• Title/Summary/Keyword: Water Absorption Test / Diagnosis

Search Result 7, Processing Time 0.023 seconds

A Study on the Water Absorption Diagnosis Method through Capacitance Measurement for Generator Stator Windings (발전기 고정자 권선의 정전용량 측정을 통한 흡습 진단 방법에 관한 연구)

  • Kim, Hee-Soo;Bae, Yong-Chae;Kee, Chang-Doo
    • Journal of the Korean Society for Precision Engineering
    • /
    • v.23 no.11 s.188
    • /
    • pp.50-57
    • /
    • 2006
  • The water leak in water-cooled generator stator windings can generate the serious accidents such as insulation breakdown and it brings a generator to the unexpected sudden outage. Accordingly, it is important to diagnose the water absorption of them for the effective operation of power plant. Especially, the capacitance value which is measured for diagnosis is very small so the special diagnosis methods like stochastic theory are needed. KEPRI developed the water absorption test equipment and diagnosis technology for them. The developed diagnosis technology is applied to the real system and the results of water absorption test for stator windings are agreed to them of water leak test.

A Study on the Water Absorption Test of Generator Stator Windings Using Probability Distributions (여러 가지 확률분포를 이용한 발전기 고정자 권선의 흡습 시험에 관한 연구)

  • Kim, Hee-Soo;Bae, Y.C.;Kim, Hee-Jeong;Na, Myung-Hwan
    • The Korean Journal of Applied Statistics
    • /
    • v.22 no.5
    • /
    • pp.961-969
    • /
    • 2009
  • Water absorption in water-cooled generator stator windings can cause serious accidents such as insulation breakdown and it brings a generator to the unexpected sudden outage. Accordingly, it is important to diagnose the water absorption of them in the effective operation of power plant. Especially, the capacitance value which is measured for diagnosis is very small so the special diagnosis methods like stochastic theory are needed. KEPRI developed the water absorption test equipment and diagnosis technology for them. In this paper we propose that water absorption test of generator stator windings using probability distributions. The proposed diagnosis technology is applied to the real system and the results of water absorption test for stator windings are agreed to them of water leak test.

A Study on the Diagnosis for Water Absorption of Generator Stator Windings (발전기 고정자 권선의 흡습 진단)

  • Bae Y.C.;Kim H.S.;Lee D.Y.
    • Proceedings of the Korean Society of Precision Engineering Conference
    • /
    • 2006.05a
    • /
    • pp.297-298
    • /
    • 2006
  • Water leak for the water-cooled generator stator windings affects seriously the availability and the reliability of power plants. Generally, water absorption test is conducted in the power plant during outage in order to confirm if leak part is in the bars or not. In this paper, it is described that the capacitance of winding bars is measured by using the developed water absorption instrument system and the water absorption of winding bars is evaluated by using the stochastic methods. The good results by proposed diagnosis technique can be got. It is expected that the reliability of diagnosis for water absorption is increased if the proposed methods are applied to evaluate the water absorption of stator winding bars.

  • PDF

Study on Reliability of Water Absorption Diagnosis through Precise Water Absorption Test

  • Kim, Hee-Soo;Bae, Yong-Chae;Kim, Hee-Dong
    • Journal of Electrical Engineering and Technology
    • /
    • v.7 no.5
    • /
    • pp.772-777
    • /
    • 2012
  • Accidents caused by water absorption in water-cooled generator stator windings often occur all over the world. The absorption into the insulator of the coolant, which is used to cool down the heat generated by stator windings during operation, leads to the deterioration of dielectric strength, and insulation breakdown. An insulation breakdown may cause not only an enormous economic loss but also a very serious grid accident that would compromise stable supply of electric power. More than 50 % of domestic generators have been in operation for more than 15 years, and water absorption tests performed on 50 water-cooled generator stator windings during a five-year planned preventive maintenance period beginning in 2006 identified water absorption problems in 10 of them, all of which required repair. Because the existing water absorption test detects this problem by utilizing stochastic methods after measuring the capacitances at the final positions of insulation breakdown, its accuracy is limited. This study demonstrates that water absorption can be more accurately diagnosed by utilizing method along with a more precise one.

Experimental Study on Prediction and Diagnosis of Leakage and Water Absorption in Water-Cooled Generator Stator Windings by Drying Process Analysis (수냉각 발전기 고정자 권선의 건조 과정 분석을 통한 누설 및 흡습 예측 진단에 관한 실험적 연구)

  • Kim, Hee-Soo;Bae, Yong-Chae;Lee, Wook-Ryun;Lee, Doo-Young
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.34 no.9
    • /
    • pp.867-873
    • /
    • 2010
  • The failure of water-cooled generator stator windings as a result of insulation breakdown due to coolant water leaks and water absorption often occurs worldwide. Such failure can cause severe grid-related accidents as well as huge economic losses. More than 50% of domestic generators have been operated for over 15 years, and therefore, they exhibit signs of aging. Leaking and water-absorbing windings are often found during an overhaul. In an existing method for evaluating the integrity of generator stator windings, the drying process of the interior of the windings is ignored and only final leak tests are performed. In this study, it is shown that water leaks and water absorption in stator windings can be detected indirectly through vacuum pattern analysis in the vacuum drying mode, which is the used in the preparation stage of the leak test.