• Title/Summary/Keyword: Water-to-refrigerant

Search Result 211, Processing Time 0.027 seconds

Performance evaluation of R22 alternative refrigerants (R22 대체냉매의 성능 평가)

  • 송용재;박봉진;정동수;김종보
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.10 no.3
    • /
    • pp.292-302
    • /
    • 1998
  • In this study, 14 refrigerant mixtures composed of R32, R125, R134a, R143a, R152a, and R1270(Propylene) were tested in a breadboard heat pump in an attempt to replace R22 used in most of the residential air conditioners and heat pumps. The heat pump was of 1 ton capacity and water was employed as the secondary heat transfer fluids. All tests were conducted under ARI test A condition. Ternary mixtures composed of R32, R125, and R134a were shown to have 4∼5% higher COP and capacity than R22 and hence they seem to be very promising candidates to replace R22. On the other hand, ternary mixtures containing R125, R134a, and R152a have lower COP and capacity than R22. R32/R134a binary mixtures show a 7% increase in COP and have the similar capacity to that of R22 and hence they are also good candidates to replace R22. Special care must be exercised when a suction line heat exchanger is used with these mixtures in air conditioners. Finally, the compressor discharge temperatures of all mixtures tested were lower than those of R22 by 15.g∼34.7t, which indicates that these mixtures would offer better system reliability and longer life time than R22.

  • PDF

A Study on Finned Tube Used in Turbo Refrigerator(II) - on boiling heat transfer - (터보 냉동기용 핀 튜브에 관한 연구(II) - 비등 열전달에 관하여 -)

  • Han, Kyu-Il;Kim, Si-Young;Cho, Dong-Hyun
    • Journal of Fisheries and Marine Sciences Education
    • /
    • v.5 no.2
    • /
    • pp.119-127
    • /
    • 1993
  • This work studies for heat transfer and pressure drop performance of integral inner and outer fin tubes, designed to enhance the heat transfer performance of smooth tubes for in recipro and turbo refrigerator or high performance compact heat exchangers. Eight different inner spiral fin copper tubes with integral fin at outside surfaces were employed to improve boiling heat transfer coeffcient. For comparison, tests were made using a plain tube having the inside diameter and an outside diameter equal to that at the root of the fins for the finned tubes. Pool boiling heat transfer is investigated experimentally and theoretically on single tube arrangement. The refrigerant evaporates at a saturation state of 1 bar on the outside tube surface heated by hot water. The refrigerant R11 ($CFCl_3$) was used at a pressure of $P_s=1bar$ as a convenient test fluid with a boiling temperature of $T_s=23.6^{\circ}C$. The observed heat transfer enhancement of boiling for finned tubes significantly exceeded that to be expected on grounds of increased area. The maximum Vapor - side enhancement(i.e., vapor - side heat transfer coefficient of finned tube/vapor - side coefficient for plain tube) was found to be around 4 at 1299fpm - 30grooves tube.

  • PDF

Basic performance analysis of ocean thermal energy conversion using the refrigerant mixture R32/R152a (R32/R152a 혼합냉매를 적용한 해양온도차발전의 기초성능해석)

  • Cha, Sang Won;Lee, Ho Saeng;Moon, Deok Soo;Kim, Hyeon Ju
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.38 no.4
    • /
    • pp.502-507
    • /
    • 2014
  • In this paper, performance characteristics of cycles were studied when mixed working fluid was used for ocean thermal energy conversion (OTEC). Among the various mixed refrigerants for industrial heat-pump, R32/R152a used in ocean thermal energy conversion system. For simulations, R32/R152a were used in existing closed cycle and Kalina cycle which is used only ammonia and water as mixed refrigerant. Temperature of the warm heat source was 26 and 29 celsius degree, temperature of the cold heat source was 5 celsius degree. In results of simulation, Gross power of the closed cycle on R32 was 22kW, and efficiency of the cycle was 2.02%. When the mixed refrigerant of R32/R152a, in the ratio of 90 to 10, gross power of the closed cycle was 29.93kW, and efficiency of the cycle was 2.78%. Gross power and cycle efficiency of R32/R152a increased by 36% and 37% than those of existing single refrigerant. Additionally, the same simulations were conducted in Kalina cycle with the same various composition ratio of mixed refrigerant.

