• Title/Summary/Keyword: ZnO arrester

Search Result 100, Processing Time 0.021 seconds

A Measurement and Diagnosis for Resistive Leakage Current of ZnO Arrester Element (ZnO 피뢰기 소자의 저항분 누설전류 측정 및 분석)

  • Lee, Bok-Hee;Kang, Sung-Man;Park, Jin-Woo
    • Proceedings of the KIEE Conference
    • /
    • 1999.07e
    • /
    • pp.2155-2157
    • /
    • 1999
  • This paper describes a new measurement method of resistive current and the technique of deterioration diagnosis for ZnO element. The consequence of current increasing (resistive current) with time is the eventual attainment of a state of thermal instability that may lead to arrester failure. So, it is very important to measure a leakage current of ZnO arrester installed at on-state. For the high-precision and more reliability, an iron core, which has a very high relative permeability, was used for increasing detection sensitivity, and we also used the personal computer for the data storage and program and analysis. And we have verified the reliability and performance of the sensing device through several laboratory tests.

  • PDF

Characteristics of the luminous events caused between the ZnO block and electrode (ZnO 소자와 전극의 접촉점에서 발생하는 방전광 특성)

  • Lee, B.H.;Pak, K.Y.;Kang, S.M.
    • Proceedings of the KIEE Conference
    • /
    • 2004.11a
    • /
    • pp.26-28
    • /
    • 2004
  • The primary role of ZnO arresters is to protect transmission and distribution equipments against lightning surges. The extremely nonlinear V-I characteristics of the ZnO arrester obviates the need for isolation gaps and consequently it is continuously connected to line voltage. For this reason, ZnO arresters are degraded with time in actual power systems. In this work, the characteristics of the luminous events caused between the ZnO block and electrodes according to the electrode area were investigated. As a result, the luminous events were effected by electrode area and the longer electrode areas were increased, the more luminous events were decreased. Also the reduction of luminous events was fumed up to the degraded ZnO arrester block.

  • PDF

Characteristics of ZnO Arrester Blocks Leakage Currents under Mixed Direct and 60 Hz Alternating Voltages (직류와 60 Hz 교류가 중첩된 전압에 대한 산화아연 피뢰기 소자의 누설전류 특성)

  • Lee Bok-Hee;Kang Sung-Man;Pak Keon-Young
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.54 no.1
    • /
    • pp.23-29
    • /
    • 2005
  • This paper presents the characteristics of leakage currents flowing through ZinC Oxide(ZnO) surge arrester blocks under mixed direct and 60 Hz alternating voltages. A mixed voltage, in which an alternating voltage is superimposed upon a direct voltage, appears on the HVDC system network. The mixed direct and alternating voltage generator with a peak open-circuit of 10 kV was designed and fabricated. The leakage currents and V-I curves for the fine and used ZnO surge arrester blocks were measured as a function of the voltage ratio k, where the voltage ratio k is defined as the ratio of the peak of alternating voltage to the peak of the mixed voltages. The resistive component in the leakage current in the low conduction region is significantly increased with increasing the voltage ratio k. The V-I characteristic curves for the mixed voltages lies between the direct and alternating characteristics, and the cross-over phenomenon in the high conduction region was appeared.

Electrical Characteristics of ZnO Varistor for Transmission Class Arrester (송전급 피뢰기용 ZnO 바리스터 소자의 전기적 특성)

  • Kim, Seok-Sou;Park, Choon-Hyun;Cho, I-Gon;Park, Tae-Gon
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2004.04b
    • /
    • pp.179-182
    • /
    • 2004
  • ZnO varistor for transmission class arrester$({\Phi}65{\times}20mm)$ of 10kA(Class 3) grade was recently developed in korea and is tested for the properties by switching surge operating duty test to know the line discharge class and complex surge property in electric properties. To find out changing rate of residual voltage before and after lightning impulse residual voltage testing, the sample is cool to room temperature after finishing switching surge operating duty test, and the rate is good as 1.0~1.7%. The element had been considered as applicable ZnO varistor for electricity transmission from the test results of state conterl, switching surge operating duty, thermal stability and above test. But various test should be required for actual application because this is a part of the to be needed for application.

  • PDF

The Analysis of Pressure Relief Technology for ZnO Arrester (ZnO 피뢰기의 Pressure relief 기술 분석)

  • Kim, I.S.;Han, S.W.;Cho, H.G.;Yoo, H.Y.;Kim, H.S.;Park, S.Y.
    • Proceedings of the KIEE Conference
    • /
    • 1998.07d
    • /
    • pp.1450-1452
    • /
    • 1998
  • The chief advantage of polymer arrester, from a handling viewpoint, design of pressure relief, anti-contamination, electrical failuer was reduced by polymer arrester. The life expectancy of polymer arrester depend on a number of design factor. This paper introduced and study : new material housing (silicone composite, EPDM, EPA...), cap type sealing structure, knuckle type electrode, stress relief housing, supporting insulator and sub parts, of polymer arrester.

