Statistical analysis of hazen-williams C and influencing factors in multi-regional water supply system (광역상수도 유속계수와 영향인자에 관한 통계적 분석)

  • Kim, Bumjun;Kim, Gilho;Kim, Hung soo
    • Journal of Korea Water Resources Association
    • /
    • v.49 no.5
    • /
    • pp.399-410
    • /
    • 2016
  • In case of the application of Hazen-Williams C for design, operation or maintenance of water supply system, field situations always should be reflected on the factors. In this study, the relationships between C factors and influencing factors are analyzed using statistical techniques with 174 measured C factor data collected in periodic inspection for safety diagnosis in multi-regional water supply systems. To analyze their relationships, cross analysis, one-way ANOVA, correlation analysis were conducted. Analysis results showed that C factors had high correlations with both of elapsed year and pipe diameter and were relatively highly affected by coating material among influencing factors with the categorical type. On the other hand, elapsed year, pipe diameter and water type were meaningful influencing factors according to the results of multiple regression analysis. The Cluster analysis revealed that C factors had a tendency of being fundamentally classified on the basis of the elapsed year of about 20 years and the pipe diameter of 1500mm. Although C factors were generally greatly affected by elapsed year, size of pipe diameter relatively had an large influence on values of them in case of large diameter pipes. Lastly, It can be suggested that C factor estimation formulas using multiple regression analysis and clustering analysis in this study, can be applied as decision standards of C factor in multi-regional water supply systems.

Consideration of Pressure-Rise and Water Hammer for Pipe System in Relation to Start-Up and Sudden Stop of the Pump (펌프 기동 및 정지에 따른 배관 압력상승과 수격작용 영향 고찰)

  • Heo, Min Woong;Min, Ji Ho
    • Transactions of the Korean Society of Pressure Vessels and Piping
    • /
    • v.13 no.1
    • /
    • pp.69-74
    • /
    • 2017
  • In the fire protection system or fire fighting water supply system, the jockey pump is generally installed for the prevention of the pressure decrease of pipes, the frequent driving of the fire pump and protection the pipes from the water hammer. In this paper, the pressure-rise in fire fighting water distribution pipes in condition of pipe pressurization by the surge tank at the start-up and the sudden-stop of the fire pump without additional installation of jockey pump is considered by using simple formula calculations and the evaluation of water hammer occurrence in condition of pipe pressurization by the surge tank is included. As a result, the pressure-rise of pipes is less than the pipe design pressure at the condition of pump's start-up and sudden stop, and the possibility of water hammer occurrence is remarkably low due to pressurization of the pipes by the surge tank.

Investigating coating material and conditions for rehabilitation of water transmission pipe using a robotic system (자동화 장비를 이용한 대형 상수관로 갱생을 위한 코팅재료 선정 및 방법에 관한 연구)

  • kim, Jinwon;Kim, Donghyun;Lee, Younggun;Lee, Sewan;Kim, Dooil
    • Journal of Korean Society of Water and Wastewater
    • /
    • v.30 no.6
    • /
    • pp.725-736
    • /
    • 2016
  • There is a growing concern on the improvement of water distribution pipeline for multi-regional water supply system in Korea along with its aging infrastructure. Rehabilitation of large diameter pipeline is more efficient in cost and time compared to replacement with trenching. The procedure for rehabilitation are diagnosis, cleaning, spraying coating material, and final inspection. The internal state of pipeline was carefully diagnosed and got C grade, which required rehabilitation. We found that 17,274,787,000 Korean won could be saved after pipe surface coating because of increased C coefficient of Hazen-Williams equation. Optimal coating material was D polyurea. We also found optimal distance between spraying nozzle and pipe wall to be 70 - 80 cm, which were critical factors for coating quality. This study also illustrated the time for spray drying to be more than 30 min. These results could be used in the quality control process during rehabilitation of aged pipelines.

