• Title/Summary/Keyword: arrester

Search Result 303, Processing Time 0.023 seconds

Evaluation and Performance Test of Arresters for Electric Power Distribution (전력용 피뢰기의 성능확인시험과 평가 분석)

  • Kim, S.S.;Kim, K.U.;Cho, H.G.;Park, T.G.
    • Proceedings of the KIEE Conference
    • /
    • 1999.07e
    • /
    • pp.2329-2331
    • /
    • 1999
  • Metal oxide surge arrester were developed in the late 1970s, and were immediately adopted as significant breakthrough in over voltage protection of power system. Work was continued throughout the world on the design, development and application of metal oxide surge arrester. This paper describes the evaluating test and results of practical use for analyzing the performance of gapless metal oxide surge arresters under various type test.

  • PDF

Analysis of lightning surge on the 345kV Gas Insulated Substation (345kV GIS 변전소 뇌써지 해석)

  • Kim, Jae-Kwan;Lee, Jong-Beom;Cho, Han-Goo
    • Proceedings of the KIEE Conference
    • /
    • 2003.07a
    • /
    • pp.561-563
    • /
    • 2003
  • This paper deals with simulation of lightning overvoltage generated by back flashover entering 345[kV] Gas Insulated Substation. In order to protect the substation equipment against lightning surge, insulation coordination is performed with the lightning arrester. This paper suggests optimal location of lightning arrester using the EMTP/ATPDraw to mere economically and effectively reduce the lightning surge incoming overhead lines.

  • PDF

Effects of an Overhead Ground Wire and Surge Arrester in the Railway due to Lightning Strokes (전차선로에서의 뇌격에 의한 가공지선과 보안기의 차폐효과)

  • 임성정;김재철;창상훈;정용철
    • Proceedings of the KSR Conference
    • /
    • 2000.05a
    • /
    • pp.93-99
    • /
    • 2000
  • Using the EMTP(Electro Magnetic Transient Program) for the analysis of lightning direct voltage on the railway system, the shielding effects of overhead grounding wire on the railway were studied quantitatively. Installation of overhead ground wire and gap-type arrester such as s-horn Provides a 6.6㎸ HV distribution line with good protection effects. Even severe lightning induced voltage were create, 6.6㎸ HV lines can be withstand.

  • PDF

Study on Enhancing Lightning Protection Scheme of Catenary in Subway Viaduct Section

  • Li, Rui-Fang;Chen, Kui;Chen, Li-Sheng;Cao, Xiao-Bin;Wu, Guang-Ning;Zhang, Xue-Qin
    • Journal of Electrical Engineering and Technology
    • /
    • v.12 no.2
    • /
    • pp.950-958
    • /
    • 2017
  • Viaduct increases the height of subway catenary, namely magnifies lightning attraction scope that lead to higher possibility of suffering lightning stroke. Therefore, it is necessary to analyze performance of lightning striking to catenary of subway in viaduct section and propose an improving lightning protection scheme. In this paper, using ATP-EMTP simulation software to establish an associated model to evaluate lightning withstand level of catenary with existing lightning protection schemes including arrester and grounding point, an improving lightning protection scheme is proposed - every pillar ground earth and arresters are installed with some installing spacing between 200m to 400m based on lightning damage degree and reliability requirements - according to analyzing results: while lightning withstand level is lowest for lightning striking to the neutral pillar, lightning withstand level is greatest for lightning striking to the both-ends pillar that arrester and grounding point are both installed; grounding point could obviously improve lightning withstand level for lightning striking to ground wire while arrester could obviously improve the lightning withstand level for lightning striking to catenary; every pillar ground earth could enhance the lowest lightning withstanding level up to 2.5 times than of that pillar ground earth across every 200m.

Implementation of on Expert System to Supervise GIS Arrester Facilities (GIS 피뢰설비 관리를 위한 전문가 시스템 구현)

  • Kil, Gyung-Suk;Song, Jae-Yong;Kim, Il-Kwon;Moon, Seung-Bo;Kwon, Jang-Woo
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.21 no.1
    • /
    • pp.75-81
    • /
    • 2007
  • This paper dealt with the design and implementation of an expert system to monitor and diagnose the lightning arresters in GIS substations. The expert system consists of a data acquisition module(DAM) based on microprocessor and diagnostic algorithms. The DAM measures and analyzes several parameters necessary for the arrester diagnosis such as system voltages, leakage current components, and temperatures. Also, it includes an intelligent surge counter which can record the date and tin, the polarity, and the amplitude of surge currents. All the data acquired is transmitted to a remote computer by a low rate wireless network specified in IEEE 802.15.4 to avoid electromagnetic intereference under high voltage and large current environments. The decision-making for the arrester diagnosis completes with a Java Expert System Shell(JESS) which is composed of a knowledge base, an inference engine and a graphic user interface(GUI).