  • PDF

The Study on the Aging Characteristics of the Arrester Block(ZnO) (피뢰기 소자(ZnO)의 열화특성에 관한 연구)

  • Kim, Chan-Young;Song, Il-Keun;Kim, Ju-Yong;Jeoung, Nyeon-Ho
    • Proceedings of the KIEE Conference
    • /
    • 1998.07d
    • /
    • pp.1459-1461
    • /
    • 1998
  • This paper provides the results of analysis of lightening arrester failed in the field. XRD was used for qualitative analysis and SEM for microstructure analysis of zinc oxide (ZnO) block. The failure of lightening arrester might occur due to the following reasons: the uneven size of zinc oxide grains and cement layers. the re-crystallization of zinc oxide grains resulting from electrical stress around impurities, and the presence of too large pores($\simeq$ 50 ${\mu}m$).

  • PDF

Fracture and Protection Technologies against Impulse of Power Arresters (전력용 피뢰기의 임펄스에 의한 파손과 대척 기술)

  • 한세원;조한구;김석수
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2001.07a
    • /
    • pp.190-193
    • /
    • 2001
  • ZnO varistors have been widely used to protect power system and electronic system against overvoltages based on their excellent nonlinearity. In order to increase their protection capability, the fracture and protection technologies of arresters have to study according to their applications, namely ImA DC voltage, leakage currents, impulse residual voltages, withstanding capability to impulse surge, and energy absorption capability. ZnO varistors which have nonlinear current-voltage characteristic name a number of failure mechanism when ZnO elements absorb surge energies. Failure mode by thermal stress and Pin hole are among the most common failure mechanism at the high current surge current. In this study, the fracture mechaism of power arresters are introduced and protection technologies are researched. In particular the effect of thermal stress by surge currents to ZnO elements and methods against arc surge energy through withstand structure design of arrester are discussed.

  • PDF

A Study on the Improvement of ZnO Varistor for Distribution Class Surge Arrester(18kV, 5kA) (배전급 피뢰기(18kV, 5kA)용 산화아연바리스타의 성능향상에 관한 연구)

  • Yoo, Deok-Son;Yoon, Han-Soo;Kim, Suk-Soo;Choi, Yeon-Gyu;Jang, Sung-Do
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2003.07b
    • /
    • pp.744-746
    • /
    • 2003
  • A ZnO varistor with reference voltage 250V/mm was fabricated through the control of particle size in slurry and the variation of sintering conditions. It was found that to measure the flatness of the V-I characteristic curve in the small-current region and the flatness of the V-I characteristic curve in a large-current region was improved nonlinearity of the fabricated ZnO varistor. According to the IEC 60099-4 was measured the accelerated aging test and high current test of the distribution class surge varistor which is excellent in respect to the property of ZnO varistor.

  • PDF

Leakage Current Characteristics of 18kv ZnO Lightning Arresters by Accelerated Aging Test (가속열화시험에 의한 18kV ZnO 피뢰기의 누설 전류 특성 분석)

  • Kim, Ju-Yong;Song, Il-Geun;Kim, Chan-Yeong;Mun, Jae-Deok
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.51 no.2
    • /
    • pp.62-67
    • /
    • 2002
  • This paper provides the results of accelerated aging test of 18kV ZnO lightning arresters to investigate the leakage current characteristics. It was impossible to establish the replacement criterion for field operating lightning arrester because conventional aging test was only focused on the aging of ZnO elements. In general, it is possible to replace the aged arresters before the failure in the field using the leakage current measurement because it must be increased by the aging. But we can not use the method because we don't know the characteristics of the installed lightning arresters. Therefore in this paper we applied operating voltage and accelerating cycle which consists of temperature and humidity to the arresters. Then we measured the variation of total and resistive leakage current and found out the characteristics of the acted lightning arresters.

Influence of Harmonics in Power System Voltage on Arrester Deterioration Diagnostics by Leakage Current Measurement (누설전류측정에 의한 피뢰기 열화진단에 있어 전원고조파의 영향)

  • 길경석;한주섭;주문노
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.52 no.1
    • /
    • pp.42-46
    • /
    • 2003
  • Arresters are deteriorated by overvoltages or impulse currents, and the resistive leakage current of arresters increases as the deterioration of the arrester progresses, showing an increase in the 3$^{rd}$ harmonic component of the leakage current. In this reason, arrester diagnostic techniques based on the 3$^{rd}$ harmonic leakage current as a reference parameter of deterioration are widely used. The technique, however, includes an error due to the harmonics of power system voltage. Therefore, the influence of the harmonics on arrester diagnostics should be considered. In this paper, we designed a PSpice ZnO arrester model to simulate the influence of the voltage harmonics described above. A pure sinusoidal voltage and its the 3r harmonic voltage were applied to the model, and the leakage current components were analyzed. From the simulation results, it is confirmed that the peak value of resistive leakage current depends not only on the phase of the 3$^{rd}$ harmonic voltage but also on the magnitude of it. Consequently, the errors caused 1)y the harmonic voltage could be minimized by correcting the magnitude of leakage current upon analyzing the harmonics.cs.