Cooling Enhancement Potential of an Air-Cooled Condenser by Evaporative Cooling (증발냉각에 의한 공랭 응축기의 성능향상 가능성에 관한 연구)

  • 이대영;백영진;김영일
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.16 no.3
    • /
    • pp.203-210
    • /
    • 2004
  • This paper describes the potential advantages in applying evaporative cooling to air-cooled condensers. The cooling characteristics of an air-cooled condenser with its surface fully covered with thin water film are investigated and compared with that of an air-cooled condenser with usual dry surface. By applying the evaporative cooling, the cooling performance of the condenser is shown to improve enormously. When the outdoor air is 35$^{\circ}C$ and 40% in relative humidity, the condensing temperature of the refrigerant is decreased by 2$0^{\circ}C$. Even when the incoming air is fully saturated with water vapor, the evaporation from the wet surface occurs to cause a decrease in the condensing temperature by 1$0^{\circ}C$. The main reason for this improvement is assessed as the addition of an efficient cooling mechanism which is the water evaporation resulting in latent heat absorption.

Analysis of Heat Transfer Performance of a Gas Cooler of CO2 Heat Pump for Water Heating (온수제조용 CO2 히트펌프의 가스쿨러 열전달 성능 해석)

  • Kwon, Jeong-Tae;Lee, Chang-Kyung;Baek, Dong-Seok;Kwon, Young-Chul
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.14 no.11
    • /
    • pp.5317-5322
    • /
    • 2013
  • This study presents a prediction method for heat transfer performance of a gas cooler of $CO_2$ heat pump using ${\epsilon}$-NTU method, and compared the results with the experimental data from the open literature. The heat transfer rate, refrigerant side outlet temperature and water side outlet temperature were calculated by using EES(Engineering Equation Solver)program in multi-tube-in-tube type $CO_2$ heat pump gas cooler. Analysis was performed in two methods : The first method performed without dividing into the test section by applying an analysis of the mean properties(mean analysis). The second method, tube length divided into 50 sections, was applied to the local properties(local analysis). From the present study, a good agreement at the local analysis was obtained between the analytical and experimental results by 0.3~1.1%, 1.31~1.88% and 3.12~5.18% for heat transfer rate, water and refrigerant side outlet temperatures, respectively.

Experimental study on the performance of a brazed plate heat exchanger (용접식 판형 열교환기의 성능에 관한 실험적 연구)

  • Kim, Jong-Ha;Yun, Jae-Ho;Kwon, Oh-Kyung;Kim, Jong-Hun;Ryu, Hae-Sung;Lee, Chang-Sik
    • Proceedings of the KSME Conference
    • /
    • 2001.06d
    • /
    • pp.477-482
    • /
    • 2001
  • An experimental study on the performance evaluation of a brazed plate heat-exchanger with 10RT of normal cooling capacity has been carried out. In the present study, a brazed type plate heat exchanger was tested at a chevron angle $25^{\circ}$ with refrigerant R-22. Mass flux was ranged from $23\;to\;58kg/m^{2}s$ in condensation, and from $22\;to\;53kg/m^{2}s$ in evaporation. The heat transfer coefficient and pressure drop increased with the mass flux increases. The water side pressure drop increased with the cooling water flow rate and chilled water flow rate increases, while mass flux has little affect. It is also shown that the system performance can be improved by enlarging condensation heat transfer area.

  • PDF

Growth Characteristics and Plasmid Profiles of Yersinia enterocolitica lsolated from Springs Water (약수터수로부터 분리한 Yersinia enterocolitica의 성장특성 및 Plasmid 유형)

  • 차인호;김미희;이상준
    • Journal of Life Science
    • /
    • v.7 no.3
    • /
    • pp.212-218
    • /
    • 1997
  • The studies were conducted to explore the dffects of growth or survival against various factors and plasmid profiles of 49 Y. enterocolitica isolated from springs water. In the presence of calcium hypochlorite, y. enterocolitica was entirely extinguished by exposure for 33 hours at 0.8 ppm concentration, and was grown up to 7% NaCl, but not at 95 NaCI. Y. enterocolitica was presented optimal growth at pH 7.0 anad 9.0, and not allowth the growth at pH3.0, 5.0 and 11.0. The optimal temperature for growth of Y. enterocolitica was 25$\circ$C and 35$\circ$C, and allowed the growth at refrigerant temperature, 5$\circ$C. Y. enterocolitica was remarkably decreased by exposure for 30 seconds under UV light, and entirely extinguished by exposure for 90 seconds. Therefore, UV light was effective for sterilization of Y. enterocolitica. Fourty-nine strains of Y. enterocolitica were harbor plasmid DNA of approximately 46 Kb molecular weight.