Characteristics and control of intermittent flow in water distribution systems due to restricted supply (상수도관망에서 제한급수에 따른 간헐적 흐름의 특성 및 제어)

  • Yang, Kangseung;Kim, Donghong;Jung, Kwansoo;Kim, Juhwan
    • Journal of Korean Society of Water and Wastewater
    • /
    • v.28 no.1
    • /
    • pp.1-11
    • /
    • 2014
  • The water distribution system should be invariably operated on continuous pattern for 24 hours a day. Occasionally, it is not practically possible to operate for 24 hours due to water shortage or financial constraints. Therefore an intermittent water supply is unavoidable in water shortage area and developing countries. But the intermittent water supply can introduce large pressure forces and rapid fluid accelerations into a water supply network. These disturbances may result in new pipe failure, leakage and secondary contamination. This paper proposed an improvement methodology to prevent the disturbances by intermittent water supply. For the study, the hydraulic variation of intermittent flow in water distribution system was measured and analyzed in the field by comparing with simulation of hydraulic model. Installations of control valves such as, pressure reducing and sustaining and air valves were employed for pressure and flow control. The effectiveness of the methods are presented by comparing hydraulic conditions before and after introducing the proposed solutions.

Analysis of Operating and Maintenance Parameters for Agricultural Pipeline System Using EPANET (EPANET을 이용한 농업용 관수로 시스템의 운영 및 유지관리 인자 분석)

  • Kim, Nam Do;Kim, Sun Joo;Kwon, Hyung Joong;Kim, Phil Shik;Park, Hyun Jun
    • Journal of The Korean Society of Agricultural Engineers
    • /
    • v.59 no.4
    • /
    • pp.17-26
    • /
    • 2017
  • In this study, EPANET model which is using on the pipe network analysis was applied to Haenam irrigation district has provided irrigation water by pipeline system about 1,125ha and then have built pipe network to study area and supply performance evaluation of existing structure was analyzed by SPA (Single Period Analysis) in EPANET. As model results of simulation average ratio of maximum supply quantity/irrigation water requirements(base demand) was analyzed by 2.63. It means also that was analyzed as being capable of ensuring the water supply capacity. It was provided the necessary information for the maintenance facility through analyzed hydraulic behaviors in the pipeline inside such as flow velocities, pressures and hydraulic grade lines. It was satisfied with the allowable design criteria that was compared analyzed results with presented allowable design standards at agricultural production infra improvement project planning and design (Pipeline design standard). In order to analyze efficiency promotions of irrigation water, using Extended Period Simulation it was compared supply quantity with irrigation water requirements while pumps set operating pattern in 24 hours, then efficiency promotions of irrigation water was determined through analyzed oversupply water quantity and occurrence time by branch lines. According to results for oversupply quantity in Haenam district by time and end of branch lines efficiency promotions of irrigation water was suggested from 0.33 % to 37.59 %. To draw reasonable operating rules for water use and through this research, it is expected to be helpful for efficient water use and operational management of agricultural pipeline system to the current agricultural irrigation.

An Experimental Study on the Sterilizing and Antibacterial Performance of Polybutylene Pipe with Nano-Silver (은나노 입자를 함유한 폴리부틸렌관의 살균 및 항균성능에 관한 실험적 연구)

  • Choi Sang-Gon;Hong Jin-Kwan;Kim Yong-Bong;Yang Chan-Mo;Park Min-Kyu
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.18 no.7
    • /
    • pp.549-555
    • /
    • 2006
  • In the present study, sterilizing and antibacterial performance tests of Polybutylene pipe with nano-silver were carried out in the testing bench of water supply facilities. Experimental results show that the average sterilizing and antibacterial rate of two micro-biological samples such as E. coli and S. aureus is about 90% in case of stillness experimental condition and 99% in case of flowing experimental condition, when elapsed time is 120 hours and 3 hours, respectively. Experimental results also show that the supply water velocity in nano-silver Polybutylene pipe varies from 1 m/s to 1.5 m/s, the elapsed time needed sterilizing rate reach to 100% decreases.

An Experimental Study on the Heat Transfer Characteristics of Stainless-Acetone Heat Pipe (스테인리스-아세톤 히트파이프의 열전달 특성에 관한 실험적 연구)

