heatedness and risks of the arrester.

  • PDF

Optimal Design of a Follow Current Disconnector for DC Arresters in Traction Vehicles

  • Wang, Guoming;Kim, Sun-Jae;Park, Seo-Jun;Kil, Gyung-Suk;Ji, Hong-Keun
    • Transactions on Electrical and Electronic Materials
    • /
    • 제17권5호
    • /
    • pp.289-292
    • /
    • 2016
  • This paper dealt with the optimal design of a follow current disconnector for DC arresters used in electric traction vehicles. The disconnector separates the ground lead from an arrester to prevent a line-to-ground fault of an aged arrester and should not affect the operation and function such as the reference and the clamping voltage of the connected arrester. The designed disconnector is composed of a resistor, a spark gap, and a cartridge. The results showed that the sparkover voltage increased with the gap distance whereas the reference voltage was almost the same as that without the disconnector. The sparkover voltage was 3.95 kV when the gap distance was 0.5 mm. Regardless of the gap distance, the reference and the clamping voltage of the assembled disconnector with an arrester were measured to be the same as those of the arrester alone.

피뢰기 누설전류 분석장치를 이용한 ZnO 피뢰기의 누설전류 변화 분석 (The Leakage Current Analysis of ZnO Arrester Using Leakage Current Dete)

  • 김영춘;문선호;오정환;김재철;이영길
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1998년도 하계학술대회 논문집 C
    • /
    • pp.1082-1084
    • /
    • 1998
  • In this paper, we developed a diagnosis device for ZnO arrester to detect on-line leakage current and acquire data from the power distribution system. The arrester is important power equipment used in power transmission and distribution systems to protect the generator and the main transformer from surge and overvoltage. First of all we developed a diagnosis device for ZnO arrester leakage current. And then we detect the total leakage current by the developed device without disconnecting the arrester ground wire and analysis the 3rd order harmonic by Fast Fourier Transform(FFT) to diagnose the ZnO arrester deterioration. With measuring the total current and the resistive current of power distribution system in operation, we analysis the trend of resistive current component in the total leakage current. We expect the result will be promote the method to protect electrical utility and customer from accident.

  • PDF

직류+60[Hz]교류 중첩전압에 대한 18[kV] ZnO 피뢰기의 전기적 특성 (Electrical Properties of 18[kV] ZnO Surge Arrester Stressed by the Mixed DC and 60[Hz] AC Voltages)

  • 이수봉;이승주;이복희
    • 조명전기설비학회논문지
    • /
    • 제21권10호
    • /
    • pp.66-72
    • /
    • 2007
  • 이 논문은 직류+60[Hz] 교류 중첩전압에서 신품과 노후된 18[kV] 산화아연 서지피뢰기의 누설전류와 전력손실에 대하여 기술하였다. 최대 50[kV]의 직류+60[Hz] 교류를 발생시킬 수 있는 중첩전압발생장치가 설계되고 제작되었다. 피뢰기의 I-V 특성곡선은 전압중첩률 K의 함수로 측정된다. DC와 AC 전압이 중첩된 I-V, R-V 특성곡선은 순수한 직류와 교류곡선 사이에 있고 저전류 영역에서 교차현상이 나타난다. 그 결과 중첩 전압에서 직류 성분의 증가는 ZnO 피뢰기의 전체 누설전류의 저항성분의 증가를 유발한다. 또한 같은 인가전압에서 피뢰기를 통해 흐르는 누설전류는 상용전원에서 장시간 스트레스 받은 피뢰기가 신품 피뢰기에 비해서 높게 나타났다.

산화아연 피뢰기 소자의 다중 뇌 임펄스 특성 (Effect of Multiple Lightning Impulse Currents on Zinc Oxide Arrester Blocks)

  • 이복희;강성만;박건영;최휘성
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 추계학술대회 논문집 전기물성,응용부문
    • /
    • pp.22-24
    • /
    • 2003
  • In this work, in order to investigate the effect of multiple lightning impulse currents on zinc oxide arrester blocks. We have been designed and fabricated a multi-impulse generator which can produce quintuple voltages with $1.2/50{\mu}s$ to 100kV and quintuple currents with $8/20{\mu}s$ to 12kA and we have evaluated the characteristics of zinc oxide arrester block using several electrical and physical methods after the multi-impulse test. It was found that the multi-impulse failures of ZnO arrester blocks were mainly caused by surface flashover and the multi-impulse currents test would be more suitable than single impulse current test in evaluation of the characteristics of zinc oxide arrester blocks corresponding to actual situations.

  • PDF

배전계통에서 낙뢰보호용 피뢰기의 접지저항 영향에 관한 연구 (A Study on the Grounding Resistance Effects of Lightning Arrester for Lightning Stroke Protection in Electric Distribution Systems)

  • 김경철;정지원;이규진
    • 조명전기설비학회논문지
    • /
    • 제24권6호
    • /
    • pp.107-114
    • /
    • 2010
  • 낙뢰는 구름이 가진 높은 전압이 대지로 방출되는 현상이다. 낙뢰 보호 접지는 낙뢰로부터 건물, 배전선로와 전기설비를 보호하는 중요한 역할을 한다. 기기 접지는 제한된 중성점 전위상승을 위한 목적으로 한다. 기기 접지는 제한된 중성점 전위상승을 위한 목적으로 한다. 본 논문에서는 낙뢰가 배전선로에 급습했을 때 중성점 전위와 피뢰기의 제한 전압을 분석하여 피뢰기 접지저항의 영향을 심도 있게 조사하였다. 사례연구는 EDSA 프로그램으로 수치와 그래프로 시뮬레이션하였다.