  • PDF

Performance of the Geothermal Heat Pump using Vapor Injection for Hot Water (증기분사를 적용한 고온수용 지열 히트펌프의 성능특성)

  • Park, Yong-Jung;Park, Byung-Duck
    • Transactions of the Korean hydrogen and new energy society
    • /
    • v.25 no.3
    • /
    • pp.297-304
    • /
    • 2014
  • The purpose of this study is to evaluate the experimental performance characteristics of a water-to-water geothermal heat pump featuring a vapor refrigerant injection for the production of hot water. The performance of geothermal heat pump with a vapor injection was evaluated by comparing with that of a conventional geothermal heat pump without a vapor injection. For heating operation, the geothermal heat pump with a vapor injection is superior in COP and heating capacity. The vapor injection was more effective for supplying hot water while overloading. The vapor injection was effective for the improvement of the cooling capacity. However, the vapor injection was not effective for the increasing of COP according to the increased input of a compressor. The advantage of vapor injection in water-to-water geothermal heat pump become disappeared while cooling operation with lower part loading.

An Experimental Study on Pressure drop Characteristics in Plate and Shell Heat Exchanger (Plate and Shell 열교환기내의 R-22 응축압력강하 특성에 관한 실험적 연구)

  • 이기백;서무교;박재홍;김영수
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.25 no.6
    • /
    • pp.1220-1227
    • /
    • 2001
  • The condensation pressure drop fur refrigerant R-22 flowing in the plate and shell heat exchanger were investigated experimentally in this study. Two vertical counterflow channels were formed in the exchanger by three plates of commercial geometry with a corrugated trapezoid shape of a chevron angel of $45^{\circ}$. The condensing R-22 flowing down in one channel exchanges heat with the cold water flowing up in the other channel. The effects of the mean vapor quality, mass flux, average imposed heat flux and system pressure of R-22 on the pressure drop were explored in detail. The quality change of R-22 between the inlet and outlet of the refrigerant channel ranges from 0.03 to 0.05. The present data showed that pressure drop increases with the vapor quality. At a higher mass flux, pressure drop is higher for the entire range of the vapor quality. Also, a rise in the average imposed heat flux causes an slight increase in the Pressure drop. Finally, at a higher system pressure the pressure drop is found to be slightly lower. Correlation is also provided for the measured pressure drops in terms of the friction factor.

  • PDF

Development of a New Refrigerant Mixture (RM-1) to improve the performance of Heat Pump System for Heating and Cooling of the Living Space (생활공간 냉난방용 열펌프의 성능개선을 위한 새로운 혼합냉매(RM-1) 개발)

  • Song, Heon;Ro, Jeong-Geun
    • Journal of the Korean Solar Energy Society
    • /
    • v.31 no.5
    • /
    • pp.67-76
    • /
    • 2011
  • 생활공간 냉난방용 열펌프의 성능향상을 위해 R22의 대체 냉매로서 새로운 혼합냉매R22/R23/R152a(RM-1)을 개발하고 U. S. A.의 NIST사의 REFPRO Pprogram을 이용해 이 혼합냉매의 P-h diagram을 구성하여 실용화에 이용할 수 있도록 하였다. 본 연구는 실험을 통해 R22와 RM-1의 열펌프 성능효과를 분석하였다. 입 출구 물의 온도와 제2의 전열매체로서 물의 질량유량, 압축기의 소요 에너지 그리고 열펌프의 기타 열적 특성을 다양한 조건하에서 측정하였다. 이 실험 데이터를 통해 공기-물 열펌프 시스템에서의 RM-1과 R22의 성능계수(COP)를 비교하였다. 이를 통해, 혼합냉매 RM-1을 사용하는 열펌프 시스템은 외기온 $-17^{\circ}C$에서도 2.2의 성능계수로 작동하는 결과를 본 연구에서 보여주었다.