A Study of Lightning Impulse Operating Duty and Temperature Dependence of Series Gap Type Arrester (Series Gap Type 피뢰기의 뇌임펄스 동작책무 및 온도의존성에 관한 연구)

  • Cho, Han-Goo;Yoo, Dae-Hoon
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.22 no.8
    • /
    • pp.659-664
    • /
    • 2009
  • This paper describes lightning impulse operating duty performance and temperature dependence of series gap type for transmission line arresters. The ageing parameters of lightning arresters are impulse current, moisture ingress, temperature ageing and so on. Especially it is important to estimate the change of electrical characteristics by lightning impulse current. In the discharge withstand test, total energy applied to the ZnO arrester each time is 4/10 ${\mu}s$, 30 kA. and in the operating duty test, the arrester has passed the test if thermal stability is achieved, if the residual voltage measured before and after the test is not changed by more than 5 %, and after the test reveals no evidence of puncture, flashover or cracking of the ZnO block. As a results, the residual voltage was in the range of 17.2${\sim}$20.3 kV and ZnO block bear up against at 2 shot of series impulse current of 30 kA. Also it was so excellent that the mechanical destruction does not occur at the 2 groups of 5 impulses current of 2/20 ${\mu}s$ 10 kA. According to the tests, it is thought that the ZnO arrester shows good stability with impulse current test. and it was found that the ambient temperature is increased resistive leakage current was increased in the range 47.3${\sim}$167.4 ${\mu}A$.

Seismic Fragility Analysis of Lightning Arrester using Capacity Spectrum Method (역량스펙트럼 방법을 이용한 피뢰기의 지진취약도 해석)

  • Kim, Gwang-Jeon;Song, Jong-Keol
    • Journal of the Computational Structural Engineering Institute of Korea
    • /
    • v.27 no.4
    • /
    • pp.255-263
    • /
    • 2014
  • In this paper, seismic fragility analysis of lightning arrester is performed using capacity spectrum method(CSM). Since seismic fragility analysis of structure with many structural members is required to calculate many inelastic responses for several tens or hundreds of ground motions, simple method such as CSM is more appropriate than response history analysis(RHA). In general, accuracy of seismic response evaluated by CSM is less than that by RHA. In order to increase accuracy of CSM, equivalent SDOF method and performance point calculation technique are applied to CSM. Seismic fragility method proposed by Shinozuka et al. is used. In order to evaluate site effect of ground motions on seismic fragility, 60 different site classification earthquakes are selected as input ground motions. From the seismic fragility curves of lightning arrester evaluated by CSM and RHA, it can be observed that the seismic fragility curves evaluated by CSM are very similar to those by RHA. Also, it can be observed that main seismic failure mode of lightning arrest is bushing breakage.

New Diagnostic Technique and Device for Lightning Arresters by Analyzing the Wave Height Distribution of Leakage Currents (누설전류의 파고분포 분석에 의한 새로운 피뢰기 진단기술 및 장치)

  • 길경석;한주섭;송재영;조한구;한문섭
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.52 no.12
    • /
    • pp.562-567
    • /
    • 2003
  • Lightning arresters are deteriorated by repetition of protective operation against overvoltages or impulse currents in environments of its use. If a deteriorated arrester is left in power lines, it can lead to an accident such as a line to ground fault even in a normal system. Therefore, it is necessary to eliminate the deteriorated arrester in advance by checking the soundness of arresters on a regular basis, and to ensure the reliability of power systems by preventing accidents. Various deterioration diagnostic techniques and devices are suggested, and most of which measure leakage current components as an indicator of arrester ageing. However, the techniques based on the magnitude of leakage current measure simply RMS or peak value of leakage current components and do not provide detailed information needed in the diagnosis. In this study, we found that the wave height distributions of the total leakage currents are remarkably changed or a new wave height are produced with the progress of arrester deterioration. To propose a new technique for the diagnosis, we designed a leakage current detection unit and an analysis program which can measure leakage current magnitudes and analyze wave height distributions. From the experimental results, we confirmed that the proposed technique by analyzing the wave height distribution can simply diagnose the mode of defects such as a partial damage and an existence of punctures in arresters as well as deterioration of arresters.