  • Kang, K. C.;Kim, Y. J.;Ryou, Y. S.;Baek, Y.;Rhee, K. J.
    • Journal of Biosystems Engineering
    • /
    • v.25 no.6
    • /
    • pp.489-496
    • /
    • 2000
  • This study was conducted in order to find an ideal working fluid kind and a proper filling amount in the heat pipe as well as an inclined angle of heat pipe when they are placed to recover exhaust gas heat in the hot air heater. Followings are the findings of this research. 1. Of the four different working fluids-gasoline kerosene distilled water and acetone-acetone filled heat pipe showed the best performance giving out more homogeneous temperature profile on the radiating part than the kerosene and gasoline heat pipe an carrying out heat transmitting function better than the distilled water heat pipe by 10~2$0^{\circ}C$ higher on the radiating part. Acetone would be a good choice for recycling of exhaust gas heat in the hot air heater. 2. Of the filling amount of working fluid inside the heat pipes dry-out situations possible caused by insufficient filling were found in the filling amount of 5, 7.5 and 10% heat pipes as heat supply rate increases gradually in the range of 50 to 15kJ/sec. but no dry-out and stabilized heat transmitting performance occurred in the heat pipes of 12.5 and 15% filling at the same heat supply rate. It recommends that filling amount shall exceed 12.5% at least with the working fluids of this experiment. 3. The test revealed that the heat transmitting performance of heat pipe was more affected by filling amount rather than inclined angle.

  • PDF

Artificial Intelligence-based Leak Prediction using Pipeline Data (관망자료를 이용한 인공지능 기반의 누수 예측)

  • Lee, Hohyun;Hong, Sungtaek
    • Journal of the Korea Institute of Information and Communication Engineering
    • /
    • v.26 no.7
    • /
    • pp.963-971
    • /
    • 2022
  • Water pipeline network in local and metropolitan area is buried underground, by which it is hard to know the degree of pipe aging and leakage. In this study, assuming various sensor combinations installed in the water pipeline network, the optimal algorithm was derived by predicting the water flow rate and pressure through artificial intelligence algorithms such as linear regression and neuro fuzzy analysis to examine the possibility of detecting pipe leakage according to the data combination. In the case of leakage detection through water supply pressure prediction, Neuro fuzzy algorithm was superior to linear regression analysis. In case of leakage detection through water supply flow prediction, flow rate prediction using neuro fuzzy algorithm should be considered first. If flow meter for prediction don't exists, linear regression algorithm should be considered instead for pressure estimation.

Expert System for Emergency Decision Making for Metro Water Supply Systems (광역상수도 시설의 비상시 의사결정을 위한 전문가시스템)

  • Kim, Eung Seok;Kim, Joong Hoon;Baek, Chun Woo;Lee, Jung Ho
    • Journal of Korean Society on Water Environment
    • /
    • v.23 no.1
    • /
    • pp.103-110
    • /
    • 2007
  • An efficient operational strategy using expert system for metro water supply systems in case of emergency situations is developed in this study. The emergency situations of the water supply systems are classified into three categories : pipeline system accident, machinery and electric facility accident and water quality accident. A PC-based expert system is developed using CLIPS for Seoul metro water supply system, Phase 1 & 2 system and Phase 3 & 4 system. Broad professional knowledges and experiences from the experts in the water supply systems have been collected systematically to construct the knowledge base. Decision-making in case of an emergency is based upon the professional knowledge so that a rational and efficient operational management can be available even in the absence of experienced expert. Especially the expert model developed in this study also provides a guide for pumping operation in case of pipeline accident to confirm that the proper pressure to all nodes in the system is supplied. The pipe network simulator KYPIPE has been consecutively executed by trial and error fashion for each pipeline in the system. The results from KYPIPE were included in the knowledge base to supplement the knowledge of the field engineers.

Water pipe deterioration assessment using ANN-Clustering (ANN-Clustering 기법을 이용한 상수관로 노후도 평가 및 분류)

  • Lee, Sleemin;Kang, Doosun
    • Journal of Korea Water Resources Association
    • /
    • v.51 no.11
    • /
    • pp.959-969
    • /
    • 2018
  • The aging water pipes induce various problems, such as water supply suspension due to breakage, insufficient water pressure, deterioration of water quality, damage by sink holes, and economic losses due to water leaks. However, it is impractical and almost impossible to repair and/or replace all deteriorated water pipes simultaneously. Hence, it is required to quantitatively evaluate the deterioration rate of individual pipes indirect way to determine the rehabilitation order of priority. In this study, ANN(Artificial Neural Network)-Clustering method is suggested as a new approach to assess and assort the water pipes. The proposed method has been applied to a water supply network of YG-county in Jeollanam-do. To assess the applicability of the model, the evaluation results were compared with the results of the Numerical Weighting Method (NWM), which is being currently utilized in practice. The assessment results are depicted in a water pipe map to intuitively grasp the degree of deterioration of the entire pipelines. The application results revealed that the proposed ANN-Clustering models can successfully assess the water pipe deterioration along with the conventional approach of NWM.