전차선로용 폴리머 피뢰기(42kV 10kA Class3)의 전기적 특성 및 누설전류 특성 평가 (Evaluation of Electrical and Leakage Current Characteristics of Polymer Arrester(42kV 10kA Class3) for Railroad Line)

  • 김석수;최익순;박춘현;조이곤;박태곤
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2004년도 하계학술대회 논문집 Vol.5 No.2
    • /
    • pp.1171-1174
    • /
    • 2004
  • Leakage current of the polymer arrester(42kV, 10kA, Class3) for railroad line applied actually field was observed and electrical characteristics of arrester before and after applied actually field were investigated. During applied actually field, leakage current of arresters were $610{\sim}647{\mu}A$ in AN SAN line and $500{\mu}A$ in YUNG DONG line. After applied actually field, electrical characteristics of arrester, such as insulation test, reference voltage test, leakage current test and partial discharge current test, wasn't variation as before applied actually field.

  • PDF

전력용 피뢰기의 열안정화 특성 (Study on Thermal Stability Characteristics of Surge Arrester for High Power)

  • 한세원;조한구
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2004년도 하계학술대회 논문집 Vol.5 No.2
    • /
    • pp.1142-1145
    • /
    • 2004
  • ZnO surge arresters continuously endure the operating voltages during the operation course, and in the mean time, which need to withstand occasionally transient voltages of lightning and switching overvoltages. Under these voltages, the ZnO varistors inside arresters would have aging phenomena, one important result of aging phenomena is the increasing of resistive currents of varistors, which leads to the increasing of power losses of varistors. And the operating voltage is continuously applied on the ZnO varistors, there is a degradation phenomenon existing in ZnO varistors. When the degradation reaches a certain degree, then the arrester must stop operation. The degradation is related to the applied voltage ratio, the applied voltage ratio is high, the degradation is quickly. When the power loss is higher than the thermal dispersion ability of house of arrester, then the arrester will thermally breakdown. In this study the thermal stability characteristics of surge arresters for high power wil be discussed on the view point of watt losses and thermal breakdown.

  • PDF

직류전동차용 피뢰기 진단기술 (Diagnostic Techniques of Lightning Arresters for DC Electric Traction Vehicles)

  • 길경석;송재용;김일권;문승보;신광철
    • 한국철도학회논문집
    • /
    • 제9권4호
    • /
    • pp.357-361
    • /
    • 2006
  • This paper dealt with the performance evaluation and the diagnostic techniques of lightning arresters for DC electric traction vehicle. Field Measurements on the protective operation of lightning arresters against surge currents were carried out on running vehicles to acquire the data necessary for the diagnosis. The frequency and the magnitude of surge events were analyzed. Surge currents of $1\sim3$ times were recorded in one running service route and their magnitudes were ranges of $150A\sim2kA$. Also, an acceleration experiment on a lightning arrester by the standard lightning impulse current of 8/20 us and 5 kA was performed to know the aging characteristics. After the surge current application of 3,000 times, the reference voltage decreased by 4.5 %, and the leakage current was below 10 uA at the continuous operating voltage and about 50 uA at the rated voltage. From the experimental results, we propose a decision level of leakage current for the arrester used in this paper and designed an arrester tester which analyzes arrester condition by the magnitude of leakage current.

피뢰기 열화진단을 위한 저항분 누설전류의 측정장치 (Measurement Device of Resistive Leakage Current for Arrester Deterioration Diagnosis)

  • 길경석;한주섭;김정배
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제52권10호
    • /
    • pp.469-475
    • /
    • 2003
  • Resistive leakage current flowing ZnO blocks increases with its ages, which is an important indicator of arrester deterioration. However, a complicated circuitry is essential to measure the resistive leakage current included in the total leakage current, and the difficult handling of the measurement makes few applications to the fields. In this paper, we propose a resistive leakage current measurement device which is composed of a current detection circuit and an analysis program operated on a microprocessor. The device samples the input leakage current waveform digitally, and discriminate the zero-cross and the peak point of the waveform to analyze the current amplitude vs. phase. The capacitive leakage current is then eliminated from the total leakage current by using an algorithm to extract the resistive leakage current only. Also, the device can be operated automatically and manually to analyze the resistive leakage current even when the leakage current waveform is distorted due to various types of arrester deterioration. To estimate the performance of the device, we carried out a test on ZnO blocks and lightning arresters. From the results, it is confirmed that the device could analyze most parameters needed for the arrester diagnostics such as total leakage current. resistive leakage current, and the $3^rd$ harmonic leakage current.