• Title/Summary/Keyword: Water spray extinguishing system

Search Result 15, Processing Time 0.021 seconds

An Experimental Study of Fire Suppression Using a Water Mist in a Compartment (물분무를 이용한 화재제어에 관한 실험적 연구)

  • Kim, Sung-Chan;Park, Hyun-Tae;Ryou, Hong-Sun
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.27 no.3
    • /
    • pp.367-373
    • /
    • 2003
  • The present study investigates the fire suppression characteristics using a water mist fire suppression system. The fire extinguishing times are measured for various fire sources, fuel types, and different total flooding rates of water mist. Pool fire with hydrocabon fuel is successfully extinguished within a minute under the operating conditions of the water mist system. Two different regimes of the smoke layer cooling are observed, such as rapid and slow cooling processes. The regimes are divided by threshold time which is calculated with auto-correlation function. The threshold time for the initial cooling decreases with increasing water flow-rates and fire sources. These initial cooling effects play an important role in preventing the occurance of flashover fire by the initial fire suppression.

A Fire Scenario for Application of Water Mist System to an Indoor Power Transformer Room (변전소 주변압기실 미분무수 소화시스템 성능평가를 위한 화재시나리오)

  • Choi Byung-Il;Han Yong-Shik;Kim Myung-Bae
    • Fire Science and Engineering
    • /
    • v.19 no.3 s.59
    • /
    • pp.52-57
    • /
    • 2005
  • It has been known that there is not the general design method for water mist system because the fire extinguishing mechanisms are dependent on both spray characteristics and a fire compartment. It is therefore rational that a general performance-evaluation guideline does not exist. The present work suggests the performance-evaluation guideline for water mist system applied to the power transformer room based upon the investigation and analysis of fire accidents and the similar guideline.

Numerical study on the foam spraying for AFDSS applicable to initial fire suppression in large underground spaces (지하대공간 초동 화재진압에 적용가능한 자율형 소화체계의 폼 분사 해석 기법 연구)

  • Park, Jinouk;Yoo, Yongho;Kim, Whiseong
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.23 no.6
    • /
    • pp.503-516
    • /
    • 2021
  • Autonomous fire detection and suppression system requires advanced technology for complex detection technology and injection/control technology for accurate hitting by fire location. Also, foam spraying should be included to respond to oil fires. However, when a single spray monitor is used in common, water and foam spray properties appear different, so for accurate fire suppression, research on the spray trajectory and distance will be required. In this study, experimental studies and numerical analysis studies were combined to analyze the foam spray characteristics through the spray monitor developed for the establishment of an autonomous fire extinguishing system. For flow analysis of foam injection, modeling was performed using OpenFOAM analysis software, and the commonly used foaming agent (Aqueous Film-Forming Foam) was applied for foam properties. The injection distance analysis was performed according to the injection pressure and the injection angle according to the form of the foam, and at the same time, the results were verified and presented through the injection experiment.

A study on use of quantitative risk analysis on life safety performance for the effect of fixed fire fighting system at road tunnel fires (정량적 위험성 평가를 활용한 도로터널 화재시 물분무 소화설비의 피난 안전 효과 연구)

  • Park, Kyung-Hwan;Yoo, Ji-Oh
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.14 no.1
    • /
    • pp.1-22
    • /
    • 2012
  • This paper tried to verify whether the fixed fire fighting system (FFFS) that is installed in road tunnel improves evacuation performance or not. Verification was performed according to the Disaster Prevention Facilities Installation and Management Guide at Road Tunnel. Twenty seven different fire scenarios were set up for the verification and the cases that FFFS was installed were compared with the cases that FFFS was not installed. The result of the comparison showed that the average equivalent death was reduced in 26 cases out of 27 cases when water spray extinguishing system was installed. It was confirmed that the risk when was not installed was unacceptable in Hong Kong and the Netherlands. On the other hand, it was confirmed that the risk was reduced to as low as reasonably practicable (ALARP) when was installed. The cumulative frequency of average death in case with FFFS was compared against the frequency of death without FFFS: death of one or more is about 50 times less; 10 or more is about 100 times less; and the death of more than 100 is four times less. It was verified that FFFS makes improved conditions to escape from the fires in road tunnel.

A Study on Improvement of Discharge Obstruction Prevention Standard for Sprinkler Head on NFSC 103 (스프링클러설비 소화성능 향상을 위한 NFSC 103 살수장애 방지기준 개선 방안에 관한 연구)

  • Kim, Sunghyun;Lee, Sungsu
    • Journal of the Society of Disaster Information
    • /
    • v.16 no.2
    • /
    • pp.237-247
    • /
    • 2020
  • Purpose: This study aims to draw the problems and improvements of NFSC 103 sprinkler head discharge obstruction prevention standard to increase the fire extinguishing performance of sprinkler system in order to contribute to the protection of people's lives and property in the event of a fire. Method: NFSC 103 was compared to NFPA 13 which is the latest 2019 version in U.S in terms of sprinkler head discharge obstruction prevention. Results: This study found that NFSC 103 doesn't define even the basic concept of sprinkler discharge obstruction. And NFSC 103 doesn't have detailed standard for side wall sprinkler head discharge obstruction prevention as well as the "height" criteria of the "three times" separation rule. Conclusion: NFSC 103 needs a lot of supplements and improvements such as the addition of definition for water discharge obstructions, the adoption of sidewall sprinkler heads standard for preventing water discharge obstructions and the additional establishment of the "three times rule" considering the "height" of obstacles to promote the advance of fire safety standard equal or above fire fighting advanced country and increase the reliability for the suppression performance of sprinkler system.